Installationsanleitung RIF 5 – Relais Interface Modul Artikel Nr. 850 009 Schnittstellenmodul zur Bereitstellung von Statusmeldungen über potentialfreie Meldekontakte, inklusive Fernschalteinrichtung zum Blockieren und Stromschleife zur Meldung von Netzausfall Unterverteilung. Integriert ist ein einphasiger Phasenwächter zur Überwachung des Hauptver- teilers, sowie eine Anschlussmöglichkeiten für einen Temperaturfühler. Vorgesehen für Hutprofilschienenmontage. INOTEC Sicherheitstechnik GmbH Technische Daten INOTEC Sicherheitstechnik GmbH Funktionen INOTEC Sicherheitstechnik GmbH Installation instruction INOTEC Sicherheitstechnik GmbH Technical data INOTEC Sicherheitstechnik GmbH Monitoring INOTEC Sicherheitstechnik GmbH RIF 5 – Relais Interface Modul Order no: 850 009 Interface module to allow status messages through volt-free contacts, including blocking remote switch and current loop for signalling sub-distribution board mains failure. A single-phase monitor function for main distribution board is integrated and also a connectivity for a temperature sensor for temperature controlled charging. Provided for DIN rail mounting. Important notes After unpacking kindly check for complete delivery and wether there are any visible external damages. Furthermore, inform the forwarding agents at once about visible damages, as we do not accept complaints that reach us at a later time. Prior to starting the system take into consideration all references in the mounting and operating instructions! All guarantee claims cease in case of wrong installation or of any intervention on the products. In general original spare part must be used. Safety Notes Installation and connection of these products is only for trained and qualified electricians. This product is a safety relevant device. Tests must be carried out according to national requirements. The product has to be operated within the design parameters and only in functional, undamaged condition. The system has to be disconnected from mains supply prior to any work being carried out. For installation and operation of these product national safety standards and legal requirements have to be observed. Massbild: Technische Daten Netzspannung: 230V 50/60 Hz Temp.-Bereich: -15°C ... +40°C Gehäuse: Thermoplast V0 Leiteranschluss: 2,5mm² eindrähtig oder 1,5mm² Litze mit Aderendhülse Funkentstörung: gem. DIN EN 55015 Schutzklasse: I Schutzart: IP20 Allgemeine Hinweise Nach dem Auspacken des Geräts nehmen Sie bitte eine Überprüfung auf Voll- ständigkeit und erkennbare äußere Beschädigungen vor. Melden Sie offensicht- liche Beschädigungen sofort, da wir spätere Reklamationen nicht anerkennen. Die Hinweise der Montage- und Betriebsanleitung sind vor der ersten Inbetriebnahme zu beachten! Bei fehlerhafter Installation bzw. Eingriff in das Gerät erlischt der Garantieanspruch! Generell sind nur Originalersatzteile zu verwenden! Sicherheitshinweise Die Installation darf nur durch Elektrofachkräfte gem. EltbauVO erfolgen. Dieses Gerät ist ein sicherheitstechnisches Betriebsmittel, es ist entsprechend der nationalen Vorschriften zu prüfen. Das Gerät ist bestimmungsgemäß und nur in einwandfreiem, unbeschädigtem Zustand zu betreiben. Vor Arbeiten an der Anlage ist diese in jedem Fall von der Netz- und Batteriespannung zu trennen! Für die Installation und den Betrieb des Geräts sind die nationalen Sicherheits- und Unfallverhütungsvorschriften zu beachten. Anschluss des RIF-Moduls an das Steuerteil Das Modul wird über eine dreiadrige Busleitung an den internen BUS des Steuerteils angeschlossen. Dabei wird zwischen aktivem und passivem RIF unterschieden. Nach erfolgtem Anschluss muss das RIF in der Programmierung des Steuerteils angemeldet werden. Näheres finden Sie in der Betriebsanleitung des entsprechenden Gerätes. Als aktives RIF wird jenes bezeichnet, welches auch den Kontakt des Fernschalters bzw. der Stromschleife und der Phasenüberwachung auswertet. Das passive RIF schaltet nur die potentialfreien Meldekontakte. An jedem Steuerteil ist nur ein aktives RIF möglich, dafür aber beliebig viele passive. Achtung: Handelt es sich bei diesem Modul um ein passives RIF, so muss am Adressschalter die Adresse 0 eingestellt werden. Connection of RIF-module to controller The module is connected with a three-wired bus data line to the internal controller BUS. Differentiate between active and passive RIF. After connecting the RIF module has to be registered at the controller programming. For further information see the manual of the certain device. The active RIF is also able to analyse the remote switch contact, the current loop and the phase monitor. The passive RIF is just switching the volt-free contacts. At every controller just one active RIF is connectable but any number of passive ones. Attention: In case of using the module as passive RIF the address switch has to be turned to address 0. Potentialfreie Kontakte Die potentialfreien Kontakte sind für 24V mit 1A Belastung ausgelegt. Nutzung des Fernschalters Der Fernschalter dient zur Blockierung des Systems und kann je nach Programmierung im Steuerteil das Dauerlicht bzw. Not- und Dauerlicht blockieren. (Näheres dazu finden Sie in der Betriebsanleitung des Gerätes!) Schalter SLÜ Ein/Aus Der SLÜ-Schalter deaktiviert die Stromschleife und die Phasenüberwachung. Bei Geräten des Typ LPS 24 muss der Schalter in der Stellung “Aus” stehen 24V-Stromschleife Bei offenen Kontakten schaltet die Stromschleife alle Leuchten des angeschlossenen Notlichtsystems ein. Werkseitig sind die Kontakte SL+/SL- der Schließerkontakte anzuschließen (Drahtbrücke entfernen). Bei Schalterstellung SLÜ “Aus” = deaktiviert. Phasenüberwachung Wenn die Phasenüberwachung einen Ausfall der Phase feststellt, schaltet das Gerät in den Notlichtbetrieb. (Batteriebetrieb!) Bei Schalterstellung SLÜ “Aus” = deaktiviert. Anschlusmöglichkeiten für einen Temperaturfühler Temperaturfühler zur temperaturgeführten Ladung der Batterie. 24V-Spannungsversorgung Spannungsversorgung 24V, max.100mA , z.B. für Schaltsignale für LSA8.1 24V Volt-free contact The volt-free contacts are designed for 24V and 1A load. Remote switch usage The remote switch is for system blocking. Depending on controller programming it is able to block the maintained light or the non-maintained and maintained light. (For further information see the manual of the device.) Switch SLÜ on / off The SLÜ switch deactivates the current loop and phase monitor. At device types LPS 24 the switch has to be put to position “off” . 24V current loop At open contact the current loop switches on all luminaries of the connected emergency system. At delivery a jumper is mounted at contacts SL+/SL-. These NOC contacts have to be disconnected by removing this jumper. SLÜ switch position “off” = deactivated. Phase monitor When a phase fall is detected at the phase monitor the system switches to emergency operation. (battery operation!) SLÜ switch position “off” = deactivated Connectivity for temperature sensor Temperature sensor for temperature controlled battery charging. 24V power supply system Power supply system 24V, max. 100mA e.g. for switching signal for LSA8.1 24V Dimension: Technical data: Mains: 230V 50/60 Hz Amb. temp.range: -15°C ... +40°C Housing: Thermoplast V0 Wiring/terminals: 2,5mm² single wire or 1,5mm² multicore EMC protection: to DIN EN 55015 Protection class: I Protection category: IP20 59 90 71,5 59 90 71,5

Transcript of Installationsanleitung INOTEC Technische Daten INOTEC ...€¦ · Interface module to allow status...

Page 1: Installationsanleitung INOTEC Technische Daten INOTEC ...€¦ · Interface module to allow status messages through volt-free contacts, including blocking remote switch and current

Installationsanleitung

RIF 5 – Relais Interface Modul Artikel Nr. 850 009Schnittstellenmodul zur Bereitstellung von Statusmeldungen über potentialfreie Meldekontakte, inklusive Fernschalteinrichtung zum Blockieren und Stromschleife zur Meldung von Netzausfall Unterverteilung. Integriert ist ein einphasiger Phasenwächter zur Überwachung des Hauptver-teilers, sowie eine Anschlussmöglichkeiten für einen Temperaturfühler.Vorgesehen für Hutprofilschienenmontage.

INOTEC Sicherheitstechnik GmbH Technische Daten INOTEC

Sicherheitstechnik GmbH Funktionen INOTEC Sicherheitstechnik GmbH

Installation instruction INOTEC Sicherheitstechnik GmbH Technical data INOTEC

Sicherheitstechnik GmbH Monitoring INOTEC Sicherheitstechnik GmbH

RIF 5 – Relais Interface Modul Order no: 850 009Interface module to allow status messages through volt-free contacts, including blocking remote switch and current loop for signalling sub-distribution board mains failure. A single-phase monitor function for main distribution board is integrated and also a connectivity for a temperature sensor for temperature controlled charging. Provided for DIN rail mounting.

Important notesAfter unpacking kindly check for complete delivery and wether there are any visible external damages. Furthermore, inform the forwarding agents at once about visible damages, as we do not accept complaints that reach us at a later time.Prior to starting the system take into consideration all references in the mounting and operating instructions!All guarantee claims cease in case of wrong installation or of any intervention on the products. In general original spare part must be used.

Safety NotesInstallation and connection of these products is only for trained and qualified electricians.This product is a safety relevant device. Tests must be carried out according to national requirements.The product has to be operated within the design parameters and only in functional, undamaged condition.The system has to be disconnected from mains supply prior to any work being carried out.For installation and operation of these product national safety standards and legal requirements have to be observed.

Massbild:Technische Daten

Netzspannung: 230V 50/60 HzTemp.-Bereich: -15°C ... +40°CGehäuse: Thermoplast V0Leiteranschluss: 2,5mm² eindrähtig oder 1,5mm² Litze mit AderendhülseFunkentstörung: gem. DIN EN 55015Schutzklasse: ISchutzart: IP20

Allgemeine HinweiseNach dem Auspacken des Geräts nehmen Sie bitte eine Überprüfung auf Voll- ständigkeit und erkennbare äußere Beschädigungen vor. Melden Sie offensicht- liche Beschädigungen sofort, da wir spätere Reklamationen nicht anerkennen.Die Hinweise der Montage- und Betriebsanleitung sind vor der ersten Inbetriebnahme zu beachten!Bei fehlerhafter Installation bzw. Eingriff in das Gerät erlischt der Garantieanspruch!Generell sind nur Originalersatzteile zu verwenden!

SicherheitshinweiseDie Installation darf nur durch Elektrofachkräfte gem. EltbauVO erfolgen.Dieses Gerät ist ein sicherheitstechnisches Betriebsmittel, es ist entsprechend der nationalen Vorschriften zu prüfen. Das Gerät ist bestimmungsgemäß und nur in einwandfreiem, unbeschädigtem Zustand zu betreiben.Vor Arbeiten an der Anlage ist diese in jedem Fall von der Netz- und Batteriespannung zu trennen!Für die Installation und den Betrieb des Geräts sind die nationalen Sicherheits- und Unfallverhütungsvorschriften zu beachten.

Anschluss des RIF-Moduls an das SteuerteilDas Modul wird über eine dreiadrige Busleitung an den internen BUS des Steuerteils angeschlossen. Dabei wird zwischen aktivem und passivem RIF unterschieden. Nach erfolgtem Anschluss muss das RIF in der Programmierung des Steuerteils angemeldet werden. Näheres finden Sie in der Betriebsanleitung des entsprechenden Gerätes.Als aktives RIF wird jenes bezeichnet, welches auch den Kontakt des Fernschalters bzw. der Stromschleife und der Phasenüberwachung auswertet. Das passive RIF schaltet nur die potentialfreien Meldekontakte. An jedem Steuerteil ist nur ein aktives RIF möglich, dafür aber beliebig viele passive.

Achtung: Handelt es sich bei diesem Modul um ein passives RIF, so muss am Adressschalter die Adresse 0 eingestellt werden.

Connection of RIF-module to controllerThe module is connected with a three-wired bus data line to the internal controller BUS. Differentiate between active and passive RIF.After connecting the RIF module has to be registered at the controller programming. For further information see the manual of the certain device.The active RIF is also able to analyse the remote switch contact, the current loop and the phase monitor.The passive RIF is just switching the volt-free contacts.At every controller just one active RIF is connectable but any number of passive ones.

Attention: In case of using the module as passive RIF the address switch has to be turned to address 0.

Potentialfreie KontakteDie potentialfreien Kontakte sind für 24V mit 1A Belastung ausgelegt. Nutzung des FernschaltersDer Fernschalter dient zur Blockierung des Systems und kann je nach Programmierung im Steuerteil das Dauerlicht bzw. Not- und Dauerlicht blockieren. (Näheres dazu finden Sie in der Betriebsanleitung des Gerätes!)

Schalter SLÜ Ein/AusDer SLÜ-Schalter deaktiviert die Stromschleife und die Phasenüberwachung. Bei Geräten des Typ LPS 24 muss der Schalter in der Stellung “Aus” stehen

24V-StromschleifeBei offenen Kontakten schaltet die Stromschleife alle Leuchten des angeschlossenen Notlichtsystems ein. Werkseitig sind die Kontakte SL+/SL- der Schließerkontakte anzuschließen (Drahtbrücke entfernen).Bei Schalterstellung SLÜ “Aus” = deaktiviert.

PhasenüberwachungWenn die Phasenüberwachung einen Ausfall der Phase feststellt, schaltet das Gerät in den Notlichtbetrieb. (Batteriebetrieb!)Bei Schalterstellung SLÜ “Aus” = deaktiviert.Anschlusmöglichkeiten für einen TemperaturfühlerTemperaturfühler zur temperaturgeführten Ladung der Batterie.

24V-SpannungsversorgungSpannungsversorgung 24V, max.100mA ,z.B. für Schaltsignale für LSA8.1 24V

Volt-free contactThe volt-free contacts are designed for 24V and 1A load. Remote switch usageThe remote switch is for system blocking. Depending on controller programming it is able to block the maintained light or the non-maintained and maintained light.(For further information see the manual of the device.)

Switch SLÜ on / offThe SLÜ switch deactivates the current loop and phase monitor.At device types LPS 24 the switch has to be put to position “off”.

24V current loopAt open contact the current loop switches on all luminaries of the connected emergency system.At delivery a jumper is mounted at contacts SL+/SL-. These NOC contacts have to be disconnected by removing this jumper.SLÜ switch position “off” = deactivated.

Phase monitorWhen a phase fall is detected at the phase monitor the system switches to emergency operation. (battery operation!)SLÜ switch position “off” = deactivated

Connectivity for temperature sensorTemperature sensor for temperature controlled battery charging.

24V power supply systemPower supply system 24V, max. 100mAe.g. for switching signal for LSA8.1 24V

Dimension:Technical data:

Mains: 230V 50/60 HzAmb. temp.range: -15°C ... +40°CHousing: Thermoplast V0Wiring/terminals: 2,5mm² single wire or 1,5mm² multicoreEMC protection: to DIN EN 55015Protection class: IProtection category: IP20

59

90

71,5

59

90

71,5

Page 2: Installationsanleitung INOTEC Technische Daten INOTEC ...€¦ · Interface module to allow status messages through volt-free contacts, including blocking remote switch and current

INOTEC Sicherheitstechnik GmbH Einbau INOTEC

Sicherheitstechnik GmbH Mounting INOTEC Sicherheitstechnik GmbH

INOTEC Sicherheitstechnik GmbHAm Buschgarten 17D - 59 469 EnseTelefon +49 29 38/ 97 30 - 0Telefax +49 29 38/ 97 30 - 29e-mail [email protected]

Technische Änderungen vorbehalten!Subject to technical changes!

Anschluss Connection INOTEC Sicherheitstechnik GmbH

708

097

B

201

3/07

TemperaturfühlerTemp. sensor

FernschalterRemote switch

24V StromschleifeMonitoring loop

potentialfreieKontakte24V/1A (DC)Volt free contacts

24V DCmax. 100mA

Interne Verdrahtung, Firmenseitiginternal wiring, factory set

Phasenüber-wachung

einphasigsingle phase

supply monitor

850 009

850 009

Gerätezustand System status Betrieb Störung Batteriebetrieb Operation Sum-failure Battery operationKontakt 1-2 Störung geschlossen offen geschlossenContact 1-2 Failure closed open closedKontakt 3-4 Betrieb geschlossen offen offenContact 3-4 Operation closed open openKontakt 5-6 Batteriebetrieb offen offen geschlossenContact 5-6 Battery open open closedKontakt 7-8 Option 1 frei programmierbar *Contact 7-8 to be definedKontakt 9-10 Option 2 frei programmierbar *Contact 9-10 to be defined

Relaiskontakte Relay contacts

Nachrüstung in CPS 220, LPS 24Upgrade in CPS 220, LPS 24

* Funktion nicht in jedem Gerät verfügbar Function not available in every device

RIF5

3. BUS- Leitung anschließen und unter dem Baugruppenträger herführen Connect BUS data line and route it under the rack

24V+ => Rot red

=> Blau blue

B+ => Weiß white

1. Das RIF 5 auf die Hutschiene aufrasten Rest RIF5 on the DIN-rail2. Abdeckplatte abnehmen Remove cover plate

4. Den BUS - Stecker auf einen freien BUS-Verteilerplatz stecken

Put on the BUS connector to avacant BUS distribution position

5. Abdeckplatte wieder anbringen Replace cover plate

SLÜEin/AusOn/Off