7PA30_3-phase (V18)
-
Upload
julio-antonio-bastias-vargas -
Category
Documents
-
view
42 -
download
5
Transcript of 7PA30_3-phase (V18)
DETAIL
The relay is for the supervision of the trip circuit ofa circuit breaker with three selective trip coils. The trip circuit wiring is supervised from thepositive supply to the negative supply whilst thecircuit breaker is open or closed.
FEATURESThe design, quality and rugged construction ofthe relay make it suitable for applicationsrequiring high levels of reliability/dependability.The high degree of protection guarantees reliableoperation over a wide temperature range, evenunder extreme environmental conditions.The relay has been tested in accordance with IEC,EN and IEEE standards. The relay is CE marked.The supervision current is always less than1,4mA thus avoiding unwanted operation of thetrip coil. Correct operation is shown via a green LED.
•Standard voltages and consumption:
•Drop-out time: < 400 ms•Contacts:
Permanent current: 8 AInstantaneous current: 15 AMaking capacity: 15 A/4 s/110 VDCBreaking capacity: 0,3 A/110 VDC
•Umax, opened contact: 250 VDC/400 VAC•Mechanical life: 107 operations•Operating temperature: -10°C +55°C•Storage temperature: -30°C +70°C•Operating humidity: 93%/40°C
Das Relais wird eingesetzt zur Überwachung desAuslösekreises von Leistungsschaltern mit dreiphasenselektiven Auslösespulen. Bei offenem und geschlossenem Leistungsschalterwird jeweils der Auslösekreis vom anliegenden L+über die Verkabelung und die Ausspule bis zum L-überwacht.
HAUPTMERKMALEDesign und Qualität der Relais, ihre hoheBeständigkeit und Funktionssicherheit gewährleistendie Anwendung in Steuerungen hoher Verantwortungund garantieren die korrekte Überwachung vomgesamten Auslösekreis.Der hohe Schutzgrad gewährleistet einen absolutzuverlässigen Betrieb innerhalb eines weitenTemperaturbereiches auch bei erschwertenUmweltbedingungen.Prüfungen wurden gemäß den Normen nach IEC, EN,IEEE durchgeführt, die CE- Kennzeichnung istvorhanden.Der Überwachungsstrom beträgt weniger als 1,4mAund stellt damit sicher, dass eine Fehlfunktion derAuslösspule nicht erfolgen kann.Der korrekte Betrieb wird über eine grüne LED amGerät signalisiert.
•Nennspannung und Eigenverbrauch:
•Ansprechzeit bei Entregung: < 400 ms•Kontakte:
Dauerstrom: 8 AÜberlastbarkeit: 15 ASchaltleistung: 15 A/4 s/110 VDCAbschaltleistung: 0,3 A/110 VDC
•Umax, Kontakt offen: 250 VDC/400 VAC•Mechanische Lebensdauer: 107 Schaltspiele•Betriebstemperatur: -10ºC +55ºC•Einlagerungstemperatur: -30ºC +70ºC•Max. Luftfeuchtigkeit: 93%/40ºC
BESCHREIBUNG DESCRIPTION
AUSLÖSEKREISÜBERWACHUNGTRIP-CIRCUIT-SUPERVISION
NEW VERSION
7PA30•3 phase
CHARACTERISTICSEIGENSCHAFTEN
7PA30 3 phase: 165g • Carton: 150x124x84 mm7XP9010-4: 400g • 7XP9012-0: 225g
7PA30 3-phasig: 165g • Karton: 150x124x84 mm7XP9010-4: 400g • 7XP9012-0: 225g
WEIGHT AND PACKINGGEWICHTE UND VERPACKUNG
ANSCHLÜSSE • CONNECTIONS
+
-
1
11 10 21 20 30 313 40 414 70 71752a
CBTrip-coil
CBTrip-coil
CBTrip-coil
52b 52a 52b 52a 52b
CIRCUIT BREAKER (open)
2 a b eK1
1
K3
K11
150-400ms
K21
K12 K22
K13 K23K2
1
K12
K22
K13
K23
FU
FU
TRIP SUPPLY
TRIP SUPPLY
TRIP CONTACT 1
TRIP CONTACT 2
TRIP CONTACT 3
h
UN
[VDC]
SpannungsbereichVoltage range
[VDC]
EigenverbrauchConsumption
24/30
60
110/125
220
18-33
42-66
77-138
154-275
35 mA
20 mA
20 mA
15 mA
Impedanz per PhaseImpedance per phase
(kOhms)
EntregungsspannungDrop out voltage
[VDC]
20
44
94
200
zwischen 12 und 18Vbetween 12 and 18Vzwischen 36 und 42Vbetween 36 and 42Vzwischen 66 und 77Vbetween 66 and 77V
zwischen 132 und 154Vbetween 132 and 154V
Kontakte dargestellt für spannungsfreies Relais.Contacts represented without auxiliary supply inthe relay.
7PA3
0*2-
3*
AlarmContacts
3 phase 3
AUSLÖSEKREIS ÜBERWACHUNG 7PA30 TRIP-CIRCUIT-SUPERVISION
AUSWAHL UND BESTELLDATEN SELECTION AND ORDER NUMBER
Number of phases
•Elektrische Prüfungen nach IsolationStoßspannungsfestigkeit Isolationswiderstand
•EntflammbarkeitKunststoffe
•Schutzklasse Relais•Umweltbedingungen
Trockene Kälte, in Betrieb Trockene Wärme, in BetriebLagerung und Transport
KONSTRUKTIONSRICHTLINIENIEC60255-5
2 kV/50 Hz/1 min5 kV/1,2/50 µs
> 100 MΩ/500 VdcUL94: V0
IEC60529, EN60529: IP40IEC60068-2
-10°C+55°C
-30°C +70°C
•Electrical testsDielectric testSurge withstand testInsulation resistance
• Inflammability class ofPlastic materials
•Protection degree relay•Climatic tests
Dry cold, operationDry heat, operationStorage and transport
CONSTRUCTION STANDARDS
Description: • Three phase trip circuit supervision relay with 2
changeover contacts.
6
-6 7 8 9 10 11 12 13
2 A A 0 0Reference: 7PA30
24/30 VDC 160 VDC 2110/125 VDC 3220 VDC 4
Auxiliary Voltage
SocketWithout Socket 0With Socket 7XP9010-4 (Flush mounting) 1With Socket 7XP9012-0 (Surface mounting) 2
-
13
83-phasig 3
Anzahl der Phasen
Benennung: • 3-phasiges Auslösekreisüberwachungsrelais
mit zwei Wechslern.
6
-6 7 8 9 10 11 12 13
2 A A 0 0Bestell-Nr.:7PA30
24/30 VDC 160 VDC 2110/125 VDC 3220 VDC 4
Nennspannung
SockelOhne Sockel 0Mit Sockel 7XP9010-4 (Einbau) 1Mit Sockel 7XP9012-0 (Aufbau) 2
-
13
8
Dimensionen und Dimensions andEinbaumaße panel mounting cut-out
Relais 7PA30 Relay
Sockel 7XP9012-0 Socketfür Aufbau for surface mounting
Sockel 7XP9010-4 Socketfür Einbau for flush mounting
82,5
12015
124
10696
= =
10
12,5
80
4 of Ø 4,5
R2
50,4
125 Min
90 M
in66 57=
=
EinbauöffnungCut-out
96,6
Minimum Drehmoment: 0,5 Nm Maximum Drehmoment: 1 Nm
Minimum torque value: 0,5 Nm Maximum torque value: 1 Nm
EMC-PRÜFUNGEN EMC TESTS•Hochfrequenzprüfung:
Test level: 1 MHz, 400 imp/s, 2 sCommon mode: 2,5 kVDiferential mode: 1 kV
•Schnelle transiente Störgrößen/Burst: Testlevel: 4 kV, 2,5 kHz, 1 min•2 kV, 5 kHz, 1 min
•Energiereiche Stoßspannungen(Surge)8/20 µs.(current)-1,2/50 µs.(voltage)Common mode: 2 kV-Diferential mode: 1 kV
•Bestrahlung mit HF-Feld, amplitudenmoduliert:Test level: 80-1000MHz,10V/m,80% AM (1kHz)
•Bestrahlung mit HF-Feld, pulsmoduliert:Test level:900 ±5MHz, 10V/m, 50%(200Hz)1.89GHz ±10MHz, 10V/m, 50% (200Hz)
•Leitungsgeführte HF,amplitudenmoduliert: Test level:0,15-80 MHz, 10V, 80% AM (1kHz)
•Entladung statischer Elektrizität: Test level:Contact ±15 kV, Air mode ±15 kV
•Magnetfeld mit energietechnischer Frequenz:Test level: 100 A/m 1min•1000 A/m 1s.
•Prüfungen zur Störaussendung: Test level:Deckel:30-230 MHz, 40dB(µV/m)(quasi peak)-10m
230-1000 MHz, 47dB(µV/m)(quasi peak)-10mStromversorgung:
0,15-0,5 MHz, 79dB(µV)(quasi peak)/66dB average0,5-5 MHz, 73dB(µV)(quasi peak)/60dB average5-30 MHz, 73dB(µV)(quasi peak)/60dB average
EN 60255-22-1
EN 61000-4-4
EN 61000-4-5
EN 61000-4-3
EN 61000-4-3
EN 61000-4-6
EN 61000-4-2
EN 61000-4-8
EN 55011Class A
•High frequency 1MHz burst disturbance test:Test level: 1 MHz, 400 imp/s, 2 sCommon mode: 2,5 kVDiferential mode: 1 kV
•Electrical Fast transient burst: Test level:4 kV, 2,5 kHz, 1 min•2 kV, 5 kHz, 1 min
•Surge:8/20 µs.(current)-1,2/50 µs.(voltage)Common mode: 2 kV-Diferential mode: 1 kV
•Radiated electromagnetic field: Test level:80-1000MHz, 10V/m, 80% AM (1kHz)
•Digital telephones radiatedelectromagnetic field: Test level:900 ±5MHz, 10V/m, 50%(200Hz)1.89GHz ±10MHz, 10V/m, 50% (200Hz)
•Conducted disturbances induced by radiofrequency fields. Test level:0,15-80 MHz, 10V, 80% AM (1kHz)
•Electrostatic discharges: Test level:Contact ±15 kV, Air mode ±15 kV
•Power frequency magnetic field:Test level: 100 A/m 1min•1000 A/m 1s.
•Emission test: Test level: Cover:30-230 MHz, 40dB(µV/m)(quasi peak)-10m230-1000 MHz, 47dB(µV/m)(quasi peak)-10mPower supply:
0,15-0,5 MHz, 79dB(µV)(quasi peak)/66dB average0,5-5 MHz, 73dB(µV) (quasi peak)/60dB average5-30 MHz, 73dB(µV)(quasi peak)/60dB average
10,5
V 18
82,7 29
60= =
80
112
2 of Ø 3,5
BefestigungsbohrungenFixing centres
DIN-Schiene Rail DIN fixEN50022 DIN46277/3