KR550RC - Kohler Power · 2016. 3. 2. · ISO 8528-1. ESP : The standby power rating is applicable...
Transcript of KR550RC - Kohler Power · 2016. 3. 2. · ISO 8528-1. ESP : The standby power rating is applicable...
-
KR550RC Engine type TAD1641GE Alternator type AT02450T Canopy type M3228 Performance class G3
GENERAL CHARACTERISTICS 50 400/230 550 440 500 400 794 DEC4000
Frequency (Hz) Voltage (V) Max power ESP (kVA) Max power ESP (kWe) Max power PRP (kVA) Max power PRP (kWe) Intensity (A) Standard control panel
This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products. GBD5-08013 (KR550RC) 02/16
SMALL AUTONOMY DIMENSIONS 5000161126005990
N/A
Length (mm). Width (mm). Height (mm). Dry weight (kg). Tank capacity (L). Autonomy @ 75% of load (h) Autonomy @ 50% of load (h) N/A
SOUND LEVELS 78 (0.7) 68
POWER DEFINITION PRP : Prime Power is available for an unlimited number of annual operating hours in variable load applications, in accordance with ISO 8528-1. ESP : The standby power rating is applicable for supplying emergency power in variable load applications in accordance with ISO 8528-1. Overload is not allowed.
TERM OF USE According to the standard, the nominal power assigned by the genset is given for 25°C Air Intlet Temperature, of a barometric pressure of 100 kPA (100 m A.S.L), and 30 % relative humidity. For particular conditions in your installation, refer to the derating table.
ASSOCIATED UNCERTAINTYFor the generating sets used indoor, where the acoustic pressure levels depends on the installation conditions, it is not possible to specify the ambient noise level in the exploitation and maintenance instructions . You will also find in our exploitation and maintenance instructions a warning concerning the air noise dangers and the need to implement appropriated preventive measures.
Acoustic pressure level @1m in dB(A) Acoustic pressure level @7m in dB(A) Sound power level guaranteed (Lwa) 98
1481
DESCRIPTIVE Four-pole circuit breaker Connection terminal box rental type Containment fuel tank and large autonomy Forks and frame protection pads Sockets pack : 1x32A 400V - 1x16A MONO indus -
1xMONO SCHUCCO Battery isolating switch Heavy duty air filter with interchangeable cartridge Primary filter European socket packs Electronic governor with speed adjustment
-
KR550RC ENGINE SPECIFICATIONS
This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products. GBD5-08013 (KR550RC) 02/16
VOLVO
TAD1641GE
Turbo
L 616.12
144 x 165
1500 8.25
484
+/- 0.5%
21.88
GENERAL ENGINE DATA Engine model
Engine type
Air inlet
Cylinders arrangement
Number of cylinders
Displacement (L)
Charge Air coolant
Bore (mm) x Stroke (mm)
Compression ratio
Speed (RPM)
Pistons speed (m/s)
Maximum stand-by power at rated
RPM (kW)
Frequency regulation, steady state (%)
BMEP (bar)
Governor type Electronic
COOLING SYSTEMRadiator & Engine capacity (L) 60
Max water temperature (°C) 103
Outlet water temperature (°C) 93
Fan power (kW)Fan air flow w/o restriction (m3/s) Available restriction on air flow (mm H2O)Type of coolant Glycol-Ethylene
Thermostat modulating range HT (°C) 86-96
1.155.460.12
455
1533
EXHAUSTExhaust gas temperature @ ESP 50Hz (°C)
Exhaust gas flow @ ESP 50Hz (L/s)
Max. exhaust back pressure (mm H2O) 1000
112.56
102.05
75.38
FUELConsumption @ 110% load (L/h)
Consumption @ 100% load (L/h)
Consumption @ 75% load (L/h)
Consumption @ 50% load (L/h)
Maximum fuel pump flow (L/h) 170
48
0.76.5
0.1
OILOil capacity (L)
Min. oil pressure (bar)
Max. oil pressure (bar)
Oil consumption 100% load (L/h)
Oil sump capacity (L) 42
326
20
HEAT BALANCEHeat rejection to exhaust (kW)
Radiated heat to ambient (kW)
Heat rejection to coolant (kW) 184
500
AIR INTAKEMax. intake restriction (mm H2O) Intake air flow (L/s) 633
16.5 : 1
Air/Air DC
51.02
EMISSIONS Emission PM (g/kWh)
Emission CO (g/kWh)
Emission HC+NOx (g/kWh)
Emission HC (g/kWh)
0.086
1110.9
30
-
KR550RC ALTERNATOR SPECIFICATIONS
This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products. GBD5-08013 (KR550RC) 02/16
GENERAL DATA Alternator type AT02450TNumber of Phase Three phasePower factor (Cos Phi) 0.8Altitude (m) 0 to 1000Overspeed (rpm) 2250
4
Yes
Number of poleCapacity for maintaining short circuit at 3 ln for 10 sInsulation class H T° class (H/125°), continuous 40°C H / 125°K T° class, standby 27°C H / 163°KAVR Regulation Yes
-
KR550RC CONTROL PANEL
This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products. GBD5-08013 (KR550RC) 02/16
DEC4000, ergonomic and user-friendly
The highly versatile DEC4000 control unit is complex yet accessible, thanks to the particular attention paid to optimising its ergonomics and ease of use. With its large display screen, buttons and scroll wheel, it places the accent on simplicity and communication.
The DEC4000 offers the following functions:
Electrical measurements: voltmeter, frequency meter, ammeter.
Engine parameters: working hours counter, oil pressure, coolant temperature, fuel level, engine speed, battery voltage.
Alarms and faults: oil pressure, coolant temperature, failure to start, overspeed, alternator min./max., battery voltage min./max., emergency stop, fuel level.
Ergonomics: wheel for navigating around the various menus.
Communication: remote control and operation software, USB connections, PC connection.
For more information on the product and its options, please refer to the sales documentation.