INOTEC – Conformity certificate with central battery systems
1. OTi DALI Linear non isolated1.1 OTi DALI 60/220-240/550 D LT2 L1.2 OTi DALI 90/220-240/1A0 LT2 L
2. OTi DALI Linear SELV2.1 OTi DALI 35 /220-240/700 LT2 L2.2 OTI DALI 50/220-240/1A4 LT2 L2.3 OTI DALI 80/220-240/2A1 LT2 L
3. OTi DALI Ultraflat3.1 OTi DALI 35/220-240/350 D LT2 UF L3.2 OTI DALI 75/220-240/700 D LT2 UF L
4. OTi DALI Compact SELV4.1 OTi DALI 15/220-240/1A0 LT24.2 OTi DALI 25/220-240/700 LT24.3 OTi DALI 35/220-240/1A0 LT24.4 OTI DALI 50/220-240/1A4 LT2 FAN
(VII/2015)
INOTEC Sicherheitstechnik GmbH
Technische Anforderungen an elektrische Betriebsgeräte für LEDs
zum Anschluss an INOTEC Zentralbatteriegeräte
Hersteller: Typ / Bezeichnung:
OSRAM
OTi DALI 60/220-240/550 LT2
Projekt / Projektort: Projektnummer:
Marcel-Breuer-Straße 6, 80807 München
Merkmale Techn. Daten / INOTEC Anforderung Erklärung Erfüllt (Ja / Nein) Betriebsspannungsbereich AC 230V ± 10% Spannungsbereich im Netzbetrieb Ja
Betriebsspannungsbereich DC 186V - 260V Möglicher Batteriespannungsbereich im Notstrombetrieb Ja
Betriebsgerät geeignet für "Joker-Spannung" ?
B2-Gleichrichtung der Netzspannung (ohne Glättung)
ungeglättete Gleichspannung (hochgeklappte Halbwelle)
Ja
Betriebsgerät kompatibel mit der Umschaltzeit der Anlage ?
Umschaltzeit: 150 - 1000ms
Typische Umschaltzeit von INOTEC Anlagen zwischen Netz- und Ersatzstromquelle Ja
Startverhalten Betriebsgerät im DC- Betrieb
Stabile Stromaufnahme innerhalb von 1,6s Notwendig für Fehlererkennung der Einzelleuchtenüberwachung Ja
Betriebsgerät erfüllt die Norm: (nur für Leuchtstofflampe)
DIN EN 60929 Wechsel- und/oder gleichstromversorgte elektronische Betriebsgeräte für
röhrenförmige Leuchtstofflampen - Anforderung an die Arbeitsweise
N/A
Betriebsgerät erfüllt die Norm: (nur für Leuchtstofflampe)
DIN EN 61347-2-3 (incl. Anhang J) Besondere Anforderungen an wechsel-und/oder gleichstromversorgte
elektronische Betriebsgeräte für Leuchtstofflampen
N/A
Betriebsgerät erfüllt die Norm: (nur für LED)
DIN EN 62384 Gleich- oder wechselstromversorgte elektronische Betriebsgeräte für LED-
Module- Anforderungen an die Arbeitsweise
Ja
Betriebsgerät erfüllt die Norm: (nur für LED)
DIN EN 61347-2-13 Besondere Anforderungen an gleich- oder wechselstromversorgte elektronische
Betriebsgeräte für LED-Module
Ja
Betriebsgerät erfüllt die Norm: DIN EN 55015 (Messung bei AC und DC)
Grenzwerte und Messverfahren für Funkstörungen von elektrischen Beleuchtungseinrichtungen und ähnlichen Elektrogeräten
Ja
Betriebsgerät erfüllt die Norm:
DIN EN 61000-3-2
Elektromagnetische Verträglichkeit (EMV) - Teil 3-2: Grenzwerte -Grenzwerte für Oberschwingungsströme (Geräte-Eingangsstrom ≤ 16A je Leiter)
Ja
Betriebsgerät erfüllt die Norm: DIN EN 61547 Einrichtungen für allgemeine Beleuchtungszwecke -
EMV-Störfestigkeitsanforderung
Ja
Betriebsgerät erfüllt die DALI- Normen DIN EN 62386-101/-102/-207*1 Das EVG muss das DALI Logo tragen Ja Hinweis: Die Kennzeichnung "gemäß VDE 0108" ist nicht aussagekräftig, da dieses keine EVG-Gerätenorm ist.
Merkmale Techn. Daten / INOTEC Anforderung Erklärung Angabe Hersteller Nennstrom des Betriebsgerätes mit angeschlossenem Leuchtmittel im AC Betrieb (230V)
Auswahlhilfe zur Bestimmung der maximal zulässigen Anzahl Leuchten je Stromkreis
294,14 mA
Nennstrom des Betriebsgerätes mit angeschlossenem LED-Modul im DC Betrieb (216V)
Auswahlhilfe zur Bestimmung der benötigten Batteriekapazität
300,9 mA
Verhalten des EVGs im DC-Betrieb - nicht gesperrter Dimmlevel - gesperrter Dimmlevel (Dimming on DC)
Die Dimmleveleinstellung des DALI-SV-Moduls ist nur möglich bei nicht gesperrtem Dimmlevel im DC-Betrieb
Bei gesperrtem Dimmlevel im DC-Betrieb kann das DALI-SV-Modul den Lichtstrom nicht einstellen !
gesperrter Dimmlevel
Verhältnis des Ausgangsstromes bei DC-Betrieb vs. AC-Betrieb
Keine Regelung des Lichtstroms durch das DALI-SV-Modul im DC-Betrieb
Fester Ausgangss trom des DALI-EVGs bei gesperrtem Dimmlevel im DC-Betrieb. Wichtig für die Lichtplanung der Sicherheitsbeleuchtung
15%
Verwendung des DALI Komandos 146 (Query Lamp Failure) gem. IEC 62386 Part 102
Erfüllt die IEC 62386 Teil 102
Wichtig für den Funktiontest: Um einen Leuchtenfehler zu detektieren, sendet das DALI-SV-Modul das DALI Komando 146 zum DALI EVG
Ja
Max. Einschaltstrom des Betriebsgerätes mit angeschlossenem Leuchtmittel im AC Betrieb (230V)
Zulässiger Gesamteinschaltstrom je Stromkreis: SK 4x2A: 250A / 500µs SK 2x4A: 250A / 500µs SK 2x3A: 250A / 500µs SK 1x6A: 250A / 500µs
Bezieht sich auf den maximal zulässigen Einschaltstrom aller Leuchten in einem Stromkreis, um die maximale Kontaktbelastbarkeit der Stromkreisschaltungen zu berücksichtigen (*2)
24A / 240µs
Leuchten, die für den Einsatz als Sicherheitsleuchte vorgesehen sind, müssen u.a. der Norm DIN EN 60598-2-22 (Besondere Anforderungen - Leuchten für Notbeleuchtung) entsprechen. *1: Die Ansteuerung des DALI-SV-Moduls zum DALI EVG erfolgt zu 100% über DALI Kommandos gem. IEC 62386-101/-102, so ist es zwingend erforderlich, dass das DALI EVG das DALI-Logo trägt. *2: zur Planung muss der Einschaltstrom des Überwachungsmoduls mit berücksichtigt werden !
Notiz: Im DC-Betrieb ist der DALI-Dimmlevel gesperrt jedoch mittels DALI magic einstellbar und entsperrbar
Stand: Okt. 2015 INOTEC_Anforderungen an Betriebsgeräte_DALI_OTi-DALI-60_550 D LT2
INOTEC Sicherheitstechnik GmbH
Technische Anforderungen an elektrische Betriebsgerä te (EVGs)
zum Anschluss an INOTEC Zentralbatteriegeräte
Hersteller: Typ / Bezeichnung: OSRAM
OTi DALI 90/220-240/1A0 LT2 L
Projekt / Projektort: Projektnummer: Marcel-Breuer-Straße 6, 80807 München
Merkmale Techn. Daten / INOTEC Anforderung Erklärung Erfüllt (Ja / Nein)
Betriebsspannungsbereich AC 230V ± 10% Spannungsbereich im Netzbetrieb JA Betriebsspannungsbereich DC 186V - 260V Möglicher Batteriespannungsbereich im Notstrombetrieb JA Betriebsgerät geeignet für "Joker-Spannung" ? ungeglättete Gleichspannung - (hochgeklappte Halbwelle) JA Betriebsgerät kompatibel mit der Umschaltzeit der Anlage ?
Umschaltzeit: von AC auf DC: 150 - 1000ms von DC auf AC: 150 - 1000ms
Typische Umschaltzeit von INOTEC Anlagen zwischen Netz- und Ersatzstromquelle
JA
Abschaltzeit des EVG (bei defektem Leuchtmittel) im DC Betrieb
innerhalb von 3s
Notwendig für Erkennung eines defekten Leuchtmittels
JA
Merkmale Techn. Daten / INOTEC Anforderung Erklärung Angabe Hersteller Nennstrom des Betriebsgerätes mit angeschlossenem Leuchtmittel im AC Betrieb
Auswahlhilfe zur Bestimmung der maximal zulässigen Anzahl Leuchten je Stromkreis
433,24 mA
Nennstrom des Betriebsgerätes mit angeschlossenem Leuchtmittel im DC Betrieb (bei eingestelltem Lichtstrom- verhältnis)
J-SV-Modul/S (5-120W): > 20mA = OK J-SV-Modul.2/S (20-300W): > 70mA = OK J-SV-Modul.3/S (2-30W): > 12mA = OK J-SV-Modul.4/S (18-120W): > 70mA = OK J-SV-Modul.L/S (20-120W): > 20mA = OK J-SV-Modul T/S (20-100W): > 60mA = OK
Auswahlhilfe Überwachungsmodul. Diese Werte dürfen im Spannungsbereich 186 - 260V DC nicht unterschritten werden, damit die Leuchte als OK gemeldet wird.
U=186V; I=101,2 mA
U=260V; I=78,5 mA
Verhältnis des Ausgangsstromes bei DC-Betrieb vs. AC-Betrieb
15% Leerlaufstrom des Betriebsgerätes (ohne oder defektes Leuchtmittel) im DC Betrieb
J-SV-Modul/S (5-120W): < 10mA = n.OK J-SV-Modul.2/S (20-300W): < 45mA = n.OK J-SV-Modul.3/S (2-30W): < 8mA = n.OK J-SV-Modul.4/S (18-120W): < 45mA = n.OK J-SV-Modul.L/S (20-120W): < 10mA = n.OK J-SV-Modul T/S (20-100W): < 50mA = n.OK
Auswahlhilfe Überwachungsmodul. Diese Werte dürfen im Spannungsbereich 186 - 260V DC nicht überschritten werden, damit ein defektes Leuchtmittel als Fehler gemeldet wird.
U=186V ;I=7,8 mA
U=260V ;I=9,3 mA
Max. Einschaltstrom der EVGs je Stromkreis
80A / 500µs (für alle J-SV-Module, ohne J-SV-Modul T/S) 40A / 500µs (für J-SV-Modul T/S) SK 4x2A: 250A / 500µs SK 2x4A: 250A / 500µs SK 2x3A: 250A / 500µs SK 1x6A: 250A / 500µs
Bezieht sich auf den maximalen zulässigen Einschaltstrom der Leuchte je Überwachungsbaustein, bzw. aller Leuchten in einem Stromkreis, um die maximale Kontaktbelastbarkeit des Überwachungsbausteins bzw. der Stromkreisschaltung zu berücksichtigen
24A /250 µs
Notiz: Im DC-Betrieb ist der DALI-Dimmlevel gesperrt jedoch mittels DALI magic einstellbar und entsperrbar.
Leuchten, die für den Einsatz als Sicherheitsleuchte vorgesehen sind, müssen u.a. der Norm DIN EN 60598-2-22 (Besondere Anforderungen - Leuchten für Notbeleuchtung) entsprechen.
Stand: Apr. 2014 INOTEC_Anforderungen an Betriebsgeräte-OTi DALI 90-1A0 LT2L
Company: OSRAM GmbH
Date: 05.08.2016
EVG:
Type! Description:
Luminaire:
OTi DALI 35 220-240 700 LT2 L LED:
Specified by:
Name: Daniel Graser
Manufacturer:
OSRAM GmbH Marcel-Breuer-Str. 6 D-80807 München
Project / Place / Project ID:
Features Techn. data / INOTEC requirements Explanation Fullfilled (Yes / No)
1 Voltage range AC 230V ± 10% Voltage range in normal mains operation Yes
2 Voltage range DC 186V - 260V Possible voltage range in emergency operation Yes
3 Control gear suitable for
"Joker-Voltage" ?
B2-rectification of the AC voltage (without smoothing)
Pulsating DC voltage ,.'-\i'—',› Yes
4 Control gear compatible with change-
over time of the System?
Change-over time: 150- 1000ms
Typical change-over time of INOTEC systems between
mains- and battery operation Yes
5 Starting behavior of the control gear
in DC operation
Stahle current consumption within 1,6s
Necessary for individual lamp monitoring (SV) Yes
6
Control gear complies with the
standard:
(only for fluorescent lamps)
DIN EN 60929 AC and/or DC-supplied electronic control gear for tubular
fluorescent lamps - Performance requirements not relevant
7
Control gear complies with the
standard:
(only for fluorescent lamps)
DIN EN 61347-2-3 (incl. Attachment I) Particular requirements for AC and/or DC supplied
electronic control gear for fluorescent lamps not relevant
8
Control gear complies with the
standard:
(only for LED)
DIN EN 62384 DC or AC supplied electronic control gear for
LED modules - Performance requirements Yes
9
Control gear complies with the
standard:
(only for LED)
DIN EN 61347-2-13 Lamp control gear - Part 2-13: Particular requirements for
DC or AC supplied electronic control gear for LED
modules
Yes
10 Control gear complies with the
standard:
DIN EN 55015
(Measurement on AC and DC) Limits and methods of measurement of radio
interference Yes
11 Control gear complies with the
standard: DIN EN 61000-3-2
Electromagnetic compatibility (EMC) - Part 3-2: Limits -
Limits for harmonic current emissions (equipment input
current 5 16 A per phase) Yes
12 Control gear complies with the
standard: DIN EN 61547
Equipment for general lighting purposes — EMC
immunity requirements Yes
13 Control gear complies with the DALI-
standards: DIN EN 62386-101 /-102 / -207 *1 Control gear must have the DALI Logo Yes
Note: VDE 0108 is not a standard for ECG, marking is not applicable
Technical requirements for dimmable DALI control gears
for fluorescent lamps and LED ...MINOTEC Sicherheitstechnik GmbH
0 • 0 •
• •01I• •
Stand: Dez. 2015 1/2 INOTEC_Requirements for control gears_DALI_V2
Technical requirements for dimmable DALI control gears
for fluorescent lamps and LED ...M1NOTEC Sicherheitstechnik GmbH
o • 0 • •60.••
Type! Description:
Luminaire:
EVG: OTi DALI 35 220-240 700 LT2 L
LED:
Manufacturer:
OSRAM GmbH Marcel-Breuer-Str. 6 D-80807 München
Project / Place / Project ID: Specified by:
Name: Daniel Graser
Company: OSRAM GmbH
Date: 05.08.2016
Features Techn. data / INOTEC requirements Explanation Manufacturer
information
14
Nominal current of the control gear
with connected illuminant in
AC- operation (230V)
Selection guide for the calculation of the max. number of
luminairs per circuit 191 mA
15
Nominal current of the control gear
with connected illuminant in
DC- operation (216V)
Selection guide for the calculation of the necessary
battery capacity 44 mA
16
Behavier control gear in DC operation:
- Unlocked light output level
- Locked light output level (Dimming
on DC)
The DC-light output settings on the DALI-SV-
Module is only active if control gear is
unlocked
In case of locked DC light output level, the DC level of the
DALI-SV-Module is not active! locked
17
Light output level in DC operation with
locked light output level (Dimming on
DC)
No control of light output level from DALI-SV.
Module in DC operation possible
Locked light output level in %.
Important for lighting design. 15 %
18
Using the DALI command 146
(Query Lamp Failure)
acc. IEC 62386 Part 102
According to IEC 62386 Part 102
Important for function test:
To detect a lamp failure, the DALI-SV-Module send the
DALI command query 146 to the DALI driver
Attention: The query is made after 2 / 2,5 / 3 seconds
Yes
19
Max. inrush current of the control
gear with connected illuminant
in AC operation (230V)
Max. permitted inrush current per circuit:
SK 4x2A: 250A / 500ps
SK 2x4A: 250A! 500gs
SK 2x3A: 250A / 5001.ts
SK 1x6A: 250A / 500ps
Describes the max. inrush current of all ballasts in a
circuit, to calculate the maximum contact rating of the
circuit
(*2)
32 A Ris
Luminaires, which should work as emergency lighting, have to be in accordance with DIN EN 60598-2-22. (Particular requirements - Luminaires for emergency lighting)
*1: Control of DALI-SV-Module to the DALI driver is 100% done via DALI-commands according to IEC 62386-101 /-102, so the DALI driver must sign with the DALI logo.
*2: For calculation the inrush current of the monitoring module must be considered!
Notes:
**) The light output level is blocked in DC Operation. Factory setting is 15% of the maximum level. lt is possible to change the bebavior of the controlgear in DC operation. For this the Tuner4Tronic and Dali magic is needed.
For the correctness:
Get OIA44,L
7
c
i
ttuee.e,
£
Place, Date u Signature
Stand: Dez. 2015 2/2 INOTEC_Requirements for control gears_DALI_V2
Technical requirements for dimmable DALI control gears
for fluorescent lamps and LED opINOTEC Sicherheitstechnik GmbH
manufacturer Type / Description:
OSRAM GmbH Luminaire:
Marcel-Breuer-Str. 6 EVG: OSRAM OTi DALI 50/220-240/1A4 LT2 L
D-80807 München LED:
Project / Place / Project ID: Specified by:
Name: Lucie Sniegon
Company: OSRAM GmbH
Date: 05.04.2016
Features Techn. data / INOTEC requirements Explanation Fullfilled (Yes / No)
1 Voltage range AC 230V ± 10% Voltage range in normal mains Operation Yes
2 Voltage range DC 186V - 260V Possible voltage range in emergency Operation Yes
3 Control gear suitable for
" "Joker-Voltage ?
132-rectification of the AC voltage
(without smoothing)
u
ldbAkiL
Yes Pulsatinp DC voltaee t
4 Control gear compatible with change-
over time of the system?
Change-over time:
150- 1000ms
Typical change-over time of INOTEC systems between
mains- and battery Operation Yes
5 Starting behavior of the control gear
in DC Operation
Stable current consumption
within 1,6s Necessary for individual lamp monitoring (SV) Yes
6
Control gear complies with the
standard:
(only for fluorescent lamps)
DIN EN 60929 AC and/or DC-supplied electronic control gear for tubular
fluorescent lamps - Performance requirements Not relevant
7
Control gear complies with the
standard:
(only for fluorescent lamps)
DIN EN 61347-2-3 (incl. Attachment J) Particular requirements for AC and/or DC supplied
electronic control gear for fluorescent lamps Not relevant
8
Control gear complies with the
standard:
(only for LED)
DIN EN 62384 DC or AC supplied electronic control gear for
LED modules - Performance requirements Yes
9
Control gear complies with the
standard:
(only for LED)
DIN EN 61347-2-13
Lamp control gear - Part 2-13: Particular requirements for
DC or AC supplied electronic control gear for LED
Modules Yes
10 Control gear complies with the
standard:
DIN EN 55015
(Measurement on AC and DC)
Limits and methods of measurement of radio
interference Yes
11 Control gear complies with the
standard: DIN EN 61000-3-2
Electromagnetic compatibility (EMC) - Part 3-2: Limits -
Limits for harmonic current emissions (equipment input
current 5 16 A per phase) Yes
12 Control gear complies with the
standard: DIN EN 61547
Equipment for general lighting purposes — EMC
immunity requirements Yes
13 Control gear complies with the DALI-
standards: DIN EN 62386-101 /-102 / -207 *1 Control gear must have the DALI Logo Yes
ote: VDE 0108 is not a standardor ECG, mar ing is not app icable
Stand: Dez. 2015 1/2 INOTEC_Requirements for control gears_DALI_V
Technical requirements for dimnnable DALI control gears
for fluorescent lamps and LED A1NOTEC Sicherheitstechnik GmbH
0 • 0 •
• 111()•••
ECG type Lamp type IN in AC-operation
IN in DC-operation
OTi DALI 50/220-240/1A4 LT2 L Maximum load Minimum load [lout 600mA]
164mA 83mA (240V)
154mA 71mA (240V)
Maximum load Minimum load [lout 1400mA]
262mA 158mA (240V)
252mA 147mA (240V)
Table 1
Stand: Dez. 2015 3/2 INOTEC_Requirements for control gears_DALI_V;
Manufacturer:
OSRAM GmbH
Marcel-Breuer-Str. 6
D-80807 München
Type / Description:
Luminaire:
EVG: OSRAM OTi DALI 80/220-240/2A1 LT2 L
LED:
Specified by:
Name: Lucie Sniegon
Company: OSRAM GmbH
Date: 05.04.2016
Project / Place / Project ID:
Features Techn. data / INOTEC requirements Explanation Fullfilled (Yes / Na)
1 Voltage range AC 230V ± 10% Voltage range in normal mains Operation Yes
2 Voltage range DC 186V - 260V Possible voltage range in emergency Operation Yes
3 Control gear suitable for
"" Joker-Voltage ?
B2-rectification of the AC voltage
(without smoothing)
u
lddkikiL
Yes Pulsatinz DC voltape i
4 Control gear compatible with change-
over time of the System?
Change-over time:
150- 1000m5
Typical change-over time of INOTEC systems between
mains- and battery operation Yes
5 Starting behavior of the control gear
in DC Operation
Stable current consumption
within 16s , Necessary for individual lamp monitoring (SV) Yes
6
Control gear complies with the
standard:
(only for fluorescent lamps)
DIN EN 60929 AC and/or DC-supplied electronic control gear for tubular
fluorescent lamps - Performance requirements Not relevant
7
Control gear complies with the
standard:
(only for fluorescent lamps)
DIN EN 61347-2-3 (incl. Attachment J) Particular requirements for AC and/or DC supplied
electronic control gear for fluorescent lamps Not relevant
8
Control gear complies with the
standard:
(only for LED)
DIN EN 62384 DC or AC supplied electronic control gear for
LED modules - Performance requirements Yes
9
Control gear complies with the
standard:
(only for LED)
DIN EN 61347-2-13
Lamp control gear - Part 2-13: Particular requirements for
DC or AC supplied electronic control gear for LED
Modules Yes
10 Control gear complies with the
standard:
DIN EN 55015
(Measurement an AC and DC)
Limits and methods of measurement of radio
interference Yes
11 Control gear complies with the
standard: DIN EN 61000-3-2
Electromagnetic compatibility (EMC) - Part 3-2: Limits -
Limits for harmonic current emissions (equipment input
current 16 A per phase) Yes
12 Control gear complies with the
standard: . DIN EN 61547
Equipment for general lighting purposes — EMC
immunity requirements Yes
13 Control gear complies with the DALI-
standards: DIN EN 62386-101 /-102 / -207 *1 Control gear must have the DALI Logo Yes
Note: VDE 0108 is not a standard for ECG, marking is not applicable
Technical requirements for dimmable DALI control gears
for fluorescent lamps and LED o • 0 •
••00••
1 NOTEC Sicherheitstechnik GmbH
Stand: Dez. 2015 1/2 INOTEC_Requirements for control gears_DALI_V;
ECG type Lamp type IN
in AC-operation IN
in DC-operation
OTi DALI 80/220-24012A1 LT2 L
Maximum load Minimum load [lout 1000mA]
261mA 119mA (240V)
248mA 105mA (240V)
Maximum load Minimum load [lout 2100mA]
393mA 225mA (240V)
381mA 214mA (240V)
Table 1
Technical requirements for dimmable DALI control gears
for fluorescent lamps and LED o • 0 •
• 00•••
1NOTEC Sicherheitstechnik GmbH
0
Stand: Dez. 2015 3/2 INOTEC_Requirements for control gears_DALI_V;
Type / Description:
Luminaire:
EVG: OTi DALI 35/220-240/350 D LT2 UF L
LED:
manufacturer
OSRAM GmbH
Marcel-Breuer-Str. 6
D-80807 Munich
Project / Place / Project ID: Specified by:
Name: Buenyamin Ocak
Company: OSRAM GmbH
Date: 13.05.2016
Technical requirements for dimmable DALI control gears
for fluorescent lamps and LED ...MINOTEC 0 • 0 • Sicherheitstechnik GmbH 0
Features Techn. data / INOTEC requirements Explanation Fullfilled (Yes / No)
1 Voltage range AC 230V ± 10% Voltage range in normal mains Operation YES
2 Voltage range DC 186V - 260V Possible voltage range in emergency Operation YES
3 Control gear suitable for
"Joker-Voltage" ?
B2-rectification of the AC voltage
(without smoothing)
u
7\7\ .7\ YES Pulsating DC voltage 'i
4 Control gear compatible with change-
over time of the System?
Change-over time:
150- 1000ms
Typical change-over time of INOTEC systems between
mains- and battery Operation YES
5 Starting behavior of the control gear
in DC Operation
Stable current consumption
within 1,65 Necessary for individual lamp monitoring (w) YES
6
Control gear complies with the
standard:
(only for fluorescent lamps)
DIN EN 60929 AC and/or DC-supplied electronic control gear for tubular
fluorescent lamps - Performance requirements not relevant
7
Control gear complies with the
standard:
(only for fluorescent lamps)
DIN EN 61347-2-3 (incl. Attachment J) Particular requirements for AC and/or DC supplied
electronic control gear for fluorescent lamps not relevant
8
Control gear complies with the
standard:
(only for LED)
DIN EN 62384 DC or AC supplied electronic control gear for
LED modules - Performance requirements YES
9
Control gear complies with the
standard:
(only for LED)
DIN EN 61347-2-13
Lamp control gear - Part 2-13: Particular requirements for
DC or AC supplied electronic control gear for LED
modules YES
10 Control gear complies with the
standard:
DIN EN 55015
(Measurement on AC and DC)
Limits and methods of measurement of radio
interference YES
11 Control gear complies with the
standard: DIN EN 61000-3-2
Electromagnetic compatibility (EMC) - Part 3-2: Limits -
Limits for harmonic current emissions (equipment input
current 16 A per phase) YES
12 Control gear complies with the
standard: DIN EN 61547
Equipment for general lighting purposes — EMC
immunity requirements YES
13 Control gear complies with the DALI-
standards: DIN EN 62386-101 /-102 1-207 *1 Control gear must have the DALI Logo YES
o e: is not a standard tor ECU, mar ing is not app ica e
Stand: Dez. 2015 1/2 INOTEC_Requirements for control gears_DALI_V;
For the correctness:
Munich, 13.05.2016
Place, Date
Technical requirements for dimmable DALI control gears
for fluorescent lamps and LED 000M INOTEC Sicherheitstechnik GmbH
0 • 0 •
••09••
Manufacturer: Type! Description:
OSRAM GmbH Luminaire:
Marcel-Breuer-Str. 6 EVG: OTi DALI 35/220-240/350 D LT2 UF L
D-80807 M u n ich LED:
Project / Place / Project ID: Specified by:
Name: Buenyamin Ocak
Company: OSRAM GmbH
Date: 13.05.2016
Features Techn. data / INOTEC requirements Explanation Manufacturer
Information
14
Nominal current of the control gear
with connected illuminant in
AC- Operation (230V)
Selection guide for the calculation of the max. number of
luminairs per circuit 187,91 mA
15
Nominal current of the control gear
with connected illuminant in
DC- operation (216V)
Selection guide for the calculation of the necessary
battery capacity 39,15 mA
16
Behavier control gear in DC operation:
- Unlocked light output level
- Locked light output level (Dimming
on DC)
The DC-light output settings on the DALI-SV-
Module is only active if control gear is
unlocked
In case of locked DC light output level, the DC level of the
DALI-SV-Module is not active!
, . . *1 locked
17
Light output level in DC Operation with
locked light output level (Dimming on
DC)
No control of light output level from DALI-SV-
Module in DC Operation possible
Locked light output level in %.
Important for lighting design. *118%
18
Using the DALI command 146
(Query Lamp Failure)
acc. IEC 62386 Part 102
According to IEC 62386 Part 102
Important for function test:
To detect a lamp failure, the DALI-SV-Module send the
DALI command query 146 to the DALI driver
Attention: The query is made after 2 / 2,5 / 3 seconds
YES
19
Max. inrush current of the control
gear with connected illuminant
in AC Operation (230V)
Max. permitted inrush current per circuit:
SK 4x2A: 250A / 500s
SK 2x4A: 2504 / 500µs
SK 2x3A: 250A / 500p.s
SK 1x6A: 250A / 500i..is
Describes the max. inrush current of all ballasts in a
circuit, to calculate the maximum contact rating of the
circuit
(*2)
15,2A / 191 µs
Luminaires, which should work as emergency lighting, have to be in accordance with DIN EN 60598-2-22. (Particular requirements - Luminaires for emergency lighting)
*1: Control of DALI-SV-Module to the DALI driver is 100% done via DALI-commands according to IEC 62386-101 /-102, so the DALI driver must sign with the DALI logo.
*2: For calculation the inrush current of the monitoring module must be considered!
Notes:
**) The light input level is locked in DC-operation. Factory setting is 18% of the maximum level. lt is possible to change
the behavior of the controlgear in DC-operation.
Signature
Stand: Dez. 2015 2/2 INOTEC_Requirements for control gears_DALI_V;
Manufacturer:
OSRAM GmbH
Marcel-Breuer-Str. 6 D-80807 Munich
Type / Description:
Luminaire:
EVG: OTi DALI 75/220-240/700 D LT2 UF L
LED:
Project / Place / Project ID: Specified by:
Name: Buenyamin Ocak
Company: OSRAM GmbH
Date: 13.05.2016
Features Techn. data / INOTEC requirements Explanation Fullfilled (Yes / No)
1 Voltage range AC 230V ± 10% Voltage range in normal mains Operation YES
2 Voltage range DC 186V - 260V Possible voltage range in emergency Operation YES
3 Control gear suitable for
"Joker-Voltage" ?
B2-rectification of the AC voltage
(without smoothing)
u,
' ._____47.Z:\„ Pulsating DC voltage I
YES
4 Control gear compatible with change-
over time of the System?
Change-over time:
150- 1000ms
Typical change-over time of INOTEC systems between
mains- and battery Operation YES
5 Starting behavior of the control gear
in DC Operation
Stable current consumption
within 165 , Necessary for individual lamp monitoring (SV) YES
6
Control gear complies with the
standard:
(only for fluorescent lamps)
DIN EN 60929 AC and/or DC-supplied electronic control gear for tubular
fluorescent lamps - Performance requirements not relevant
7
Control gear complies with the
standard:
(only for fluorescent lamps)
DIN EN 61347-2-3 (incl. Attachment J) Particular requirements for AC and/or DC supplied
electronic control gear for fluorescent lamps not relevant
8
Control gear complies with the
standard:
(only for LED)
DIN EN 62384 DC or AC supplied electronic control gear for
LED modules - Performance requirements YES
9
Control gear complies with the
standard:
(only for LED)
DIN EN 61347-2-13
Lamp control gear - Part 2-13: Particular requirements for
DC or AC supplied electronic control gear for LED
modules YES
1.o Control gear complies with the
standard:
DIN EN 55015
(Measurement on AC and DC)
Limits and methods of measurement of radio
interference YES
11 Control gear complies with the
standard: DIN EN 61000-3-2
Electromagnetic compatibility (EMC) - Part 3-2: Limits -
Limits for harmonic current emissions (equipment input
current 16 A per phase) YES
12 Control gear complies with the
standard: DIN EN 61547
Equipment for general lighting purposes — EMC
immunity requirements YES
13 Control gear complies with the DALI-
standards: DIN EN 62386-101 /-102 / -207 *1 Control gear must have the DALI Logo YES
o e: VUL U1OS is not a standard tor ECG, marking is not app ica e
Technical requirements for dimmable DALI control gears
for fluorescent lamps and LED c,A I N OT C Sicherheitstechnik GmbH
0 • 0 •
0•01>••
Stand: Dez. 2015 1/2 INOTEC_Requirements for control gears_DALI_V;
0 • o •
900•••
Technical requirements for dimmable DALI control gears
for fluorescent lamps and LED 000M 1 N OTEC Sicherheitstechnik GmbH
Type! Description:
Luminaire:
EVG: OTi DALI 75/220-240/700 D LT2 UF L
LED:
Manufacturer:
OSRAM GmbH
Marcel-Breuer-Str. 6
D-80807 Munich
Project / Place / Project ID: Specified by:
Name: Buenyamin Ocak
Company: OSRAM GmbH
Date: 13.05.2016
Features Techn. data / INOTEC requirements Explanation Manufacturer
Information
14
Nominal current of the control gear
with connected illuminant in
AC- operation (230V)
Selection guide for the calculation of the max. number of
luminairs per circuit 350,23 mA
15
Nominal current of the control gear
with connected illuminant in
DC- operation (216V)
Selection guide for the calculation of the necessary
battery capacity 64,13 mA
16
Behavier control gear in DC operation:
- Unlocked light output level
- Locked light output level (Dimming
on DC)
The DC-light output settings on the DALI-SV-
Module is only active if control gear is
unlocked
In case of locked DC light output level, the DC level of the
DALI-SV-Module is not active! **) locked
17
Light output level in DC operation with
locked light output level (Dimming on
DC)
No control of light output level from DALI-SV-
Module in DC operation possible
Locked light output level in %.
Important for lighting design. **) 18%
18
Using the DALI command 146
(Query Lamp Failure)
acc. IEC 62386 Part 102
According to IEC 62386 Part 102
Important for function test:
To detect a lamp failure, the DALI-SV-Module send the
DALI command query 146 to the DALI driver
Attention: The query is made after 2! 2,5! 3 seconds
YES
19
Max. inrush current of the control
gear with connected illuminant
in AC operation (230V)
Max. permitted inrush current per circuit:
SK 4x2A: 250A / 500µ5
SK 2x4A: 250A / 500µs
SK 2x3A: 250A / 500µ5
SK 1x6A: 250A/ 500µs
Describes the max. inrush current of all ballasts in a
circuit, to calculate the maximum contact rating of the
circuit
(*2)
17,2A / 210 gs
Luminaires, which should work as emergency lighting, have to be in accordance with DIN EN 60598-2-22. (Particular requirements - Luminaires for emergency lighting)
*1: Control of DALI-SV-Module to the DALI driver is 100% done via DALI-commands according to IEC 62386-101 /-102, so the DALI driver must sign with the DALI logo.
*2: For calculation the inrush current of the monitoring module must be considered!
Notes:
**) The light input level is locked in DC-operation. Factory setting is 18% of the maximum level. lt is possible to change
the behavior of the controlgear in DC-operation.
Signature
Stand: Dez. 2015 2/2 INOTEC_Requirements for control gears_DALI_V:
For the correctness:
Munich, 13.05.2016
Place, Date
Luminaire:
EVG:
LED:
Name:
Company:
Date:
1 Voltage range AC
2 Voltage range DC
3Control gear suitable for
"Joker-Voltage" ?
4Control gear compatible with change-
over time of the system?
5Starting behavior of the control gear
in DC operation
6
Control gear complies with the
standard:
(only for fluorescent lamps)
Control gear complies with the Particular requirements for AC and/or DC supplied
Possible voltage range in emergency operation
Pulsating DC voltage
Type / Description:
Specified by:
Features Fullfilled (Yes / No)Explanation
Voltage range in normal mains operation
Techn. data / INOTEC requirements
186V - 260V
B2-rectification of the AC voltage
(without smoothing)
Change-over time:
150 - 1000ms
Stable current consumption
within 1,6s
DIN EN 60929
230V ± 10%
Typical change-over time of INOTEC systems between
mains- and battery operation
Necessary for individual lamp monitoring (SV)
AC and/or DC-supplied electronic control gear for tubular
fluorescent lamps - Performance requirements
Technical requirements for dimmable DALI control gears
for fluorescent lamps and LED
Manufacturer:
Project / Place / Project ID:
7
Control gear complies with the
standard:
(only for fluorescent lamps)
8
Control gear complies with the
standard:
(only for LED)
9
Control gear complies with the
standard:
(only for LED)
10Control gear complies with the
standard:
11Control gear complies with the
standard:
12Control gear complies with the
standard:
13Control gear complies with the DALI-
standards:DIN EN 62386-101 /-102 / -207 *1 Control gear must have the DALI Logo
Particular requirements for AC and/or DC supplied
electronic control gear for fluorescent lamps
DC or AC supplied electronic control gear for
LED modules - Performance requirements
Lamp control gear - Part 2-13: Particular requirements for
DC or AC supplied electronic control gear for LED
modules
Limits and methods of measurement of radio
interference
Electromagnetic compatibility (EMC) - Part 3-2: Limits -
Limits for harmonic current emissions (equipment input
current ≤ 16 A per phase)
DIN EN 61347-2-3 (incl. Attachment J)
DIN EN 61547
DIN EN 62384
DIN EN 61347-2-13
DIN EN 55015
(Measurement on AC and DC)
DIN EN 61000-3-2
Equipment for general lighting purposes — EMC
immunity requirements
Note: VDE 0108 is not a standard for ECG, marking is not applicable
Stand: Dez. 2015 1/2 INOTEC_Requirements for control gears_DALI_V2
OSRAM GmbH Marcel-Breuer-Str. 6 D-80807 Munich
---
OTi DALI 15/220-240/1A0 LT2
---
Buenyamin Ocak
OSRAM GmbH
2016-02-29
Yes
Yes
Yes
Yes
Yes
not relevant
not relevant
Yes
Yes
Yes
Yes
Yes
Yes
Luminaire:
EVG:
LED:
Name:
Company:
Date:
14
Nominal current of the control gear
with connected illuminant in
AC- operation (230V)
mA
15
Nominal current of the control gear
with connected illuminant in
DC- operation (216V)
mA
16
Behavier control gear in DC operation:
- Unlocked light output level
- Locked light output level (Dimming
on DC)
17
Light output level in DC operation with
locked light output level (Dimming on
DC)
%
Techn. data / INOTEC requirements
No control of light output level from DALI-SV-
Module in DC operation possible
The DC-light output settings on the DALI-SV-
Module is only active if control gear is
unlocked
In case of locked DC light output level, the DC level of the
DALI-SV-Module is not active!
Features
Specified by:
Explanation
Type / Description:
Manufacturer
information
Selection guide for the calculation of the max. number of
luminairs per circuit
Selection guide for the calculation of the necessary
battery capacity
Locked light output level in %.
Important for lighting design.
Technical requirements for dimmable DALI control gears
for fluorescent lamps and LED
Manufacturer:
Project / Place / Project ID:
18
Using the DALI command 146
(Query Lamp Failure)
acc. IEC 62386 Part 102
19
Max. inrush current of the control
gear with connected illuminant
in AC operation (230V)
A / µs
Signature
Describes the max. inrush current of all ballasts in a
circuit, to calculate the maximum contact rating of the
circuit
(*2)
According to IEC 62386 Part 102
Max. permitted inrush current per circuit:
SK 4x2A: 250A / 500µs
SK 2x4A: 250A / 500µs
SK 2x3A: 250A / 500µs
SK 1x6A: 250A / 500µs
Important for function test:
To detect a lamp failure, the DALI-SV-Module send the
DALI command query 146 to the DALI driver
Attention: The query is made after 2 / 2,5 / 3 seconds
Place, Date
Luminaires, which should work as emergency lighting, have to be in accordance with DIN EN 60598-2-22. (Particular requirements - Luminaires for emergency lighting)
*1: Control of DALI-SV-Module to the DALI driver is 100% done via DALI-commands according to IEC 62386-101 /-102, so the DALI driver must sign with the DALI logo.
*2: For calculation the inrush current of the monitoring module must be considered!
Notes:
For the correctness:
Stand: Dez. 2015 2/2 INOTEC_Requirements for control gears_DALI_V2
117,88
48,12
locked
15 *)
Yes
5A / 45µs
*) The light input level is locked in DC-operation. Factory setting is 15% of the maximum level. It is possible to change the behavior of the controlgear in DC-operation. For this the software DALI magic is needed.
2016-02-29
OSRAM GmbH Marcel-Breuer-Str. 6 D-80807 Munich
---
OTi DALI 15/220-240/1A0 LT2
---
Buenyamin Ocak
OSRAM GmbH
2016-02-29
Date: 10.August.2016
Type / Description:
Luminaire:
EVG: Oti DALI 25 220-240 700 LT2
LED:
Specified by:
Name: Daniel Graser
Project / Place / Project ID:
Company: OSRAM GmbH
Manufacturer:
OSRAM GmbH
Marcel-Breuer-Str. 6
D-80807 München
Features Techn. data / INOTEC requirements Explanation Fullfilled (Yes / No)
1 Voltage range AC 230V ± 10% Voltage range in normal mains operation Yes
2 Voltage range DC 186V - 260V Possible voltage range in emergency operation Yes
Control gear suitable for
Joker-Voltage'?
82-rectification of the AC voltage
(without smoothing)
iJ
Pulsating DC voltage Yes i
4 Control gear compatible with change-
over time of the System?
Change-over time:
150- 1000ms
Typical change-over time of INOTEC systems between
mains- and battery operation Yes
5 Starting behayior of the control gear
in DC operation
Stable current consumption
within 1,6s Necessary for individual lamp monitoring (SV) Yes
6
Control gear complies with the
standard:
(only for fluorescent lamps)
DIN EN 60929 AC and/or DC-supplied electronic control gear for tubular
fluorescent lamps - Performance requirements not relevant
7
Control gear complies with the
standard:
(only for fluorescent lamps)
DIN EN 61347-2-3 (incl. Attachment.1) Particular requirements for AC and/or DC supplied
electronic control gear for fluorescent lamps not relevant
8
Control gear complies with the
standard:
(only for LED)
DIN EN 62384 DC or AC supplied electronic control gear for
LED modules - Performance requirements Yes
9
Control gear complies with the
standard:
(only for LED)
DIN EN 61347-2-13
Lamp control gear - Part 2-13: Particular requirements for
DC or AC supplied electronic control gear for LED
modules Yes
10 Control gear complies with the
standard:
DIN EN 55015
(Measurement on AC and DC)
Limits and methods of measurement of radio
interference Yes
11 Control gear complies with the
standard: DIN EN 61000-3-2
Electromagnetic compatibility (EMC) - Part 3-2: Limits -
Limits for harmonic current emissions (equipment input
current 5 16 A per phase) Yes
12 Control gear complies with the
standard: DIN EN 61547
Equipment for general lighting purposes — EMC
immunity requirements Yes
13 Control gear complies with the DALI-
standards: DIN EN 62386-101 /-102 / -207 *1 Control gear must have the DALI Logo Yes
Note: VDE 0108 is not a standard for ECG, marking is not applicable
Technical requirements for dimmable DALI control gears
for fluorescent lamps and LED ...MINOTEC Sicherheitstechnik GmbH
0 • 0 •
••0•••
Stand: Dez. 2015 1/2 INOTEC_Requirements for control gears_DALI_V2
Project / Place / Project ID:
Company: OSRAM GmbH
EVG: Oti DALI 25 220-240 700 LT2
Date: 10.August.2016
Type / Description:
Luminaire:
Manufacturer:
OSRAM GmbH Marcel-Breuer-Str. 6 D-80807 München
Specified by:
Name: Daniel Graser
LED:
Technical requirements for dimmable DALI control gears
for fluorescent lamps and LED ...MINOTEC Sicherheitstechnik GmbH
o • 0 •
• 1110•••
Features Techn. data / INOTEC requirements Explanation Manufacturer
information
14
Nominal current of the control gear
with connected illuminant in
AC- operation (230V)
Selection guide for the calculation of the max. number of
luminairs per circuit 145 mA
15
Nominal current of the control gear
with connected illuminant in
DC- operation (216V)
Selection guide for the calculation of the necessary
battery capacity 36.5 mA
16
Behavier control gear in DC operation:
- Unlocked light output level
- Locked light output level (Dimming
on DC)
The DC-light output settings on the DALI-SV-
Module is only active if control gear is
unlocked
In case of locked DC light output level, the DC level of the
DALI-SV-Module is not active! locked
17
Light output level in DC operation with
Iocked light output level (Dimming on
DC)
No control of light output level from DALI-SV.
Module in DC operation possible
Locked light output level in %.
Important for lighting design. 15 %
18
Using the DALI command 146
(Query Lamp Failure)
acc. IEC 62386 Part 102
According to IEC 62386 Part 102
Important for function test:
To detect a lamp failure, the DALI-SV-Module send the
DALI command query 146 to the DALI driver
Attention: The query is made after 2 / 2,5 / 3 seconds
Yes
19
Max. inrush current of the control
gear with connected illuminant
in AC operation (230V)
Max. permitted inrush current per circuit:
SK 4x2A: 250A / 500j.ts
SK 2x4A: 250A / 50011s
SK 2x3A: 250A / 500ps
SK 1x6A: 250A / 5001.1s
Describes the max. inrush current of all ballasts in a
circuit, to calculate the maximum contact rating of the
circuit
(*2)
10 Ahis
Luminaires, which should work as emergency lighting, have to be in accordance with DIN EN 60598-2-22. (Particular requirements - Luminaires for emergency lighting)
*1: Control of DALI-SV-Module to the DALI driver is 100% done via DALI-commands according to IEC 62386-101 /-102, so the DALI driver must sign with the DALI logo.
*2: For calculation the inrush current of the monitoring module must be considered!
Notes:
**)DC Light Level is locked, it can be modified with DALI-MAGIC with Tuner4Tronic
For the correctness:
Place, Date
Stand: Dez. 2015 2/2 INOTEC_Requirements for control gears_DALI_V2
Projekt / Projektort:
Merkmale Techn. Daten / INOTEC Anforderung Erklärung Erfüllt (Ja / Nein)
Betriebsspannungsbereich AC 230V ± 10% Spannungsbereich im Netzbetrieb Ja
Betriebsspannungsbereich DC 186V - 260V Möglicher Batteriespannungsbereich im Notstrombetrieb Ja
Betriebsgerät geeignet für
"Joker-Spannung" ?
B2-Gleichrichtung der Netzspannung
(ohne Glättung)
ungeglättete Gleichspannung
(hochgeklappte Halbwelle) Ja
Betriebsgerät kompatibel mit der
Umschaltzeit der Anlage ?
Umschaltzeit:
150 - 1000ms
Typische Umschaltzeit von INOTEC Anlagen zwischen Netz- und
Ersatzstromquelle Ja
Startverhalten Betriebsgerät im DC-
Betrieb
Stabile Stromaufnahme
innerhalb von 1,6sNotwendig für Fehlererkennung der Einzelleuchtenüberwachung Ja
Betriebsgerät erfüllt die Norm:
(nur für Leuchtstofflampe)DIN EN 60929
Wechsel- und/oder gleichstromversorgte elektronische Betriebsgeräte für
röhrenförmige Leuchtstofflampen - Anforderung an die Arbeitsweise N/A
Betriebsgerät erfüllt die Norm:
(nur für Leuchtstofflampe)DIN EN 61347-2-3 (incl. Anhang J)
Besondere Anforderungen an wechsel-und/oder gleichstromversorgte
elektronische Betriebsgeräte für Leuchtstofflampen N/A
Betriebsgerät erfüllt die Norm:
(nur für LED)DIN EN 62384
Gleich- oder wechselstromversorgte elektronische Betriebsgeräte für LED-
Module- Anforderungen an die Arbeitsweise Ja
Betriebsgerät erfüllt die Norm:
(nur für LED)DIN EN 61347-2-13
Besondere Anforderungen an gleich- oder wechselstromversorgte elektronische
Betriebsgeräte für LED-ModuleJa
Betriebsgerät erfüllt die Norm:DIN EN 55015
(Messung bei AC und DC)
Grenzwerte und Messverfahren für Funkstörungen von elektrischen
Beleuchtungseinrichtungen und ähnlichen Elektrogeräten Ja
Betriebsgerät erfüllt die Norm: DIN EN 61000-3-2
Elektromagnetische Verträglichkeit (EMV) - Teil 3-2: Grenzwerte
-Grenzwerte für Oberschwingungsströme
(Geräte-Eingangsstrom ≤ 16A je Leiter) Ja
Betriebsgerät erfüllt die Norm: DIN EN 61547Einrichtungen für allgemeine Beleuchtungszwecke -
EMV-Störfestigkeitsanforderung Ja
Betriebsgerät erfüllt die DALI-
NormenDIN EN 62386-101/-102/-207*1 Das EVG muss das DALI Logo tragen Ja
Merkmale Techn. Daten / INOTEC Anforderung Erklärung Angabe Hersteller
Nennstrom des Betriebsgerätes mit
angeschlossenem Leuchtmittel im AC
Betrieb (230V)
Auswahlhilfe zur Bestimmung der maximal zulässigen Anzahl Leuchten je
Stromkreis 189,37 mA
Nennstrom des Betriebsgerätes mit
angeschlossenem LED-Modul
im DC Betrieb (216V)
Auswahlhilfe zur Bestimmung der benötigten Batteriekapazität 37,85 mA
Verhalten des EVGs im DC-Betrieb
- nicht gesperrter Dimmlevel
- gesperrter Dimmlevel (Dimming on
DC)
Die Dimmleveleinstellung des DALI-SV-Moduls
ist nur möglich bei nicht gesperrtem Dimmlevel
im DC-Betrieb
Bei gesperrtem Dimmlevel im DC-Betrieb kann das DALI-SV-Modul den
Lichtstrom nicht einstellen !gesperrter Dimmlevel
Lichtstromlevel im DC-Betrieb bei
gesperrten Dimmlevel (Dimming on
DC)
Keine Regelung des Lichtstroms durch das
DALI-SV-Modul im DC-Betrieb
Fester Lichstromlevel des DALI-EVGs bei gesperrtem Dimmlevel im DC-Betrieb.
Wichtig für die Lichtplanung der Sicherheitsbeleuchtung 20,30%
Verwendung des DALI Komandos 146
(Query Lamp Failure)
gem. IEC 62386 Part 102Erfüllt die IEC 62386 Teil 102
Wichtig für den Funktiontest:
Um einen Leuchtenfehler zu detektieren, sendet das DALI-SV-Modul das DALI
Komando 146 zum DALI EVG Ja
Max. Einschaltstrom des
Betriebsgerätes mit angeschlossenem
Leuchtmittel im AC Betrieb (230V)
Zulässiger Gesamteinschaltstrom je Stromkreis:
SK 4x2A: 250A / 500µs
SK 2x4A: 250A / 500µs
SK 2x3A: 250A / 500µs
SK 1x6A: 250A / 500µs
Bezieht sich auf den maximal zulässigen Einschaltstrom aller Leuchten in einem
Stromkreis, um die maximale Kontaktbelastbarkeit der Stromkreisschaltungen zu
berücksichtigen (*2) 21A / 22µs
Notiz:
Technische Anforderungen an elektrische Betriebsgeräte für LEDs
zum Anschluss an INOTEC Zentralbatteriegeräte
Hersteller: Typ / Bezeichnung:
OSRAM OTi DALI 35/220-240/1A0 LT2
Marcel-Breuer-Straße 6, 80807 München
Projektnummer:
Leuchten, die für den Einsatz als Sicherheitsleuchte vorgesehen sind, müssen u.a. der Norm DIN EN 60598-2-22 (Besondere Anforderungen - Leuchten für Notbeleuchtung) entsprechen.
*1: Die Ansteuerung des DALI-SV-Moduls zum DALI EVG erfolgt zu 100% über DALI Kommandos gem. IEC 62386-101/-102, so ist es zwingend erforderlich, dass das DALI EVG das DALI-Logo trägt.
*2: zur Planung muss der Einschaltstrom des Überwachungsmoduls mit berücksichtigt werden !
Hinweis: Die Kennzeichnung "gemäß VDE 0108" ist nicht aussagekräftig, da dieses keine EVG-Gerätenorm ist.
INOTECSicherheitstechnik GmbH
Stand: Okt. 2015 INOTEC_Anforderungen an Betriebsgeräte_DALI_OTi DALI 35-1A0 LT2
Projekt / Projektort:
Merkmale Techn. Daten / INOTEC Anforderung Erklärung Erfüllt (Ja / Nein)
Betriebsspannungsbereich AC 230V ± 10% Spannungsbereich im Netzbetrieb Ja
Betriebsspannungsbereich DC 186V - 260V Möglicher Batteriespannungsbereich im Notstrombetrieb Ja
Betriebsgerät geeignet für
"Joker-Spannung" ?
B2-Gleichrichtung der Netzspannung(ohne Glättung)
ungeglättete Gleichspannung
(hochgeklappte Halbwelle) Ja
Betriebsgerät kompatibel mit der
Umschaltzeit der Anlage ?
Umschaltzeit:150 - 1000ms
Typische Umschaltzeit von INOTEC Anlagen zwischen Netz- und
Ersatzstromquelle JaStartverhalten Betriebsgerät im DC-
Betrieb
Stabile Stromaufnahmeinnerhalb von 1,6s Notwendig für Fehlererkennung der Einzelleuchtenüberwachung Ja
Betriebsgerät erfüllt die Norm:
(nur für Leuchtstofflampe)DIN EN 60929 Wechsel- und/oder gleichstromversorgte elektronische Betriebsgeräte für
röhrenförmige Leuchtstofflampen - Anforderung an die Arbeitsweise N/A
Betriebsgerät erfüllt die Norm:
(nur für Leuchtstofflampe)DIN EN 61347-2-3 (incl. Anhang J) Besondere Anforderungen an wechsel-und/oder gleichstromversorgte
elektronische Betriebsgeräte für Leuchtstofflampen N/A
Betriebsgerät erfüllt die Norm:
(nur für LED)DIN EN 62384 Gleich- oder wechselstromversorgte elektronische Betriebsgeräte für LED-
Module- Anforderungen an die Arbeitsweise Ja
Betriebsgerät erfüllt die Norm:
(nur für LED)DIN EN 61347-2-13 Besondere Anforderungen an gleich- oder wechselstromversorgte elektronische
Betriebsgeräte für LED-ModuleJa
Betriebsgerät erfüllt die Norm:DIN EN 55015(Messung bei AC und DC)
Grenzwerte und Messverfahren für Funkstörungen von elektrischen
Beleuchtungseinrichtungen und ähnlichen Elektrogeräten Ja
Betriebsgerät erfüllt die Norm: DIN EN 61000-3-2Elektromagnetische Verträglichkeit (EMV) - Teil 3-2: Grenzwerte
-Grenzwerte für Oberschwingungsströme
(Geräte-Eingangsstrom ≤ 16A je Leiter) Ja
Betriebsgerät erfüllt die Norm: DIN EN 61547 Einrichtungen für allgemeine Beleuchtungszwecke -
EMV-Störfestigkeitsanforderung Ja
Betriebsgerät erfüllt die DALI-
NormenDIN EN 62386-101/-102/-207*1 Das EVG muss das DALI Logo tragen Ja
Merkmale Techn. Daten / INOTEC Anforderung Erklärung Angabe Hersteller
Nennstrom des Betriebsgerätes mit
angeschlossenem Leuchtmittel im AC Betrieb (230V)
Auswahlhilfe zur Bestimmung der maximal zulässigen Anzahl Leuchten je
Stromkreis 267,7 mA
Nennstrom des Betriebsgerätes mit
angeschlossenem LED-Modul
im DC Betrieb (216V)Auswahlhilfe zur Bestimmung der benötigten Batteriekapazität 197,27 mA
Verhalten des EVGs im DC-Betrieb
- nicht gesperrter Dimmlevel
- gesperrter Dimmlevel (Dimming on
DC)
Die Dimmleveleinstellung des DALI-SV-Moduls
ist nur möglich bei nicht gesperrtem Dimmlevel
im DC-Betrieb
Bei gesperrtem Dimmlevel im DC-Betrieb kann das DALI-SV-Modul den
Lichtstrom nicht einstellen !gesperrter Dimmlevel
Lichtstromlevel im DC-Betrieb bei
gesperrten Dimmlevel (Dimming on
DC)
Keine Regelung des Lichtstroms durch das
DALI-SV-Modul im DC-Betrieb
Fester Lichstromlevel des DALI-EVGs bei gesperrtem Dimmlevel im DC-Betrieb.
Wichtig für die Lichtplanung der Sicherheitsbeleuchtung 15 %
Verwendung des DALI Komandos 146
(Query Lamp Failure)
gem. IEC 62386 Part 102Erfüllt die IEC 62386 Teil 102
Wichtig für den Funktiontest:
Um einen Leuchtenfehler zu detektieren, sendet das DALI-SV-Modul das DALI
Komando 146 zum DALI EVG Ja
Max. Einschaltstrom des
Betriebsgerätes mit angeschlossenem
Leuchtmittel im AC Betrieb (230V)
Zulässiger Gesamteinschaltstrom je Stromkreis:
SK 4x2A: 250A / 500µs
SK 2x4A: 250A / 500µs
SK 2x3A: 250A / 500µs
SK 1x6A: 250A / 500µs
Bezieht sich auf den maximal zulässigen Einschaltstrom aller Leuchten in einem
Stromkreis, um die maximale Kontaktbelastbarkeit der Stromkreisschaltungen zu
berücksichtigen (*2) 24A / 190µs
Notiz: Im DC-Betrieb ist der DALI-Dimmlevel gesperrt jedoch mittels DALI magic einstellbar und entsperrbar
Technische Anforderungen an elektrische Betriebsgeräte für LEDszum Anschluss an INOTEC Zentralbatteriegeräte
Hersteller: Typ / Bezeichnung:
OSRAM OTi DALI 50/220-240/1A4 LT2 FAN
Marcel-Breuer-Straße 6, 80807 München
Projektnummer:
Leuchten, die für den Einsatz als Sicherheitsleuchte vorgesehen sind, müssen u.a. der Norm DIN EN 60598-2-22 (Besondere Anforderungen - Leuchten für Notbeleuchtung) entsprechen.
*1: Die Ansteuerung des DALI-SV-Moduls zum DALI EVG erfolgt zu 100% über DALI Kommandos gem. IEC 62386-101/-102, so ist es zwingend erforderlich, dass das DALI EVG das DALI-Logo trägt.
*2: zur Planung muss der Einschaltstrom des Überwachungsmoduls mit berücksichtigt werden !
Hinweis: Die Kennzeichnung "gemäß VDE 0108" ist nicht aussagekräftig, da dieses keine EVG-Gerätenorm ist.
INOTECSicherheitstechnik GmbH
Stand: Okt. 2015 INOTEC_Anforderungen an Betriebsgeräte_DALI_OTi-DALI-50_1A4-LT2 FAN