Job Name Location Purchaser Engineer Submitted to Reference Approval Construction Unit Designation Schedule # SUBMITTAL AJ036TXJ4CH/AA (JXH36J4T) Page 1 of 4 Samsung FJM Series, 4 Port Condensing Unit © 2020 Samsung HVAC SHA-FJM-06052020 888-699-6067 www.SamsungHVAC.com &RPSDWLELOLW\ Will only operate with Samsung evaporator model numbers: AR**TSFABWKNCV (RNS**ABT): 7,000 - 24,000 Btu/h models AR**TSFYBWKNCV (RNS**YBT): 7,000 - 24,000 Btu/h models AJ***TNNDCH/AA (JNH**NDT): 9,000 - 18,000 Btu/h models AJ***TNLDCH/AA (JNH**LDT): 9,000 - 18,000 Btu/h models AJ***TNJDCH/AA (JNH**JDT): 9,000 - 18,000 Btu/h models Samsung HVAC maintains a policy of ongoing development, specifications are subject to change without notice. Auto or manual addressing of indoor units The outdoor unit shall supply power individually to the indoor units via 14 AWG X 3 power wire Soft-start to reduce current demand during compressor start Auto-restart after power loss Available maximum current setting option to reduce maximum operating current. Construction The outdoorunit shall be galvanized steel with abaked on powder coated finish for durability Heat Exchanger The heat exchanger shall be mechanically bonded fin to copper tube Controls Control signal shall be a DDC type signal Interconnect control wire between outdoor and indoor units shall be 16AWG X 2 The system shall integrate with the Samsung Controls Solution without the use of an interface module. Refrigerant System The refrigerant shall be R410A The compressor shall be hermetically sealed, inverter controlled, Twin BLDC Rotary Refrigerant flow shall be controlled by 4 separate electronic expansion valves at outdoor unit * Certified in accordance with the AHRI Unitary Small Air-Source Heat Pumps (USHP) Certification Program which is based on the latest edition of AHRI Standard 210/240. Refer to www.AHRIdirectory.org for current reference numbers. Warranty Power Voltage (ø/V/Hz) 1 / 208-230 / 60 Rated Current (amps) 1 Cooling (low / std. / max.) 2.9 / 12.2 / 17.2 Heating (low / std. / max.) 2.2 / 12.2 / 18.7 Max. Breaker Amps 30 Minimum Circuit Ampacity (A) 26.0 Dimensions W X H X D Inches 37 X 39 5/16 X 13 Weight lbs. 168.7 Heating (Max.) dB (A) 56 Cooling (Max.) dB (A) 54 Noise Level Operating Temperatures Cooling 14 ~ 114.8°F (-10 ~ 46.0°C) Heating 5 ~75°F (-15 ~ 24.0°C) Pipe Connections High Side 1/4" X 4 Low Side (suction) 3/8" X 2 + 1/2" X 2 Maximum Individual Line Set Length 82 ft Maximum Line Set Length (total) 230 ft Maximum Vertical Separation Outdoor to Indoor 49 ft Highest to Lowest Indoor 25 ft Included Pipe Adapter 2 - 1/2" X 3/8", 2 - 1/2" X 5/8" Condenser Fan Motor BLDC With Propeller Fan (1) Output Watts / FLA 125 / 1.28 CFM 2,493 Compressor Type Twin BLDC Rotary Inverter RLA Amps 18.4 Heat Exchanger Type Aluminum Fin - Copper Tube Rows 2 Refrigerant Type R410A Control Method Electronic Expansion Valve Factory Charge 109.3 oz Charged for 131 ft Additional Refrigerant 0.22 oz/ft over 131 ft Ducted 205236963 10 Years compressor, 10 year parts, 1 year limited labor (registration required) Certifications Safety ETL (UL 1995) AHRI Certification Number Non-Ducted 205291855 Mixed 205343313 1 Rated current is based on highest combination ratio of non-ducted indoor units. System can be set up as heating/cooling, cooling only, or heating only via outdoor unit option setting. System energy consumption can be viewed using Samsung SmartThings mobile app (not revenue grade, for reference only). Proper sizing and installation of equipment is critical to achieve optimal performance. Split system air conditioners and (excluding ductless systems) must be matched with appropriate coil components to meet ENERGY STAR ® criteria. Ask your contractor for details or visit www.energystar.gov. Performance* Capacity (standard / max.) Cooling (Btu/h) 32,000 / 36,000 Heating (Btu/h) 36,000 / 42,000 Minimum Cooling Capacity (Btu/h) 8,500 Minimum Heating Capacity (Btu/h) 7,600 SEER (Ducted / Mixed / Non-ducted) 16.5 / 18.0 / 19.5 EER (Ducted / Mixed / Non-ducted) 9.3 / 10.9 / 12.5 HSPF (Ducted / Mixed / Non-ducted) 9.0 / 9.5 / 10.0 JXH36J4T Model AJ036TXJ4CH/AA US Code Model Number WBB-11M Accessories Wall Bracket CKN-250 Wind Baffle Front WBF-2M-B Back

Transcript of SUBMITTAL AJ0 TXJ4CH/AA (JXH36J4 Page 1 of 4 Samsung …

Job Name LocationPurchaser EngineerSubmitted to Reference Approval ConstructionUnit Designation Schedule #

SUBMITTAL AJ036TXJ4CH/AA (JXH36J4T) Page 1 of 4

Samsung FJM Series, 4 Port Condensing Unit

© 2020 Samsung HVAC SHA-FJM-06052020 888-699-6067

www.SamsungHVAC.com

Will only operate with Samsung evaporator model numbers: AR**TSFABWKNCV (RNS**ABT): 7,000 - 24,000 Btu/h models AR**TSFYBWKNCV (RNS**YBT): 7,000 - 24,000 Btu/h models AJ***TNNDCH/AA (JNH**NDT): 9,000 - 18,000 Btu/h models AJ***TNLDCH/AA (JNH**LDT): 9,000 - 18,000 Btu/h models AJ***TNJDCH/AA (JNH**JDT): 9,000 - 18,000 Btu/h models

Samsung HVAC maintains a policy of ongoing development, specifications are subject to change without notice.

• Auto or manual addressing of indoor units

• The outdoor unit shall supply power individually to the indoor units via 14 AWG X 3 power wire

• Soft-start to reduce current demand during compressor start

• Auto-restart after power loss

• Available maximum current setting option to reduce maximumoperating current.

ConstructionThe outdoorunit shall be galvanized steel with abaked on powdercoated finish for durability

Heat ExchangerThe heat exchanger shall be mechanically bonded fin to copper tube

ControlsControl signal shall be a DDC type signal

Interconnect control wire between outdoor and indoor units shall be 16AWG X 2

The system shall integrate with the Samsung Controls Solutionwithout the use of an interface module.

Refrigerant SystemThe refrigerant shall be R410A

The compressor shall be hermetically sealed, inverter controlled,Twin BLDC Rotary

Refrigerant flow shall be controlled by 4 separate electronic expansion valves at outdoor unit

* Certified in accordance with the AHRI Unitary Small Air-Source Heat Pumps (USHP) Certification Program which is based on the latest edition of AHRI Standard 210/240. Refer to www.AHRIdirectory.org for current reference numbers.

Warranty

Power

Voltage (ø/V/Hz) 1 / 208-230 / 60

Rated Current (amps) 1Cooling (low / std. / max.) 2.9 / 12.2 / 17.2Heating (low / std. / max.) 2.2 / 12.2 / 18.7

Max. Breaker Amps 30Minimum Circuit Ampacity (A) 26.0

DimensionsW X H X D Inches 37 X 39 5/16 X 13Weight lbs. 168.7

Heating (Max.) dB (A) 56Cooling (Max.) dB (A) 54Noise Level

Operating Temperatures

Cooling 14 ~ 114.8°F (-10 ~ 46.0°C)Heating 5 ~75°F (-15 ~ 24.0°C)

Pipe Connections

High Side 1/4" X 4Low Side (suction) 3/8" X 2 + 1/2" X 2Maximum Individual Line Set Length 82 ftMaximum Line Set Length (total) 230 ft

Maximum Vertical Separation

Outdoor to Indoor 49 ftHighest to Lowest Indoor 25 ft

Included Pipe Adapter 2 - 1/2" X 3/8", 2 - 1/2" X 5/8"

Condenser FanMotor BLDC With Propeller Fan (1)

OutputWatts / FLA 125 / 1.28CFM 2,493

CompressorType Twin BLDC Rotary InverterRLA Amps 18.4

Heat ExchangerType Aluminum Fin - Copper Tube

Rows 2

Refrigerant

Type R410AControl Method Electronic Expansion ValveFactory Charge 109.3 ozCharged for 131 ftAdditional Refrigerant 0.22 oz/ft over 131 ft

Ducted 205236963

10 Years compressor, 10 year parts, 1 year limited labor (registration required)

Certifications

Safety ETL (UL 1995)

AHRI Certification Number

Non-Ducted 205291855

Mixed 205343313

1 Rated current is based on highest combination ratio of non-ducted indoor units.

• System can be set up as heating/cooling, cooling only, or heatingonly via outdoor unit option setting.

• System energy consumption can be viewed using SamsungSmartThings mobile app (not revenue grade, for reference only).

Proper sizing and installation of equipment is critical to achieve optimal performance. Split system air conditioners and (excluding ductless systems) must be matched with appropriate coil components to meet ENERGY STAR®

criteria. Ask your contractor for details or visit www.energystar.gov.

Performance*

Capacity (standard / max.)

Cooling (Btu/h) 32,000 / 36,000Heating (Btu/h) 36,000 / 42,000

Minimum Cooling Capacity (Btu/h) 8,500Minimum Heating Capacity (Btu/h) 7,600SEER (Ducted / Mixed / Non-ducted) 16.5 / 18.0 / 19.5EER (Ducted / Mixed / Non-ducted) 9.3 / 10.9 / 12.5HSPF (Ducted / Mixed / Non-ducted) 9.0 / 9.5 / 10.0

JXH36J4TModel

AJ036TXJ4CH/AAUS CodeModel Number

WBB-11MAccessories

Wall Bracket CKN-250

Wind BaffleFront WBF-2M-BBack

888-699-6067 www.SamsungHVAC.com

Page 2 of 4

Samsung FJM, 4 Port Condensing Unit Dimensional drawing

SUBMITTAL AJ036TXJ4CH/AA (JXH36J4T)

TOP

FRONT RIGHTLEFT

BOTTOM

BACK

No. Name Description

1 Refrigerant suction pipes ø3/8" x 1, ø1/2" x 3

2 Refrigerant liquid pipes ø1/4" x 4

3 Service Valve (suction) 5/8"4 Service Valve (liquid) 3/8"

5 Drain holes Connection with provided drain fitting

24 7/16"

13"

14 3

/16"

15 1

/8"

39 5

/16"

38 3

/16"

7 3/16"

3 3/4"

8 5/8" 15 7/16"

1 3/16

"

14 3/4

"

12 3/16"

9 5/8"

7 1/16

"

3/4"1 9/16" 5

3/4"

8 5/16

"10

15/16

"13

1/2

"12

3 4

5

37"

1"

Power and Communication Wiring conduit

888-699-6067 www.SamsungHVAC.com

Page 3 of 4

Samsung FJM, 4 Port Condensing Unit Indoor unit connection options

SUBMITTAL AJ036TXJ4CH/AA (JXH36J4T)

Must have a minimum of 2 indoor units connected. Will only operate with Samsung evaporator model numbers listed below:

AR**TSFABWKNCV (RNS**ABT): 7,000 - 24,000 Btu/h models AR**TSFYBWKNCV (RNS**YBT): 7,000 - 24,000 Btu/h models AJ***TNNDCH/AA (JNH**NDT): 9,000 - 18,000 Btu/h models AJ***TNLDCH/AA (JNH**LDT): 9,000 - 18,000 Btu/h models AJ***TNJDCH/AA (JNH**JDT): 9,000 - 18,000 Btu/h models

BA C D BA C D7,000 7,000 7,000 7,000 7,000 7,0007,000 9,000 7,000 7,000 7,000 9,0007,000 12,000 7,000 7,000 7,000 12,0007,000 15,000 7,000 7,000 7,000 15,0007,000 18,000 7,000 7,000 7,000 18,0007,000 24,000 7,000 7,000 7,000 24,0009,000 9,000 7,000 7,000 9,000 9,0009,000 12,000 7,000 7,000 9,000 12,0009,000 15,000 7,000 7,000 9,000 15,0009,000 18,000 7,000 7,000 9,000 18,0009,000 24,000 7,000 7,000 12,000 12,00012,000 12,000 7,000 7,000 12,000 15,00012,000 15,000 7,000 7,000 12,000 18,00012,000 18,000 7,000 7,000 15,000 15,00012,000 24,000 7,000 9,000 9,000 9,00015,000 15,000 7,000 9,000 9,000 12,00015,000 18,000 7,000 9,000 9,000 15,00015,000 24,000 7,000 9,000 9,000 18,00018,000 18,000 7,000 9,000 12,000 12,00018,000 24,000 7,000 9,000 12,000 15,0007,000 7,000 7,000 9,000 9,000 9,000 9,0007,000 7,000 9,000 9,000 9,000 9,000 12,0007,000 7,000 12,000 9,000 9,000 9,000 15,0007,000 7,000 15,000 9,000 9,000 9,000 18,0007,000 7,000 18,000 9,000 9,000 12,000 12,0007,000 7,000 24,000 9,000 9,000 12,000 15,0007,000 9,000 9,000 9,000 12,000 12,000 12,0007,000 9,000 12,0007,000 9,000 15,0007,000 9,000 18,0007,000 9,000 24,0007,000 12,000 12,0007,000 12,000 15,0007,000 12,000 18,0007,000 12,000 24,0007,000 15,000 15,0007,000 15,000 18,0007,000 18,000 18,0009,000 9,000 9,0009,000 9,000 12,0009,000 9,000 15,0009,000 9,000 18,0009,000 9,000 24,0009,000 12,000 12,0009,000 12,000 15,0009,000 12,000 18,0009,000 12,000 24,0009,000 15,000 15,0009,000 15,000 18,0009,000 18,000 18,00012,000 12,000 12,00012,000 12,000 15,00012,000 12,000 18,00012,000 15,000 15,00012,000 15,000 18,00015,000 15,000 15,000

Indoor unit Capacity (Btu/h)

4 Indoor Units

Indoor unit Capacity (Btu/h)

2 Indoor Units

3 Indoor Units

888-699-6067 www.SamsungHVAC.com

Page 4 of 4

Samsung FJM, 4 Port Condensing Unit Wiring example

SUBMITTAL AJ036TXJ4CH/AA (JXH36J4T)

Basic Wire Connection Diagram

Cable Type: System power supply cable Cable Type: Power supply to indoor units Cable Type: Communication cable (16 X 2)

ABC

This simple wiring diagram is for reference only. Please refer to installation manuals for full details and requirements.

L1 L2 L1 L2

L1 F2

1 2 F1 F2 1 2 F1 F2

F1 F2

F1 F2

F1 F2

1 2

1 2

1 2

B C B C B C

A

F1 F2

F1 F2 F1 F2

L1 L2

21 21

Earth F1 F2

F1 F2

1 2

B C

21

Earth terminal

Outdoor unit

Main PowerSupply cable

Indoor unitA-unit B-unit C-unit D-unit

Earth terminal

Earth terminal

Earth terminalterminal

L2 F1 L1 F2L2 F1 L1 F2L2 F1 L1 F2L2 F1

Outdoor unit