Page 1: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

FD720 Cerberus™ PRO, Synova, AlgoRex Detector system

Equipment overview

Building Technologies CPS Fire Safety

Page 2: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Liefermöglichkeiten und technische Änderungen vorbehalten. Data and design subject to change without notice. / Supply subject to availability. Sous réserve de modifications techniques et de la disponibilité. © 2014 Copyright by Siemens Schweiz AG Wir behalten uns alle Rechte an diesem Dokument und an dem in ihm dargestellten Gegenstand vor. Der Empfänger anerkennt diese Rechte und wird dieses Dokument nicht ohne unsere vorgängige schriftliche Ermächtigung ganz oder teilweise Dritten zugänglich mAchen oder außerhalb des Zweckes verwenden, zu dem es ihm übergeben worden ist. We reserve all rights in this document and in the subject thereof. By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part, nor to mAke them available to any third party without our prior express written authorization, nor to use it for any purpose other than for which it was delivered to him. Nous nous réservons tous les droits sur ce document, ainsi que sur l'objet y figurant. La partie recevant ce document reconnaît ces droits et elle s'engage à ne pas le rendre accessible à des tiers, même partiellement, sans notre autorisation écrite préalable et à ne pas l'employer à des fins autres que celles pour lesquelles il lui a été remis.

Page 3: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

1 About this document .............................................................................. 7

2 Automatic fire detectors in C-NET ........................................................ 9 2.1 Point detectors with detection algorithms ................................................. 9 2.1.1 Accessories for point detectors ............................................................... 13 2.2 Detector bases ........................................................................................ 14 2.2.1 Accessories for detector bases ............................................................... 15 2.3 Linear smoke detector FDL241-9 with ASAtechnology™....................... 16 2.3.1 Accessories for FDL241-9 ...................................................................... 17 2.4 Infrared flame detector FDF221-9 with detection algorithms .................. 18 2.5 Infrared flame detector FDF241-9 with ASAtechnology™ ...................... 19 2.5.1 Accessories for FDF221-9, FDF241-9 .................................................... 20

3 Alarm indicators for C-NET devices.................................................... 21 3.1 Door frame version FDAI91 .................................................................... 21 3.2 Wall versions FDAI92 and FDCAI221..................................................... 21 3.2.1 Accessory for wall versions ..................................................................... 22

4 Manual call points in C-NET ................................................................. 23 4.1 Manual call point FDM221 with direct operation ..................................... 23 4.1.1 Accessories for FDM221 ......................................................................... 24 4.1.2 Spare parts for FDM221 ......................................................................... 24 4.2 Manual call points FDM225/226 with direct operation ............................ 25 4.2.1 Accessories for FDM225, FDM226 ......................................................... 26 4.2.2 Spare parts for FDM225, FDM226 .......................................................... 27 4.3 Manual call point FDM224 with direct operation ..................................... 28 4.4 Manual call point 'Heavy Duty' FDM224H with direct operation ............. 29 4.4.1 Accessories for FDM224, FDM224H ...................................................... 29 4.4.2 Spare parts for FDM224, FDM224H ....................................................... 30 4.5 Manual call point FDM223 complete with indirect operation .................. 31 4.6 Manual call point FDM223 with indirect operation .................................. 32 4.7 Manual call point 'Heavy Duty' FDM223H with indirect operation .......... 33 4.7.1 Accessories for FDM223, FDM223H ...................................................... 33 4.7.2 Spare parts for FDM223, FDM223H ....................................................... 34

5 Alarm devices in C-NET ....................................................................... 35 5.1 Alarm sounders FDS221 ......................................................................... 35 5.2 Alarm sounder with supplementary optical indication FDS229 .............. 36 5.2.1 Accessories for FDS221, FDS229 .......................................................... 36 5.3 Sounder interbase DBS721, Sounder interbase with supplementary

optical indication DBS729 ....................................................................... 40 5.3.1 Accessory for DBS721 and DBS729 ...................................................... 41 5.4 Sounder base DBS720 ........................................................................... 42 5.4.1 Accessories for DBS720 ......................................................................... 42

6 Line separator, Input/output modules in C-NET ................................ 43 6.1 Line separator FDCL221 ......................................................................... 43 6.2 Multi line separator FDCL221-M ............................................................. 44 6.2.1 Accessories for FDCL221 / FDCL221-M ................................................ 44 6.3 Input modules FDCI221, FDCI222 .......................................................... 45 6.4 Input/output modules FDCIO22x ............................................................ 46 6.4.1 Accessories for FDCI22x, FDCIO22x ..................................................... 48 6.4.2 Spare part for FDCI22x, FDCIO22x ........................................................ 48

7 Special detectors in C-NET .................................................................. 49 7.1 SWING Radio gateway ........................................................................... 49 7.1.1 Accessory for SWING radio gateway...................................................... 49

3

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 4: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

7.2 SWING Radio smoke detector ................................................................ 50 7.2.1 Accessories for SWING radio smoke detector........................................ 50 7.3 SWING Radio manual call point ............................................................. 51 7.3.1 Accessories for SWING radio manual call point ..................................... 52 7.4 Aspirating smoke detectors ..................................................................... 53 7.4.1 Accessory ................................................................................................ 53 7.5 Aspirating smoke detectors ..................................................................... 54

8 Conventional and collective devices .................................................. 55 8.1 Conventional/Collective Line SynoLINE300/600 .................................... 55 8.2 Alarm indicators for SynoLINE300/600 devices...................................... 57 8.2.1 Accessory FDAI92 .................................................................................. 57 8.2.2 Accessories for FDAI93 .......................................................................... 58 8.3 Conventional / Collective 110-series detectors ....................................... 60 8.3.1 Accessories for point detectors ............................................................... 62 8.4 Detector bases ........................................................................................ 62 8.4.1 Accessories for detector bases ............................................................... 63 8.5 Manual call point collective ..................................................................... 64 8.5.1 Accessories for FDM1101 ....................................................................... 65 8.5.2 Spare parts for FDM1101 ........................................................................ 65 8.5.3 Accessories for DM1101 ......................................................................... 67 8.5.4 Spare parts for DM1101 .......................................................................... 67 8.5.5 Accessories for DM1103/04 .................................................................... 69 8.5.6 Spare parts for DM1103/04 ..................................................................... 70 8.6 Conventional FDM1101A manual call points .......................................... 71 8.6.1 Accessories for FDM1101A .................................................................... 72 8.6.2 Spare parts for FDM1101A ..................................................................... 72 8.7 Alarm indicators collective devices ......................................................... 73 8.7.1 Accessory for AI92C ............................................................................... 73 8.8 Air sampling smoke detection kit FDBZ292 ............................................ 74 8.8.1 Accessories FDBZ292 ............................................................................ 74 8.9 Conventional alarm devices .................................................................... 76 8.9.1 Alarm devices AGT24.1, RoLP/R/S, ROLP/W/S .................................... 76 8.9.2 Beacons SOL-LX-W-RW / SOL-LX-W-WW & SOL-LW-C-WW .............. 77 8.9.3 Combined sounders and beacons .......................................................... 79 8.10 Devices for explosion-hazard area of zones 1 and 2 .............................. 80 8.10.1 Interface for connection of the 'Ex' devices to C-NET ............................ 80 8.10.2 Interface for connection of 'Ex' devices to SynoLINE600 ....................... 81 8.10.3 Shunt Zener diode barrier SB3 ............................................................... 82 8.10.3.1 Accessories for SB3 ............................................................................... 82 8.10.4 Point detectors AlgoRex Serie 'Ex' ......................................................... 83 8.10.4.1 Accessories for DB1101A ...................................................................... 84 8.10.5 Infrared flame detector DF1101-Ex ......................................................... 85 8.10.5.1 Accessories for DF1101-Ex .................................................................... 86 8.10.6 Manual call points DM1103(Ex), DM1104(Ex) ........................................ 87 8.10.6.1 Accessories for DM1103(Ex), DM1104(Ex) ........................................... 87 8.10.6.2 Spare parts for DM1103(Ex), DM1104(Ex) ............................................ 88 8.10.7 Alarm indicators FDAI92-Ex, FDAI93-Ex ................................................ 89 8.10.7.1 Accessory for FDAI92-Ex ....................................................................... 89 8.10.7.2 Accessories for FDAI93-Ex .................................................................... 90 8.10.8 Alarm device DB3 for explosion-hazard areas........................................ 91

9 Test equipment and accessories ........................................................ 92 9.1 Detector exchanger for FD720 point detectors ....................................... 92 9.1.1 Accessory DX791 .................................................................................... 92 9.2 Detector tester RE6, RE6T, RE7T, RE8ST, RE8STCO ......................... 93 9.2.1 Accessories for RE6 ................................................................................ 93

4

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 5: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

9.2.2 Accessories for RE7T, RE8ST, RE8STCO............................................. 95 9.2.3 Spare parts for RE7T .............................................................................. 96 9.2.4 Accessories for DX791, RE6, RE6T, RE7T, RE8ST, RE8STCO ........... 96 9.2.4.1 Spare parts for FDUM291 ....................................................................... 97 9.2.4.2 Spare parts for FDUM292 ....................................................................... 97 9.3 Detector base tester DZB1191 ............................................................... 98 9.4 Test equipment for linear smoke detectors ............................................. 98 9.4.1 Adjustment device set FDLU291 ............................................................ 98 9.4.2 Detector tester RE10............................................................................... 98 9.5 Line tester FDUL221 ............................................................................... 99 9.5.1 Accessories for FDUL221 ....................................................................... 99 9.5.2 Spare parts for FDUL221 ...................................................................... 100 9.6 Test lamps for flame detectors .............................................................. 100 9.6.1 Spare part for LE3 ................................................................................. 100 9.7 Adapter for C-NET devices ................................................................... 101

10 Index ..................................................................................................... 102

5

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 6: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

6

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 7: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

About this document

1 About this document

Purpose This document is an overview about following detector products: Cerberus PRO FD720 Synova conventional/SynoLINE300 AlgoRex collective/SynoLINE600

All available conventional Synova and collective AlgoRex devices are contained in this overview, therefore the equipment overview 009252 is not applicable.

This document is continuously revised and extended.

Scope The document contains information about all available devices.

Target groups This document arranges itself to all persons.

Reference documents You can find the detailed information in the product data sheets and technical de-scriptions.

Conventions (...) Additional information bold letters Definitions of designations see Cross-reference

Document identification Place Signification Title page – System names

– Product type – Document purpose

Last page bottom left – Document number – Version date

Last page bottom right – Manual – Register

Modification index Version Date Brief description A6V10225323_a_en 05.2009 Initial edition A6V10225323_b_en 07.2009 VdS Approval DBS720, DBZ1195A. DLA/DLB1191A deleted.

Label 'avoid electrostatic charging' BPZ:5358470001 is enclosed with DMA1103D/04D it cannot be ordered separately, replace AX1204 by FA2003-A1, insert DC1192, minor changes.

A6V10225323_c_en 12.2009 Correction of the Ex-classification DM1103(Ex), DM1104 (Ex), DJ1191-Ex, DJ1192-Ex, AJUT24-Ex; FDCL221-M (new); FDMH293-O (new); VdS Approval for FDM226-RG/RP, FDM1101A-RG/RP, FDM1101-RG/RP; DB721 (new)

A6V10225323_d_en 05.2010 New FDAI91, FDAI92, FDAI93, FDAI92-Ex, FDAI93-Ex replace DJ1191, DJ1192, DJ1193, DJ1192-Ex and AJUT24-Ex. No replacement for DJ1191-Ex. FDCAI221 (new)

A6V10222523_e_en 12.2011 OOH740, OOHC740, BA720, DBS721, DBS729, DB721D, FDUD491 Correction order number DB1101A New housing FDMH292-R New accessory for DX791: FDUD491

7

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 8: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

About this document

Version Date Brief description A6V10222523_f_en 05.2012 New collective / conventional line:

OH110, OP110, HI110, HI112, DB110, DB110D, DB110R, DB110RD, PSR720-1, PSR720-2 New DB722 VdS Approval DBS721 & DBS729

A6V10222523_g_en 11.2012 SWING (new), VdS ALB24.1 & AGN24.6 A6V10222523_h_en 03.2013 New naming for FDS229, DBS729

New products: RE8ST, RE8STCO A6V10222523_i_en 12.2013 New products: FDA221, FD241, FDB295, BA721, FDUZ227 A6V10222523_j_en 04.2014 Update of LPCB numbers, content update

Download The current issue documentation and photos can be found in the Siemens Intranet. https://workspace.sbt.siemens.com/content/00001123/default.aspx (STEP, Asset Portal)

8

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 9: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Automatic fire detectors in C-NET

2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms

OOH740 Multi sensor smoke detector, ASA Part no. S54320-F7-A3 Documents Product data sheet A6V10284161

Techn. description A6V10305793 Scope of delivery Detector and dust cap

Application For the detection of flaming fires caused by the combustion of liquid and solid mAtters, as well as smol-dering fires. For reliable fire detection in environments with deceptive phenomena. Function Works according to the scattered-light principle with two sensors, optical forward and backward scatter-ing. Opto-electronic sampling chamber blocks disturbing extraneous light but optimally detects both dark and light smoke particles. Two additional heat sensors increase the fire detector’s immunity to deceptive phenomena. The base must be ordered separately. Technical data Communication protocol C-NET or collectiv Operating voltage (modulated) DC 12…33 V Operating current (quiescent) ~170…250 μA Ext. alarm indicator 2 Operating temperature -25…+55 °C Storage temperature -30…+70 °C Humidity ≤95 % rel. Color white, ~RAL 9010 Protection category EN 60529/IEC 60529 – with detector base seal RS720

IP40 IP44 with detector base seal RS720

System compatibility C-NET FS720 Standards CEA 4021, EN 54-5, EN 54-7, EN 54-17 Dimensions (detector with base) Ø117 x 49 mm (incl. base) Approvals VdS G211070, LPCB 126bh/05

9

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 10: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Automatic fire detectors in C-NET

OOHC740 Fire and CO detector, neural ASA Bestell-Nr. S54320-F8-A3 Documents Product data sheet A6V10284161

Techn. description A6V10305793 Scope of delivery Detector and dust cap

Application Fire and CO detector for very early and reliable detection of emerging fire, due to analysis of the three criteria smoke, heat and gas. Very fast response to all carbon monoxide (CO) generating fires and very early and reliable alarming in environments with deceptive phenomena. Function Works according to the scattered-light principle with two sensors, optical forward and backward scatter-ing. Opto-electronic sampling chamber blocks disturbing extraneous light but optimally detects both dark and light smoke particles. Two additional heat sensors and an additional CO sensor increase the fire detector’s immunity to deceptive phenomena and the response characteristics of the fire detector. Se-lectable detection behavior by application-specific ASA parameter sets. The additional CO analy-sis mAkes it exceptionally fast and ideal for applications where the occupants mAke speed of detection critical (e.g. nursing homes, hospitals, sheltered accommodations etc.). The base must be ordered separately. Technical data Communication protocol C-NET Operating voltage (modulated) DC 12…33 V Operating current (quiescent) ~300…380 μA Ext. alarm indicator 2 Operating temperature -10…+50 °C Storage temperature -20…+55 °C Humidity ~15…90 % rel. Color weiss, ~RAL 9010 Protection category EN 60529/IEC 60529 – with detector base seal RS720

IP40 IP44 with detector base seal RS720

System compatibility C-NET FS720 Standards CEA4021, EN 54-5, EN 54-7, EN 54-17,

LPS1279, VdS2806 Dimensions (detector with base) Ø117 x 49 mm Approvals VdS G211047, LPCB 126bh/06

10

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 11: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Automatic fire detectors in C-NET

OH720 Multi sensor smoke detector Part no. S54310-F2-A1 Documents Product data sheet A6V10202198

Technical description A6V10212047 Scope of delivery Detector and dust cap

Application For the detection of flaming fires caused by the combustion of liquid and solid mAtters, as well as smol-dering fires. For reliable fire detection in environments with deceptive phenomena. Addressable applicable. Function Works according to the scattered light principle with one sensor, optical forward scattering. Opto-electronic sampling chamber holds off disturbing extraneous light but optimally detects smoke particles. An additional heat sensor increases the fire detector’s immunity to deceptive phenomena. Selectable detection behavior by different parameter sets. Immunity against transient false alarm causes Technical data Communication protocol C-NET Operating voltage (modulated) DC 12…33 V Operating current (quiescent) ~230 μA Ext. alarm indicator 2 Permissible air speed max. 5 m/s Operating temperature -10…+50 °C Storage temperature -30…+70 °C Humidity ≤95 % rel. Color white, ~RAL 9010 Protection category EN 60529/IEC 60529 – with detector base seal RS720

IP40 IP42

System compatibility C-NET FS720 Standards CEA 4021 / EN 54-7 / EN 54-17 Dimensions (detector with base) Ø117 x 59 mm

Approvals VdS G209064, LPCB 531d/01

OP720 Smoke detector Part no. S54310-F1-A1 Documents Product data sheet A6V10202198

Techn. description A6V10212047 Scope of delivery Detector and dust cap

Application For the detection of smoke-generating flaming and smoldering fires. Addressable applicable. Function Works according to the scattered light principle with one sensor, optical forward scattering. Opto-electronic sampling chamber holds off disturbing extraneous light but optimally detects smoke particles. Selectable detection behavior thanks different parameter sets. Technical data Communication protocol C-NET Operating voltage (modulated) DC 12…33 V Operating current (quiescent) ~220 μA Ext. alarm indicator 2 Permissible air speed max. 5 m/s Operating temperature -10…+50 °C Storage temperature -30…+70 °C Humidity ≤95 % rel. Color white, ~RAL 9010 Protection category EN 60529/IEC 60529 – with detector base seal RS720

IP40 IP42

System compatibility C-Net FS720 Standards EN 54-7 / EN 54-17 Dimensions (detector with base) Ø117 x 56 mm Approvals VdS G209068, LPCB 531e/01

11

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 12: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Automatic fire detectors in C-NET

HI720 Heat detector (static + RoR) Part no. S54310-F4-A1 Documents Product data sheet A6V10202198

Techn. description A6V10212047 Scope of delivery Detector and dust cap

Application Suitable in areas in which occur different environment temperatures. Where high dust or dirt developments or large humidity which can the impact of conventional alarm units to impair. Addressable applicable. Function Equipped with one heat sensor. For high requirements. Certain response behavior with slow and fast temperature increases, also by depth temperature. Selectable detection behavior by different parameter sets. Technical data Communication protocol C-NET Operating voltage (modulated) DC 12…33 V Operating current (quiescent) ~200 μA Ext. alarm indicator 2 Operating temperature -10…+50 °C Storage temperature -30…+70 °C Humidity ≤95 % rel. Color white, ~RAL 9010 Protection category EN 60529/IEC 60529 – with detector base seal RS720

IP40 IP42

System compatibility C-NET FS720 Standards EN 54-5 / EN 54-17 Dimensions (detector with base) Ø117 x 59 mm Approvals VdS G209065, LPCB 531f/01

12

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 13: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Automatic fire detectors in C-NET

HI722 Heat detector (static) Part no. S54310-F3-A1 Documents Product data sheet A6V10202198

Techn. description A6V10212047 Scope of delivery Detector and dust cap

Application Suitable in areas, in which temporary high variations in temperature arise. Where high dirt and heat fluctuation which can the impact of conventional alarm units to impair. Addressable applicable. Function Equipped with one heat sensor. Measures permanent the ambient temperature, with exceeding of the mAximum temperature, the detec-tor sends a danger signal to control panel, at short term exceeding no alarming takes place. Technical data Communication protocol C-NET Operating voltage (modulated) DC 12…33 V Operating current (quiescent) ~200 μA Ext. alarm indicator 2 Operating temperature -10…+50 °C Storage temperature -30…+70 °C Humidity ≤95 % rel. Color white, ~RAL 9010 Protection category EN 60529/IEC 60529 – with detector base seal RS720

IP40 IP42

System compatibility C-NET FS720 Standards EN 54-5 / EN 54-17 Dimensions (detector with base) Ø117 x 59 mm Approvals VdS G209146, LPCB 531f/02

2.1.1 Accessories for point detectors

LP720 Detector locking device Part no. S54319-F9-A1

Application Threaded pin M3 x 12 to protect detector against theft. Scope of delivery 2 hexagonal wrenches, 100 threaded pins Technical data Threaded pin M3 x 12 Hexagonal wrench 1.5 mm

13

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 14: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Automatic fire detectors in C-NET

2.2 Detector bases

DB721 Detector base with loop contact Part no. S54319-F11-A1

Application For all point detectors of the series Cerberus PRO FD720. Technical data Color white, ~RAL 9010 Dimensions Ø117 x 23 mm

DB721D Detector base Part no. S54319-F15-A1

Application Universal base for the OOH740 point detector of the series Cerberus PRO FD720 in collective mode. Diode removable Technical data Color white, ~RAL 9010 Dimensions Ø117 x 23 mm

DB722 Detector base Part no. S54319-F19-A1

Application The DB722 is a universal base with detector base seal and screwless terminals for the point detectors of the series Cerberus PRO FD720. Technical data Color white, ~RAL 9010 Dimensions Ø117 x 23 mm

DBS720 Sounder base Part no. S54319-F5-A1 Details see chapter 5.3

14

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 15: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Automatic fire detectors in C-NET

2.2.1 Accessories for detector bases

FDBZ291 Designation plate Part no. A5Q00002621

10 pieces

Application To identify the location address. Compatibel to bases FDB221, FDB222, DB720, FDB271, base attachment FDB291 and sounder base DBS720. Technical data Color transparent Dimensions 62 x 35 mm

RS720 Detector base seal Part no. S54319-F8-A1

10 pieces

Application For higher protection category. Compatible with base DB720 and sounder base DBS720. Note: Not usable together with the designation plate FDBZ291. Technical data Color transparent Dimensions Ø119 x 6.5 mm

BA720 Base attachment Part no. S54319-F20-A1

Application For the supply of surface-mounted tubes (max. 20 mm) and trunking (max. 25 mm x 15 mm). The detec-tor is fixed with a spring-loaded catch. Note: mounting slots 46...90 mm. Technical data Color white, ~RAL 9010 Dimensions Ø120 x 25 mm

DBZ1190-AA Micro terminal Part no. BPZ:4677080001 DBZ1190-AB Auxiliary terminal Part no. BPZ:4942340001 DBZ1190-AA

50 pieces DBZ1190-AB

50 pieces

Application As cross-connection point for T branches, external alarm indicators (AI), cable shielding, or for the con-nection of a power supply. Technical data DBZ1190-AA for conductors 0.28…0.5 mm2 / 4-pole Dimensions 7 x 10 x 10 mm DBZ1190-AB for conductors 1.0…2.5 mm2 / 3-pole Dimensions 13.5 x 9.5 x 19.5 mm

15

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 16: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Automatic fire detectors in C-NET

2.3 Linear smoke detector FDL241-9 with ASAtechnology™

FDLB291 Base for linear smoke detector Part no. A5Q00003941 FDL241-9 Linear smoke detector Part no. A5Q00002298 Documents Product data sheet 007017 FDLB291

FDL241-9

Technical description 007016

Application Large storerooms and production workshops. Areas with complex roof structures or historically valuable ceilings. Covered courtyards. Atrium-type buildings. Reception halls. Can be used as an addressable or collective, conventional device. Function The detector consists of a light emitter and a light receiver. The light emitter emits a bundled infrared ray, which is scattered back by the prism-shaped reflector to the light emitter. The receiver converts the received infrared signal in an electric signal, which is evaluated by the microprocessor-controlled elec-tronics. Smoke penetrating the measuring section attenuates the infrared signal. When the signal reaches pre-defined measuring values, the detector transmits the corresponding danger level to the control unit. Distance measurement for the recognition of foreign mAtters. The built-in alarm indicator signals the alarm status locally. Max. Detection distance 5 – 100m. Technical data Communication protocol C-NET, collective, conventional Operating voltage addressable / collective, conven-tional

DC 12…33 V / DC 18…28 V

Operating current addressable, collective, conven-tional

1.5 mA

Ext. alarm indicator 1 Operating temperature -25…+60 °C Storage temperature -30…+75 °C Humidity ≤95 % rel. Color white, ~RAL 9010 Protection category EN 60529/IEC 60529 IP65 System compatibility C-NET FS720 System compatibility collective, conventional CZ10, BC10, FC10, XC10, CS11, FC700A,

FC330A, SIGMASYS, BMS, SM80/88/D100 Standards EN 54-12, EN 54-17 Dimensions 135 x 135 x 115 mm Approvals VdS G204063, LPCB 126bd/02

16

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 17: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Automatic fire detectors in C-NET

2.3.1 Accessories for FDL241-9

DLR1191 Long distance reflector (Prism) Part no. BPZ:4787710001 DLR1192 Middle distance reflector (400cm2) Part no. BPZ:4788490001 DLR1193 Short distance reflector (100cm2) Part no. BPZ:4787840001 DLR1191

DLR1192

DLR1193

Application Reflectors to the linear smoke detector incl. detector heating. Function Light rays arriving are reflected parallel. Any extraneous light is also reflected in its own direction and consequently does not reach the receiver. The retro reflecting prism in the DLR1191 has the shape of a pyramid that's lateral faces are formed by isosceles orthogonal triangles. Light beams entering through the base are completely reflected twice on the lateral faces and reflected back through the base. In principle, the reflector foil has the same effect (function) as the prism. Technical data Long distance reflector (Prism) for 20-100 m Supply for detector heater DC 24 V Dimensions 135 x 135 x 65 mm Middle distance reflector (400 cm2) for 30-65 m Dimensions 200 x 200 x 2.5 mm Short distance reflector (100 cm2) for 10-30 m Dimensions 100 x 100 x 2.5 mm

DLF1191-AA Short distance filter 7-10m Part no. BPZ:4933030001 DLF1191-AB Short distance filter 5-8m Part no. BPZ:4933160001 DLF1191-AC Extraneous light filter Part no. BPZ:5221480001 DLF1191-AA

DLF1191-AB, DLF1191-AC

Application The short distance filter is required for short distance of 5-10 m. The extraneous light filter is required at powerful external light causes interference Only one filter possible.

DLH1191A Detector heating element Part no. BPZ:4787970001

Application In the event of danger of condensation of the linear smoke detector. Technical data Operating voltage DC 20…30 V Operating current 30…50 mA Resistance 600 Ω

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478

10 pieces

Application For surface cable entry. Technical data Material Ms nickel-plated Dimensions M20 x 1.5

17

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 18: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Automatic fire detectors in C-NET

2.4 Infrared flame detector FDF221-9 with detection algorithms

FDFB291 Base for infrared flame detector Part no. A5Q00003310 FDF221-9 Infrared flame detector (1 Sensor) Part no. A5Q00003902 Documents Product data sheet 007012 FDFB291

FDF221-9

Technical description 007011

Application For simple applications, additional to smoke detectors. Detection of smokeless combustible liquid and gas fires, as well as smoke-forming open fire involving carbonaceous mAterials as contained in wood, plastics, gases, oil products etc. Only used without source of interference as sun, halogen light, and blackbody radiation. Can be used as an addressable, collective or conventional device. Function 1 infrared sensor with detection algorithms. Technical data Communication protocol C-NET, collective, conventional Operating voltage addressable / collective, conven-tional (quiescent)

DC 12…33 V / DC 16…28 V

Operating current addressable / collective, conven-tional (quiescent)

0.7 mA / 0.5 mA

Ext. alarm indicator 2 Connection terminals 0.2…1.5 mm2 Operating temperature -25…+70 °C Storage temperature -40…+75 °C Humidity ≤95 % rel. Color white, ~RAL 9010 Protection category EN 60529/IEC 60529 IP44 System compatibility C-NET FS720 System compatibility collective, conventional CZ10, BC10, FC10, XC10, CS11, FC700A,

FC330A, SIGMASYS, BMS, SM80/88/D100 Standards EN 54-10, EN 54-17 Dimensions 135 x 135 x 77 mm Approvals VdS G204009, LPCB 126bc/04

18

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 19: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Automatic fire detectors in C-NET

2.5 Infrared flame detector FDF241-9 with ASAtechnology™

FDFB291 Base for infrared flame detector Part no. A5Q00003310 FDF241-9 Infrared flame detector (3Sensors) Part no. A5Q00003006 Documents Product data sheet 007012 FDFB291

FDF241-9

Technical description 007011

Application Detects smokeless liquid and gas fires as well as smoke-generating open fires resulting from the com-bustion of carbonaceous mAterials such as wood, synthetics, gases, oil products, etc. Large industrial warehouses, Hangars for military and civil aircraft, Underground tunnels etc. Can be used as an addressable, collective or conventional device. Function 3 infrared sensors with ASAtechnology™. Technical data Communication protocol C-NET, collective, conventional Operating voltage addressable / collective, conven-tional (quiescent)

DC 12…33 V / DC 14…28 V

Operating current addressable / collective, conven-tional (quiescent)

0.7 mA / 0.5 mA

Ext. alarm indicator 2 Anschlussklemmen 0.2…1.5 mm2 Operating temperature -35…+70 °C Storage temperature -40…+75 °C Humidity ≤95 % rel. Color white, ~RAL 9010 Protection category EN 60529/IEC 60529 IP67 System compatibility C-NET FS720 System compatibility collective, conventional CZ10, BC10, FC10, XC10, CS11, FC700A,

FC330A, SIGMASYS, BMS, SM80/88/D100 Standards EN 54-10, EN 54-17 Dimensions 135 x 135 x 77 mm Approvals VdS G204010, LPCB 126bc/05

19

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 20: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Automatic fire detectors in C-NET

2.5.1 Accessories for FDF221-9, FDF241-9

MV1 Mounting bracket Part no. BPZ:3950450001 MWV1 Ball and socket joint Part no. BPZ:3674840001 DFZ1190 Rain hood Part no. BPZ:5302660001 Document Product data sheet 007012 MV1

MWV1

DFZ1190

Application MV1 The mounting bracket for volumetric surveillance, fixed the detector in the right angle. MWV1 Ball and socket joint for the flame detector for the orientation to a defined object. DFZ1190 Rain hood for the flame detector for outdoor applications. Technical data Mounting bracket Dimensions 136 x 120 x 120 mm Ball and socket joint Dimensions 120 x 164 x 118 mm Rain hood Dimensions 150 x 165 x 130 mm

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 For details, see chapter 2.3.1

20

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 21: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Alarm indicators for C-NET devices

3 Alarm indicators for C-NET devices 3.1 Door frame version FDAI91

FDAI91 Alarm indicator (door frame), resistor 75 Ω Part no. S54370-F9-A1 Documents Product data sheet A6V10276520

Technical description A6V10257736 Application Alarm indicators are connected in parallel to automatic fire detectors in order to indicate quickly the source of an alarm signal from detectors, which are not easily accessible or visible. For recess supply line. Function The LEDs in the alarm indicator are on, as soon as the appropriate detector is in alarm. Technical data Operating voltage DC 5…8 V Operating current, permanent max. 35 mA Screwless connection terminals Wire cross-sectional area max. 1.5 mm2 Environmental temperature -25…+80 °C Humidity ≤95 % rel. Protection category EN 60529/IEC 60529 IP40 Color white, ~RAL 9010 Dimensions 62 x 37 x 24 mm

3.2 Wall versions FDAI92 and FDCAI221

FDAI92 Alarm indicator (wall mounting), resistor 75 Ω Part no. S54370-F3-A1 Documents Product data sheet A6V10276520

Technical description A6V10257736 Application Alarm indicators are connected in parallel to automatic fire detectors in order to indicate quickly the source of an alarm signal from detectors, which are not easily accessible or visible. For recess supply line. For surface supply line use adapter frame AI330. Function The LEDs in the alarm indicator are on, as soon as the appropriate detector is in alarm Technical data Operating voltage DC 5…8 V Operating current, permanent max. 35 mA Screwless connection terminals Wire cross-sectional area max. 1.5 mm2 Environmental temperature -25…+80 °C Humidity ≤95 % rel. Protection category EN 60529/IEC 60529 IP40 Color white, ~RAL 9010 Dimensions 85 x 85 x 28 mm

21

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 22: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Alarm indicators for C-NET devices

FDCAI221 Addressable alarm indicator, resistor 75 Ω Part no. S54370-F10-A1 Documents Product data sheet A6V10244934

Technical description A6V10258110 Application Addressable alarm indicators are connected in parallel to automatic fire detectors in order to indicate quickly the source of an alarm signal from detectors, which are not easily accessible or visible. The addressable alarm indicator has 2x2 connectors for the detector line For concealed wiring. Function The alarm indicator contains indicator lamps (LEDs). They light up as soon as the connected fire detec-tor gives an alarm. Technical data Communication protocol C-NET Operating voltage DC 12…33 V Operating current, quiescent 240…400 µA Screwless connection terminals Wire cross-sectional area max. 1.5 mm2 Operating temperature -10…+55 °C Storage temperature -30…+70 °C Humidity ≤95 % rel. Color white, ~RAL 9010 Protection category EN 60529/IEC 60529 IP40 System compatibility C-NET FS720 Standards EN 54-17, EN 54-18 Dimensions 85 x 85 x 32 mm

Approval VdS G210015

3.2.1 Accessory for wall versions

AI330 Adapter frame Part no. BPZ:3169430001

Application For surface laid conduit or ducts, to increase the loop space or as an adapter for different mAkes of box. Technical data Color white, ~RAL 9010 Dimensions 85 x 85 x 16 mm

22

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 23: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Manual call points in C-NET

4 Manual call points in C-NET 4.1 Manual call point FDM221 with direct operation

FDMH291-R Housing red with key Part no. A5Q00002217 FDMH291-Y Housing yellow with key Part no. A5Q00004979 FDMH291-B Housing blue with key Part no. A5Q00004980 FDMH291-G Housing green with key Part no. A5Q00004981 FDME221 Switching unit Part no. A5Q00002451 Documents Product data sheet 007001

Technical description 007002

Application For the immediate manual actuation of an alarm. For indoor and outdoor application. For surface- and recess-mounted feed lines in easily accessible places. Addressable applicable. Function Direct alarm actuation by pushing in the glass plate. By replacing the glass plate the push button is set back and the device is ready for operation again. Technical data Communication protocol C-NET Operating voltage DC 12…33 V Operating current (quiescent) 200 μA Connection terminals 0.28…1.5 mm2 Operating temperature -25…+70 °C Storage temperature -30…+75 °C Humidity ≤95 % rel. Color red, ~RAL 3000, blue, ~RAL 5005,

yellow, ~RAL 1023, green, ~RAL 6024 Protection category EN 60529/IEC 60529 IP44 System compatibility C-NET FS720 Standards EN 54-11, EN 54-17 Dimensions 87 x 87 x 46.6 mm Approvals VdS G203059, LPCB 531k/07

23

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 24: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Manual call points in C-NET

4.1.1 Accessories for FDM221

FDMC291 Protective cover Part no. A5Q00001644

5 pieces

Application Protects the manual call point from unintentional glass break. Technical data Color transparent

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 – Back nut Part no. A5Q00004479

10 pieces

10 pieces

Application For surface-mounted feed lines. Technical data Cable gland Dimensions M20 x 1.5 Back nut Dimensions M20

4.1.2 Spare parts for FDM221

FDMG291 Glass Part no. A5Q00002122

10 pieces

Application Use as spare part. Technical data Color transparent

FDMK291 Cover with key Part no. A5Q00001643

Application Use as spare part. Technical data Color red, ~RAL 3000

24

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 25: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Manual call points in C-NET

4.2 Manual call points FDM225/226 with direct operation

FDM225-RG Manual call point with glass plate Part no. A5Q00013434 FDM225-RP Manual call point with plastic element Part no. A5Q00012020 FDM226-RG Manual call point with glass plate incl. housing

base Part no. A5Q00013435

FDM226-RP Manual call point with plastic element incl. housing base

Part no. A5Q00013436

Documents Product data sheet 009023 FDM225-RG, FDM225-RP

FDM226-RG, FDM226-RP

Technical description 009757

Application For the immediate manual actuation of a fire alarm. For indoor and outdoor application. FDM225 for surface and recess mounting in easily accessible places. FDM226 for surface mounting for IP67 applications Addressable applicable. Function FDM225/226-RG – Direct alarm actuation by pushing in the glass plate. – By replacing the glass plate the push button is set back and the device is ready for operation again. FDM225/226-RP – Direct alarm actuation by pushing on the plastic element. – The switch is set back with the key and the device is ready for operation again. An additional protective cover FDMC295 protects the manual call point from unintentional glass break. Technical data Communication protocol C-NET Operating voltage DC 13…33 V Operating current (quiescent) 180 μA Connection terminals 0.28…1.5 mm2 Operating temperature -25…+70 °C Storage temperature -30…+75 °C Humidity ≤95 % rel. Color red, ~RAL 3000 Protection category EN 60529/IEC 60529 – FDM225 – FDM226

IP44 IP66

System compatibility C-NET FS720 Standards EN 54-11, EN 54-17 Dimensions – FDM225 – FDM226

87 x 87 x 20 mm 87 x 87 (113) x 57 mm

Approvals – FDM225-RG – FDM225-RP – FDM226-RG – FDM226-RP

VdS G207092, LPCB 126ap/02 VdS G207092, LPCB 126ap/01 VdS G209194, LPCB 126ap/04 VdS G209194, LPCB 126ap/03

25

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 26: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Manual call points in C-NET

FDMH295-R Back box Part no. A5Q00013437 FDMH295-S Back box with holes and socket Part no. A5Q00013438 FDMH295-R

10 pieces FDMH295-S

10 pieces

Application Housing base for manual call points FDM225, FDM1101 and FDM1101A for surface mounting. Technical data Color red, ~RAL 3000 Dimension (WxHxD) 87 x 87 x 33 mm FDMH295-S With 2 holes and 2 sockets for cable up to Ø5 mm

4.2.1 Accessories for FDM225, FDM226

FDMC295 Protective cover Part no. A5Q00013440

10 pieces

Application Protects the manual call point from unintentional glass break. Technical data Color transparent

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 – Back nut Part no. A5Q00004479 Details see chapter 4.1.1

DBZ1190-AB Auxiliary terminal Part no. BPZ:4942340001 Details see chapter 2.2.1

26

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 27: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Manual call points in C-NET

4.2.2 Spare parts for FDM225, FDM226

FDMG295 Glass palte 'neutral' Part no. A5Q00013442 FDMP295 Plastic element 'neutral' Part no. A5Q00013445 FDMG295

5 pieces FDMP295

5 pieces

Application Use as spare part.

FDMK295 Key Part no. A5Q00013448

5 pieces

Application Use as spare part.

27

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 28: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Manual call points in C-NET

4.3 Manual call point FDM224 with direct operation

FDMH293-R Housing red with glass and key Part no. A5Q00004023 FDMH293-Y Housing yellow with glass and key Part no. A5Q00004908 FDMH293-B Housing blue with glass and key Part no. A5Q00004909 FDMH293-G Housing green with glass and key Part no. A5Q00004911 FDMH293-O Housing orange with glass and key Part no. S54311-F2-A1 FDME224 Switching unit Part no. A5Q00009392 Documents Product data sheet 007001

Technical description 007002

Application For the immediate manual actuation of an alarm. For indoor and outdoor application, equally suited for wet, humid and dusty areas. For surface- and recess-mounted feed lines in easily accessible places. Addressable applicable. Function Direct alarm actuation by smashing in the glass plate. To replace the glass plate, open the housing door with the key, upon closing the door the button is reset. Technical data Communication protocol C-NET Operating voltage DC 12…33 V Operating current (quiescent) 200 μA Ext. alarm indicator 2 Connection terminals 0.28…1.5 mm2 Operating temperature -25…+70 °C Storage temperature -30…+75 °C Humidity ≤95 % rel. Color red, ~RAL 3000,

yellow, ~RAL 1023, blue, ~RAL 5005, green, ~RAL 6024, orange, ~RAL 2011

Protection category EN 60529/IEC 60529 – with seal DMZ1197-AD

IP44 IP64

System compatibility C-NET FS720 Standards EN 54-11, EN 54-17 Dimensions 134,3 x 134,3 x 43,2 mm Approvals VdS G206123, LPCB 531k/10

28

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 29: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Manual call points in C-NET

4.4 Manual call point 'Heavy Duty' FDM224H with direct operation

FDMH292-R Housing Heavy Duty red Part no. A5Q00005525 FDME224 Switching unit Part no. A5Q00009392 Documents Product data sheet 008345 FDMH292-R

FDME224

Technical description 007002 Application For the immediate manual actuation of a fire alarm. For indoor and outdoor application, equally suited for wet, humid and dusty areas. Only for surface mounted feed lines in easily accessible places, Tunnels, Industry. Addressable. The housing is equipped with one opening at the top and two openings at the bottom for nipples (en-closed) and for M20 metal screwed cable glands –> see accessory. For IP66 applications the unused openings must be locked with the V-plug –> see accessory. Function Direct alarm actuation by smashing in the glass plate. To replace the glass plate, open the housing door with the key, upon closing the door the button is reset. Technical data Communication protocol C-NET Operating voltage DC 12…33 V Operating current (quiescent) 200 μA Ext. alarm indicator 2 Connection terminals 0.28…1.5 mm2 Operating temperature -25…+70 °C Storage temperature -30…+75 °C Humidity ≤95 % rel. Color red, ~RAL 3000 Protection category EN 60529/IEC 60529 – with seal DMZ1197-AD and V-plug

IP44 IP64

System compatibility C-NET FS720 Standards EN 54-11, EN 54-17 Dimensions 134.3 x 134.3 x 43.2 mm Approvals VdS G206124, LPCB 531k/11

4.4.1 Accessories for FDM224, FDM224H

DMZ1197-AC Protective cover Part no. BPZ:5223550001

5 pieces

Application Protects the manual call point from unintentional glass break. Technical data Color transparent

DMZ1197-AD Seal for wet areas Part no. BPZ:5470680001

5 pieces

Application Protects the manual call point in wet applications. Technical data Color transparent

29

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 30: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Manual call points in C-NET

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 Details see chapter 2.3.1

– V-plug PA M20 x 1.5 Part no. A5Q00008131

Application For locked the unused openings at the housing FDMH292-R. Technical data Color black Dimensions M20 x 1.5 mm

– Locking plug red, M20 x 1.5 (1 hole) Part no. A5Q00006735 – Locking plug red, M20 x 1.5 (2 holes) Part no. A5Q00010055 Locking plug 1 hole (10 pcs.)

Locking plug 2 holes (10 pcs.)

Application For surface-mounted feed lines. For the application in dry rooms. Technical data Color red Dimensions M20 x 1.5

4.4.2 Spare parts for FDM224, FDM224H

DMZ1196-AC Glass Part no. BPZ:4942050001

10 pieces

Application Use as spare part.

DMZ1195 Key Part no. BPZ:4851910001

10 pieces

Application Only for housing FDMH293-x Use as spare part.

30

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 31: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Manual call points in C-NET

4.5 Manual call point FDM223 complete with indirect operation

FDM223 Manual call point complete, housing red with

glass , key, switching unit and locking plug Part no. A5Q00008098

Documents Product data sheet 007001

Technical description 007002

Consists of: – Housing red – Glass – Key – Switching unit – 2 locking plugs (2 holes)

– 2 labels standard with house and Feuerwehr/Brandmelder Application For the immediate manual actuation of a fire alarm. For indoor and outdoor application, equally suited for wet, humid and dusty areas. For surface- and recess-mounted feed lines in easily accessible places. Addressable applicable. Function Indirect alarm actuation by smashing in the glass plate and pressing the push button. To replace the glass plate, open the housing door with the key. The push button must be set back be-fore closing the door again. Technical data Communication protocol C-NET Operating voltage DC 12…33 V Operating current (quiescent) 200 μA Ext. alarm indicator 2 Connection terminals 0.28…1.5 mm2 Operating temperature -25…+70 °C Storage temperature -30…+75 °C Humidity ≤95 % rel. Color red, ~RAL 3000 Protection category EN 60529/IEC 60529 – mit Dichtung DMZ1197-AD

IP44 IP64

System compatibility C-NET FS720 Standards EN 54-11, EN 54-17 Dimensions 134.3 x 134.3 x 43.2 mm Approvals VdS G204002, LPCB 531k/08

31

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 32: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Manual call points in C-NET

4.6 Manual call point FDM223 with indirect operation

FDMH293-R Housing red with glass and key Part no. A5Q00004023 FDMH293-Y Housing yellow with glass and key Part no. A5Q00004908 FDMH293-B Housing blue with glass and key Part no. A5Q00004909 FDMH293-G Housing green with glass and key Part no. A5Q00004911 FDME223 Switching unit Part no. A5Q00003087 Documents Product data sheet 007001

Technical description 007002

Application For the immediate manual actuation of an alarm. For indoor and outdoor application, equally suited for wet, humid and dusty areas. For surface- and recess-mounted feed lines in easily accessible places. Addressable applicable. Function Indirect alarm actuation by smashing in the glass plate and pressing the push button. To replace the glass plate, open the housing door with the key. The push button must be set back be-fore closing the door again. Technical data Communication protocol C-NET Operating voltage DC 12... 33 V Operating current (quiescent) 200 μA Ext. alarm indicator 2 Connection terminals 0.28…1.5 mm2 Operating temperature -25…+70 °C Storage temperature -30…+75 °C Humidity ≤95 % rel. Color red, ~RAL 3000, blue, ~RAL 5005, yellow,

~RAL 1023, green, ~RAL 6024 Protection category EN 60529/IEC 60529 – with seal DMZ1197-AD

IP44 IP64

System compatibility C-NET FS720 Standards EN 54-11, EN 54-17 Dimensions 134.3 x 134.3 x 43.2 mm Approvals VdS G204002, LPCB 531k/08

32

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 33: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Manual call points in C-NET

4.7 Manual call point 'Heavy Duty' FDM223H with indirect opera-tion

FDMH292-R Heavy Duty housing red with glass, hexagon wrench key, 3 nipples and plate fire brigade / fire detector

Part no. A5Q00005525

FDME223 Switching unit Part no. A5Q00003087 Documents Product data sheet 008345 FDMH292-R

FDME223

Technical description 007002

Application For the immediate manual actuation of a fire alarm. For indoor and outdoor application, equally suited for wet, humid and dusty areas. Only for surface mounted feed lines in easily accessible places, Tunnels, Industry etc. Addressable. The housing is equipped with one opening at the top and two openings at the bottom for nipples (en-closed) and for M20 metal screwed cable glands –> see accessories. For IP66 applications the unused openings must be locked with the V-plug –> see accessories. Function Indirect alarm actuation by smashing in the glass plate and pressing the push button. To replace the glass plate, open the housing door with the key. The push button must be set back be-fore closing the door again. Technical data Communication protocol C-NET Operating voltage DC 12…33 V Operating current (quiescent) 200 μA Ext. alarm indicator 2 Connection terminals 0.28…1.5 mm2 Operating temperature -25…+70 °C Storage temperature -30…+75 °C Humidity ≤95 % rel. Color red, ~RAL 3000 Protection category EN 60529/IEC 60529 – with seal DMZ1197-AD and V-plug

IP44 IP64

System compatibility C-NET FS720 Standards EN 54-11, EN 54-17 Dimensions 134.3 x 134.3 x 43.2 mm Approvals VdS G205014, LPCB 531k/09

4.7.1 Accessories for FDM223, FDM223H

DMZ1197-AC Protective cover Part no. BPZ:5223550001 Details see chapter 4.4.1

DMZ1197-AD Seal for wet areas Part no. BPZ:5470680001 Details see chapter 4.4.1

33

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 34: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Manual call points in C-NET

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 Details see chapter 2.3.1

– V-plug PA M20 x 1.5 Part no. A5Q00008131 Details see chapter 4.4.1

– Locking plug red, M20 x 1.5 (1 hole) Part no. A5Q00006735 – Locking plug red, M20 x 1.5 (2 holes) Part no. A5Q00010055 Details see chapter 4.4.2

4.7.2 Spare parts for FDM223, FDM223H

DMZ1196-AC Glass Part no. BPZ:4942050001 Details see chapter 4.4.2

DMZ1195 Key Part no. BPZ:4851910001 Details see chapter 4.4.2

34

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 35: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Alarm devices in C-NET

5 Alarm devices in C-NET 5.1 Alarm sounders FDS221

FDS221-R Alarm sounder red Part no. A5Q00004117 FDS221-W Alarm sounder white Part no. A5Q00006711 Documents Product data sheet A6V10203095 FDS221-R

FDS221-W

Technical description 008109

Application Only applicable with addressable detector base FDB221 or FDB222. For recess supply line. For surface supply line with FDB221 until cable 6 mm in diameter, otherwise use base attachment FDB291. Along escape routes, corridors, staircases and is mounted on the wall or on the ceiling. Function Loud alarming in case of fire alarm, clearly recognizable as danger signal. Synchronized of acoustic signals with all other alarm sounder devices and sounder bases in the same detector line (C-NET). Technical data Communication protocol C-NET Operating voltage DC 12…33 V Operating current quiescent condition Operating current ton activated

250 μA 3.5 mA

Ext. alarm indicator 2 Connection terminals according to the detector base Number of sounds 11; 2 activation levels, 3 sound intensities Sound intensity 80…99 dB(A) Operating temperature -25…+70 °C Storage temperature -30…+75 °C Humidity ≤95 % rel. Color red, ~RAL 3000, white, ~RAL 9010 Protection category EN 60529/IEC 60529 with – Base FDB221 or FDB222 – Base attachment FDB291 – Base FDB221 and sealing element FDBZ295 – Base attachment wet FDB293

mounting on the wall with cable feed from bottom –> IP43, otherwise IP40 IP44 IP54

System compatibility C-NET FS720 Standards EN 54-3, EN 54-17 Dimensions Ø100 x 43 mm Approvals VdS G204073, LPCB 531p/01

35

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 36: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Alarm devices in C-NET

5.2 Alarm sounder with supplementary optical indication FDS229

FDS229-R Alarm sounder with supplementary optical indi-

cation, red Part no. A5Q00023093

FDS229-A Alarm sounder with supplementary optical indi-cation, orange

Part no. A5Q00023092

Documents Product data sheet A6V10229545 FDS229-R

FDS229-A

Technical description 010095 Application Only applicable with addressable detector base FDB221 or FDB222. For recess supply line. For surface supply line with FDB221 until cable 6 mm in diameter, otherwise use base attachment FDB291. Along escape routes, corridors, staircases and is mounted on the wall or on the ceiling. Function Acoustic and optical alarming in case of fire alarm, clearly recognizable as danger signal. Synchronized of acoustic signals with all other alarm sounder devices and sounder bases in the same detector line (C-NET). Technical data Communication protocol C-NET Operating voltage DC 12…33 V Operating current quiescent condition – Operating current ton activated – Operating current beacon activated – Operating current ton and beacon activated

250 μA 3.5 mA 3.5 mA 7.0 mA

Sounds 11; 2 activation levels, 3 sound intensities Sound intensity 80…99 dB(A) Number of flashing pattern 1 (intermittent) Light intensity (unit: candela, cd) at DC 32 V (depending of viewing angle -30…+30°): – with hood red – with hood orange

1.27…3.2 cd 1.1…2.8 cd

Ext. alarm indicator 2 Connection terminals according to the detector base Operating temperature -25…+70 °C Storage temperature -30…+75 °C Humidity ≤95 % rel. Color transparent red, transparent orange Protection category EN 60529/IEC 60529 with – Base FDB221 or FDB222 – Base attachment FDB291 – Bsse FDB221 and sealing element FDBZ295 – Base attachment wet FDB293

mounting on the wall with cable feed from bottom –> IP43, otherwise IP40 IP44 IP54

System compatibility C-NET FS720 Standards EN 54-3, EN 54-17 Dimensions Ø100 x 43 mm Approvals VdS G207156, LPCB 531p/03, LPCB 531p/02

5.2.1 Accessories for FDS221, FDS229

FDB221 Detector base addressable Part no. A5Q00001664 FDB222 Detector base addressable, flat Part no. S54319-F1-A1 FDB221

FDB222

Application For alarm sounders and alarm sounder with supplementary optical indication. For recess supply line. Only FDB221for surface supply line until cable 6 mm in diameter. Technical data Screwless connecting terminals 'orange' wire cross-sectional area from 0.2…1.5 mm2 Color white, ~RAL 9010 Dimensions – FDB221 – FDB222

Ø100 x 22 mm Ø100 x 17 mm

36

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 37: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Alarm devices in C-NET

FDBZ295 Sealing element Part no. S54319-F10-A1

Application For higher protection category. Use only with base FDB221 and for recess supply wiring. Note: Not usable together with the designation plate FDBZ291. Technical data Dimensions Ø106 x 28 mm

FDBZ293 Detector locking device Part no. A5Q00005035

Application Threaded pin M3 x 6 for protection against theft. Scope of delivery 2 hexagonal wrenches 100 threaded pins Technical data Threaded pin M3 x 6 Hexagonal wrench 1.5 mm

FDBZ291 Designation plate (10x) Part no. A5Q00002621 Details see chapter 2.2.1

DBZ1190-AA Micro terminal Part no. BPZ:4677080001 DBZ1190-AB Auxiliary terminal Part no. BPZ:4942340001 Details see chapter 2.2.1

FDB291 Base attachment Part no. A5Q00001603

Application For the supply of surface-mounted lines > ∅6 mm. Breakouts for surface supply line. Technical data Color white, ~RAL 9010 Dimensions Ø120 x 25 mm

37

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 38: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Alarm devices in C-NET

FDB293 Base attachment wet with seal Part no. A5Q00003945

Application For mounting in humid or wet environments, and when the detector-heating unit is used. Technical data Color white, ~RAL 9010 Dimensions 135 x 135 x 49 mm

FDB295 Base attachment wet Part no. S54319-F21-A1 Document Product data sheet 007775

Installation A6V10331076 Application For mounting in humid and/or cold environments, and when the detector-heating unit is used. IP54 with FDS221-R, FDS221-W, FDS229-R & FDS229-A Technical data Color white, ~RAL 9010 Dimensions 135 x 135 x 53 mm

BA721 Base attachment wet Part no. S54319-F29-A1 Document Product data sheet 007775

Installation A6V10406006 Application For mounting in humid and/or cold environments, and when the detector-heating unit is used. IP44 with Cerberus PRO and 110-series detectors Technical data Color white, ~RAL 9010 Dimensions 135 x 135 x 41 mm

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 Details see chapter 2.3.1

DBZ1193A Designation plate (10x) Part no. BPZ:4864330001

10 pieces

Application To identify the location address. For base attachment wet FDB293. Technical data Color transparent Dimensions 62 x 52 mm

38

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 39: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Alarm devices in C-NET

DBZ1194 Protective cage Part no. BPZ:4677110001

Application For the protection of the detector against damage. Can only be used together with the base attachment wet FDB293. Technical data Dimensions Ø160 x 126 mm

FDBZ294 EMC Protective cage Part no. A5Q00023040 Document Product data sheet 007775

Application To protect the detector from large electromagnetic fields. Can only be used together with the base attachment wet FDB293. Technical data Dimensions Ø140 x 60/90 mm

FDBH291 Detector heating incl. micro terminals Part no. A5Q00004439 Documents Product data sheet 007775

Technical description 007004 Application For the operation of the point fire detectors in critical environments, danger of frost formation or moisture condensation, e.g. in cold storage houses, attics, loading ramps, cheese storage cellars, etc. Optimum function of the detector heating is only ensured with the base attachment wet FDB293, FDB295 and BA721. Technical data Operating voltage (normal operation) DC 20…30 V Operating current 35…55 mA Operating temperature -30…+40 °C Humidity ≤95 % rel.

39

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 40: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Alarm devices in C-NET

5.3 Sounder interbase DBS721, Sounder interbase with supple-mentary optical indication DBS729

BDS721 Sounder interbase Part no. S54372-F13-A1 Documents Product data sheet A6V10277374 DBS721

Technical description A6V10320094 Operating instructions A6V10320096

Application Only with addressable detector base applicable. For recess supply wiring and for surface supply wiring, cable diameter up to 8 mm. For all point detectors designed for Cerberus PRO FD720. In hotel rooms, hospital rooms, nursing homes living rooms and lounges. Function The sounder interbase DBS721 serves for acoustic alarming in an addressed FS720 fire detector sys-tem. The sounder interbase has its own address and can be configured freely with no dependence from its associated detector. Technical data Communication protocol C-NET Operating voltage DC 12…33 V Operating current quiescent condition – Sound activated

250 µA 3,5 mA

Sounds 11, 2 activation levels, 3 sound intensities Sound level 80…87 dB(A) Connection terminals 0.2…1.6 mm2 Operating temperature -25…+65 °C Storage temperature -30…+75 °C Humidity ≤95 % rel. Color White ~RAL9010 / translucent Protection category EN 60529/IEC 60529 with – Base DB720 or DB721 – Detector base sealing RS720

IP21 IP21

System compatibility FDnet FC720 Standards EN 54-3 Typ A, EN 54-17 Dimensions Ø127 x 52 mm Approvals VdS G211083

40

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 41: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Alarm devices in C-NET

DBS729 Sounder interbase with supplementary optical

indication Part no. S54372-F14-A1

Documents Product data sheet A6V10277374 DBS729

Technical description A6V10320094 Operating instructions A6V10320096

Application Only with addressable detector base applicable. For recess supply wiring and for surface supply wiring, cable diameter up to 6 mm. For all point detectors designed for Cerberus PRO FD720. In hotel rooms, hospital rooms, nursing homes living rooms and lounges. Function The sounder interbase DBS729 has the same functionality as DBS721. The configuration of the interbase DBS729 allows in addition an alarming in the addressed FS720 fire system Technical data Communication protocol C-NET Operating voltage DC 12…33 V Operating current quiescent condition – Sound activated – Light activated – Light and Sound activated

250 µA 3,5 mA 1.5/3.5/6.5 mA (low/mid/high) 5/7/10.5 mA (low/mid/high)

Sounds 11, 2 activation levels, 3 sound intensities Sound level 80…87 dB(A) Luminous intensity 1.27…3.2 cd Number of luminous intensity levels 3 levels and 2 flashing modes (not available for all

panels) Connection terminals 0.2…1.6 mm2 Operating temperature -25…+65 °C Storage temperature -30…+75 °C Humidity ≤95 % rel. Color White ~RAL9010 / translucent Protection category EN 60529/IEC 60529 with – Base attachment wet FDB293

IP41C -

System compatibility FDnet FC720 Standards EN 54-3 Typ A, EN 54-17 Dimensions Ø122 x 45 mm Approvals VdS G211084

5.3.1 Accessory for DBS721 and DBS729

BP720 Blanking plate Part no. S54372-B12-A1 Documents Product data sheet A6V10277374

Technical description A6V10320094 Operating instructions A6V10320096

Function If no detector is inserted the blanking plate provides a smooth protection. Technical data Dimensions Ø89 x 8 mm

Color white, ~RAL 9010

FDBZ291 Designation plate Part no. A5Q00002621 Details see chapter 2.2.1

DBZ1190-AA Micro terminal Part no. BPZ:4677080001 DBZ1190-AB Auxiliary terminal Part no. BPZ:4942340001 Details see chapter 2.2.1

41

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 42: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Alarm devices in C-NET

5.4 Sounder base DBS720

DBS720 Sounder base Part no. S54319-F5-A1 Documents Product data sheet A6V10203095

Technical description A6V10218037

Application Compatible to all FD720 point detectors. For surface supply line until cable 8 mm in diameter. The signal base and the detector compose a unity, which already has a base and is mounted on ceil-ings, e.g. in hotel rooms, hospitals and nursing homes. Function The sounder base serves for acoustic alarming in the addressed FS720 fire detection system. In case of a fire alarm, the signal base triggers an acoustic signal in parallel to the flashing of the detec-tor LED. Synchronized of acoustic signals with all other alarm sounder and sounder beacon devices in the same detector line (C-NET). Technical data Communication protocol detector / ton element C-NET / EAI-Link Operating voltage DC 12…33 V Operating current quiescent condition Operating current ton activated

150 μA 1.2 mA

Ext. alarm indicator 2 Number of sounds 11; 2 activation levels, 2 sound intensities Sound intensity 80…88 dB(A) Operating temperature -25…+70 °C (follow data from detector) Storage temperature -30…+70 °C Humidity ≤95 % rel. Connection terminals Wire cross-sectional area from 0.2…1.6 mm2 Color white, ~RAL 9010 Protection category EN 60529/IEC 60529 – with detector base seal RS720

IP41 IP42

System compatibility C-NET FS720 Standards EN 54-3 Dimensions 153 x 93 x 27 mm Approvals VdS G209133

5.4.1 Accessories for DBS720

FDBZ291 Designation plate Part no. A5Q00002621 Details see chapter 2.2.1

RS720 Detector base seal Part no. S54319-F8-A1 Details see chapter 2.2.1

DBZ1190-AA Micro terminal Part no. BPZ:4677080001 DBZ1190-AB Auxiliary terminal Part no. BPZ:4942340001 Details see chapter 2.2.1

42

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 43: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Line separator, Input/output modules in C-NET

6 Line separator, Input/output modules in C-NET 6.1 Line separator FDCL221

FDCL221 Line separator Part no. A5Q00004011 Documents Product data sheet 007065

Technical description 007063

Application To avoid the breakdown of several stub lines in case of a short circuit, line separators mAy be inserted. The line separator is used where several stub lines are connected to the C-NET at one point. Retrofitting of existing, collective systems to the addressed Cerberus PRO FS720 fire detection system. Function The separator is an electronic switch, which is integrated in the C-NET and separates the negative conductor in case of a short circuit, so that the short circuit-free side can continue to be operated. The separator has 2x2 connectors for the detector line. Yellow LED for the status indication signals the short circuit separation. Technical data Communication protocol C-NET Operating voltage DC 12…33 V Operating current 250 μA Operating temperature -25…+70 °C Storage temperature -30…+80 °C Humidity ≤95 % rel. Color transparent Protection category EN 60529/IEC 60529 IP44 System compatibility C-NET FS720 Standards EN 54-17 Dimensions 44 x 47,5 x 10 mm Approvals VdS G204030, LPCB 531n/01

43

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 44: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Line separator, Input/output modules in C-NET

6.2 Multi line separator FDCL221-M

FDCL221-M Line separator Part no. S54312-F6-A1 Documents Product data sheet A6V10230308

Technical description A6V10224006

Application To avoid the breakdown of several stub lines in case of a short circuit, line separators mAy be inserted. The multi line separator is used where several stub lines are connected to the C-NET at one point. The module can also be connected to 2 separate loops Retrofitting of existing, collective systems to the addressed Cerberus PRO FS720 fire detection system. Function The module has total 9 separators. Each separator is an electronic switch, which is integrated in the C-NET and separates the negative conductor in case of a short circuit, so that the short circuit-free side can continue to be operated. The separator has connections for the detector lines, connections for the stub lines (T taps), jumpers for programming of operation mode (1 loop or 2 loop mode), yellow LED for the status indication signals the short circuit separation. Technical data Communication protocol C-NET Operating voltage DC 12…33 V Operating current 2.25 mA (9 x 250 μA) or

2 x 1 mA (4 x 250 μA) Number of separators 9 with 1 loop

2 x 4 with 2 loops Operating temperature -25…+70 °C Storage temperature -30…+75 °C Humidity ≤95 % rel. Color – Housing – Cover – Aux. housing FDCH221

white, ~RAL 9010 Transparent, mAtt white, ~RAL 9010

Protection category EN 60529/IEC 60529 – With ext. Housing FDCH221

IP30 IP65

System compatibility C-NET FS720 Standards EN 54-17 Approvals VdS G209162, LPCB 531n/02

6.2.1 Accessories for FDCL221 / FDCL221-M

– U-rail TS35, L=122 mm Part no. BPZ:5644780001 – U-rail TS35, L=288 mm Part no. BPZ:5644230001

Application For the mounting of the line separator. For the series mounting of input/output modules together with mounting feet.

44

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 45: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Line separator, Input/output modules in C-NET

6.3 Input modules FDCI221, FDCI222

FDCI221 Input module Part no. S54312-F1-A1 Documents Product data sheet A6V10202196 FDCI221

2 Resistors 1 x 3k3; 1 %; 0.25 W 1 x 680 Ω; 1 %; 0.25 W 2 Mounting feet

Technical description A6V10211122

Application For the connection of 1 independent, potential-free mAke or break contact for the acknowledgement of technical states (e.g. door or ventilation control) or for alarm actuation (e.g. sprinkler alarm). Addressable applicable. Function 1 input for potential-free contact. Status indication by LED. Technical data Communication protocol C-NET Operating voltage DC 12…33 V Operating current max. 0.3 mA Connection terminals 0.2…2.5 mm2 Operating temperature -25…+70 °C Storage temperature -30…+75 °C Humidity ≤95 % rel. Color housing / cover white, ~RAL 9010 / transparent mAtt Protection category EN 60529/IEC 60529 – with auxiliary housing FDCH221

IP30 IP65

System compatibility C-NET FS720 Standards EN 54-17, EN 54-18 Dimensions 95 x 71 x 23 mm Approvals VdS G209066, LPCB 531h/01

FDCI222 Input module Part no. A5Q00001984 Documents Product data sheet 007024 FDCI222

8 Resistors 4 x 3k01; 1 %; 0.25 W 4 x 1k15; 1 %; 0.25 W 2 Mounting feet

Technical description 007023

Application For the connection of 4 independent, potential-free mAke or break contacts for the acknowledgement of technical states (e.g. door or ventilation control) or for alarm actuation (e.g. sprinkler alarm). Addressable applicable. Function 4 inputs for potential-free contacts. Status indication by LED. Technical data Communication protocol C-NET Operating voltage DC 12…33 V Operating current 0.25…0.35 mA Connection terminals 0.2…1.5 mm2 (2.5 mm2) Operating temperature -25…+60 °C Storage temperature -30…+65 °C Humidity ≤95 % rel. Color housing / cover white, ~RAL 9010 / transparent mAtt Protection category EN 60529/IEC 60529 – with auxiliary housing FDCH221

IP30 IP65

System compatibility C-NET FS720 Standards CEA GEI I-084, EN 54-17, EN 54-18 Dimensions 130 x 90 x 20 mm Approvals VdS G204028, LPCB 531m/01

45

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 46: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Line separator, Input/output modules in C-NET

6.4 Input/output modules FDCIO22x

FDCIO221 Input/output module Part no. S54312-F2-A1 Documents Product data sheet A6V10202196 FDCIO221

3 Resistors 2 x 3k3; 1 %; 0.25 W 1 x 680 Ω; 1 %; 0.25 W 2 Mounting feet

Technical description A6V10211122

Application For the connection of 1 independent, potential-free mAke or break contact for the acknowledgement of technical states (e.g. door or ventilation control) or for alarm actuation (e.g. sprinkler alarm). For the decentralized control of fire doors, ventilation, air conditioning, etc. Addressable applicable. Function 1 input for potential-free contact. 1 output configurable via jumper – not monitored –> 1 potential-free relay contact (AC 30 V, DC 2 A / 30 V, 2 A) – monitored –> 1 relay contact (DC 30 V, 2 A) Status indication by LED. Technical data Communication protocol C-NET Operating voltage DC 12…33 V Operating current max. 0.4 mA Relay output (ohm) AC 30 V, 2 A, max. 60 VA

DC 30 V, 2 A, max. 60 W Anschlussklemmen 0.2…2.5 mm2 Operating temperature -25…+70 °C Storage temperature -30…+75 °C Humidity ≤95 % rel. Color Gehäuse / Deckel white, ~RAL 9010 / transparent mAtt Protection category EN 60529/IEC 60529 – with auxiliary housing FDCH221

IP30 IP65

System compatibility C-NET FS720 Standards EN 54-17, EN 54-18 Dimensions 95 x 71 x 23 mm Approvals VdS G209067, LPCB 531h/02

FDCIO222 Input/output module Part no. A5Q00002369 Documents Product data sheet 007024 FDCIO222

8 Resistors 4 x 3k01; 1 %; 0.25 W 4 x 1k15; 1 %; 0.25 W 2 Mounting feet

Technical description 007023

Application For the connection of 4 independent, potential-free mAke or break contacts for the acknowledgement of technical states (e.g. door or ventilation control) or for alarm actuation (e.g. sprinkler alarm). For the decentralized control of fire doors, ventilation, air conditioning, etc. Addressable applicable. Function 4 inputs for potential-free contacts. 4 outputs with 4 potential-free relay contacts for fire control installations. Status indication by LED. Technical data Communication protocol C-NET Operating voltage DC 12…33 V Operating current 0.6…0.75 mA Relay output (ohm) AC 250 V, 4 A, max. 1000 VA

DC 30 V, 4 A, max. 120 W Connection terminals 0.2…1.5 mm2 (2.5 mm2) Operating temperature -25…+60 °C Storage temperature -30…+65 °C Humidity ≤95 % rel. Color housing / cover white, ~RAL 9010 / transparent mAtt Protection category EN 60529/IEC 60529 – with auxiliary housing FDCH221

IP30 IP65

System compatibility C-NET FS720 Standards CEA GEI I-084, EN 54-17, EN 54-18 Dimensions 130 x 90 x 20 mm Approvals VdS G204029, LPCB 531m/02

46

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 47: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Line separator, Input/output modules in C-NET

FDCIO223 Transponder Part no. S24218-B102-A1 Documents Product data sheet 009168 FDCIO223

2 Transzorb diode 20 V 2 x 560 Ω 1 %; 0.25 W 2 x 680 Ω 5 %; 0.25 W 2 x 2,7 kΩ 1 %; 0.35 W 2 x 3,3 kΩ 5 %; 0.25 W 2 Mounting feet

Technical description 009122

Application For connection of collective fire detectors (GMT/conventional line, GMT/conventional line with shunt-Zener-diode barrier (SB3) for explosion-hazard areas). For monitored controls of e.g. smoke dampers, alarm devices, door mAgnets and extinguishing activa-tion devices (adhere to country-specific instructions). Monitored signal input for status and alarm messages or for acknowledging technical status. Addressable applicable. Function The 2 inputs/outputs can be parameterized autonomously in each case as detector line collective, con-tact input, control output, control output and input as acknowledgement with selectable monitoring time frame. Technical data Operating voltage C-NET DC 12…33 V External power supply: Input voltage DC 18…32 V In-/outputs as collective detector line GMT Siemens/Cerberus, Synova 300 or similar Collective line factor (KLK) / end of line 32 / 20 V Transzorb diode Control output DC 24 V ±5 % / 2 A (fuse on site) Contact input End of line combinations

3,3 kΩ/680 Ω, 2,7 kΩ/560 Ω, 3,3 kΩ

Operating temperature -25…+60 °C Storage temperature -30…+65 °C Humidity ≤95 % rel. Communication protocol C-NET Connection terminals 0.2…1.5 mm2 (Auxiliary terminal 2.5 mm2) Color housing / cover white, ~RAL 9010 / transparent mAtt Protection category EN 60529/IEC 60529 – with auxiliary housing FDCH221

IP30 IP65

System compatibility C-NET FS720 Standards CEA GEI I-084, EN 54-17, EN 54-18 Dimensions 132 x 90 x 24 mm Approvals VdS G206054, LPCB 531m/03

FDCIO224 Input/output module Part no. A5Q00018689 Documents Product data sheet 007024 FDCIO224

8 Resistors 4 x 2k7; 1 %; 0.35 W 4 x 560 Ω; 1 %; 0.25 W 2 Mounting feet

Technical description 007023

Application For the VdS interface for extinguishing activating devices. Addressable applicable. Function 4 inputs for potential-free contacts. 4 outputs with 4 potential-free relay contacts (AC 230 V / 4 A) for the VdS interface for extinguishing controls. Status indication by LED. Technical data Communication protocol C-NET Operating voltage DC 12…33 V Operating current 0,6…0,75 mA Relay output (ohm) AC 250 V, 4 A, max. 1000 VA

DC 30 V, 4 A, max. 120 W Connection terminals 0.2…1.5 mm2 (2.5 mm2) Operating temperature -25…+60 °C Storage temperature -30…+65 °C Humidity ≤95 % rel. Color housing / cover white, ~RAL 9010 / transparent mAtt Protection category EN 60529/IEC 60529 – with auxiliary housing FDCH221

IP30 IP65

System compatibility C-NET FS720 Standards CEA GEI I-084, EN 54-17, EN 54-18 Dimensions 130 x 90 x 20 mm Approvals VdS G207001

47

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 48: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Line separator, Input/output modules in C-NET

6.4.1 Accessories for FDCI22x, FDCIO22x

– U-rail TS35, L=122 mm Part no. BPZ:5644780001 – U-rail TS35, L=288 mm Part no. BPZ:5644230001 Details see chapter 6.2

FDCH221 Housing for input/output modules Part no. S54312-F3-A1

Application For the mounting of the input/output modules and transponder for humid, wet applications. Technical data Protection category EN 60529/IEC 60529 IP65 Color housing / cover white, ~RAL 9010 / transparent mAtt Dimensions 207 x 119 x 48 mm

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 – Back nut Part no. A5Q00004479 Details see chapter 4.1.1

6.4.2 Spare part for FDCI22x, FDCIO22x

FDCM291 Mounting feet for input/output modules Part no. A5Q00003855

25 pieces

Application Installation in range of the input/output modules with mounting feet onto top U-rail TS35. Use as spare part.

48

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 49: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Special detectors in C-NET

7 Special detectors in C-NET 7.1 SWING Radio gateway

FDCW241 SWING Radio gateway Part no. S54370-F11-A1 Document Product data sheet A6V10271323

Operating instructions A6V10227639 Application Wireless fire detection is used in situations where the user wants to avoid wires and their installation. In addition it means less interruption of operation and high flexibility for extensions and changes. Function High transmission reliability by radio transmission in SRD band (Short Range Device), a reserved fre-quency band with defined user rules. 43 channels are available. The radio gateway FDCW241 is connected to the detector bus FDnet/C-NET and communicates with up to 30 radio detectors. Each detector has its own location address. The 3.6 V battery pack (must be ordered separately S54370-Z11-A1) safeguards operation during commissioning or when the detector bus is without voltage and leads to a service life of well over 6 years. MCL USB Adapter for connection of the SWING-Tool. mAkes reading of information possible, for commissioning, mAintenance and for the troubleshooting. Technical data Supply voltage Via detector bus, additionally 1x 3.6 V lithium

battery, monitored Communication protocol FDnet/C-NET Transmitter/receiver antenna Dual band antenna Transmitting power ≤10 mW ERP Transmission distance max. 180 m in building

max. 1000 m in open air Channel width 50 kHz Radio frequency

- 23 channels - 20 channels

868…870 mHz (SRD band) 433…435 MHz

Operating temperature -10…+55 °C Dimensions (WxHxD) 89 x 167 x 28 mm Color white, ~RAL 9010 Protection category IP40

IP65 (with housing FDCH221) Humidity ≤95 % Standard EN 54-17, EN 54-18, EN 54-25, EN 300220-2 Approval VdS G212103

7.1.1 Accessory for SWING radio gateway

– Li-SOCI2 Batteriepack 3,6 V / 10 Ah Part no. S54370-Z11-A1

Application For the supply of the radio detector and radio gateway Technical data Dimensions 25 x 48 x 16 mm

49

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 50: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Special detectors in C-NET

7.2 SWING Radio smoke detector

FDOOT271/FDB271 Neural radio detector Part no. S54313-F1-A1 FDB271 Base Part no. S54319-F12-A1 Document Product data sheet A6V10271323 FDOOT271/FDB271

FDB271

Application The Swing radio smoke detector can be inserted and removed and actuated using the DZ1191, DZ1193 detector exchanger. The radio smoke detector consists of the radio smoke detector FDOOT271, the base FDB271 and a battery pack (S54312-F3-A1). Function Uniform response to various types of fires. Dynamic analysis of the sensor signal smoke in the detector itself. Built-in diagnostic algorithms with automatic self-test. High immunity to false alarms and ambient influences. High-quality optoelectronic sensor system. Automatic compensation of soiling. Each radio smoke detector has its own address and can transmit 4 danger levels. The radio detector is supplied by a 3.6 battery pack and can be mounted at any position within radio range. In normal operating condition they have a service life of more than 3 years. Technical data Supply voltage 3.6 V-10 Ah, battery pack, order separately Communication protocol FDnet/C-NET Transmitter/receiver antenna Dual band antenna Transmitting power ≤10 mW ERP Transmission distance max. 180 m in building,

max. 1000 m in open air Channel width 50 kHz Radio frequency

- 23 channels - 20 channels

868…870 mHz (SRD Band) 433…435 MHz

Operating temperature -10…+55 °C Dimension (ØxH) 117 x 64 mm Color white, ~RAL 9010 Protection category IP44 Humidity ≤95 % Standard EN 54-17, EN 54-18, EN 54-25, EN 300220-2 Approval

- VdS G212104

7.2.1 Accessories for SWING radio smoke detector

FDBZ291 Designation plate Bestell-Nr. A5Q00002621 See chapter 2.2.1 for details.

10 pieces

BAT3.6-10 Li-SOCI2 Batteriepack 3,6 V / 10 Ah Bestell-Nr. S54370-Z11-A1 See chapter 7.1.1 for details.

50

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 51: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Special detectors in C-NET

7.3 SWING Radio manual call point

FDMH273 Switching unit for FDM273 Part no. S54323-B108-A1 FDME273 Housing for FDM273 Part no. S54323-B109-A1 Document Product data sheet A6V10271323 FDMH273-R

FDME273

Application The SWING radio manual call point is used in situations where the user wants to avoid wires and their installation. In addition it means less interruption of operation and high flexibility for extensions and changes. Function The radio base consists of a housing part inclusive radio electronic and dual band antenna. The radio base is battery-operated and can be mounted at each place within a radio range. manual call point with indirect alarm actuation by breaking the glass and pressing the push button. The housing (FDMH273), the switching unit (FDME273) and the battery pack 3.6 V, 10 Ah need to be ordered separately. Technical data Supply voltage Via detector bus, additionally 3.6 V-10 Ah, battery

pack, monitored Communication protocol FDnet/C-NET Transmitter/receiver antenna Dual band antenna Transmitting power ≤10 mW ERP Transmission distance max. 180 m in building,

max. 1000 m in open air Channel width 50 kHz Radio frequency

- 23 channels - 20 channels

868…870 mHz (SRD Band) 433…435 MHz

Operating temperature -10…+55 °C Dimension (ØxH) 135 x 135 x 58 Color Red, ~RAL 3000 Protection category IP44 Humidity ≤95 % Standard EN 54-11 Typ B indoor, EN 54-25, EN 300220-2 Approval

- VdS G213092

51

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 52: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Special detectors in C-NET

7.3.1 Accessories for SWING radio manual call point

BAT3.6-10 Li-SOCI2 Battey pack 3,6 V / 10 Ah Part no. S54370-Z11-A1 See chapter 7.1.1 for details.

DMZ1197-AC Protective cover Part no. BPZ:5223550001

5 pieces

Application Protects the manual call point from unintentional glass break. Technical data Color transparent

DMZ1196-AC Glass Part no. BPZ:4942050001

10 pieces

Application Use as spare part.

DMZ1195 Key Part no. BPZ:4851910001

10 pieces

Application Only for housing FDMH293-x or FDMH273 Use as spare part.

52

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 53: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Special detectors in C-NET

7.4 Aspirating smoke detectors

FDA221 Aspirating smoke detector (5S) Part no. S54333-F15-A1 FDA241 Aspirating smoke detector (8H) Part no. S54333-F17-A1 Document Product data sheet A6V10331032 FDA221

FDA241

Application FDA221 The FDA221 series of detectors are a very early warning dual wavelength (blue & infra-red) smoke detectors designed to protect small business-critical environments up to 500 m². FDA241 The FDA221 series of detectors are a very early warning dual wavelength (blue & infra-red) smoke detectors designed to protect small business-critical environments up to 800 m². Function The detector works by continually drawing air into sampling holes in a pipe net-work. The air is passed into a uniquely designed detection chamber where light scattering technology detects the presence of very small amounts of smoke. The FDA221and FDA241 detectors can communicate directly on the FDnet/C-NET loops (with an optional FDCC221S PCB), so there is no need for separate relay or net-work connections. Technical data Operating voltage DC 19…30 V Quiescent current 150 mA Alarm current 250 mA Display 4 Alarm state indicators(FDA241)

Purge, Dust (FDA241) 3 Alarm state indicators FDA221), Fault and disabled indicators, Smoke and airflow level bargraphs indicator

Area coverage – FDA221 – FDA241

up to 500 m2

up to 800 m2

Alarm threshold – FDA221

– FDA241

0.03 - 2.0 % obs/m / Info alarm, Pre-alarm, Fire 1 (5 sets) 2.0 - 20 % obs/m / Fire 2 (5 sets) 0.03 - 2.0 % obs/m / Info alarm, Pre-alarm, Fire 1 (10 sets) 2.0 - 20 % obs/m / Fire 2 (10 sets)

Air inlet pipe Accepts both metric and American standard pipe sizes, External diameter 25 mm, Internal diameter 21 mm

Pipe length – FDA221

– FDA241

Single pipe length: 30m Branched pipe length: 2 x 25m Single pipe length: 60m Branched pipe length: 2 x 60m

Relay output 3x 2 A / 30 V Terminals 0.2…2.5 mm2 (30…12 AWG) Dimensions (WxHxD) 155 x 280 x 114 mm Operating temperature -20…+40 °C Humidity ≤95 % rel. (no condensation) Protection category IP30 Approval VdS, LPCB

7.4.1 Accessory

FDCC221S Communication interface Part no. S24218-A201-A2

Application For connecting the aspirating smoke detector FDA221 / FDA241 to FDnet/C-NET. The installation is not permitted in the case of standalone operation. FDCC221S has its own ID. This ID is mAde visible to the detector line and it replaces the ID of the aspirating smoke detector.

53

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 54: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Special detectors in C-NET

7.5 Aspirating smoke detectors

LaserFOCUS VLF-250 Aspirating smoke detector with display Part no. VLF-250-SIE

see footnote 1) LaserFOCUS VLF-500 Aspirating smoke detector with display Part no. VLF-500-SIE

see footnote 1) Document Product data sheet A6V10221433

Application VLF-250 The LaserFOCUS detector is a very early warning smoke detector (Aspirating Smoke Detector ASD) designed to protect small, business-critical environments of less than 250 sqm. VLF-500 The LaserFOCUS detector is a very early warning smoke detector (Aspirating Smoke Detector ASD) designed to protect small, business-critical environments of less than 500 sqm. Function The detector works by continually drawing air into sample holes in a pipe network. The air is filtered and passed into a detection chamber where light scattering technology detects the presence of very small amounts of smoke. Detector status information is communicated on the detector display. The C-NET interface card is integrated. Technical data Communication protocol C-NET Operating voltage DC 18…30 V Quiescent current 220 mA Alarm current 295 mA Display 4 Alarm state indicators, Fault and disabled indi-

cators, Smoke level indicator Area coverage – VLF-250 – VLF-500

up to 250 m2

up to 500 m2

Alarm threshold 0.025 - 2.00 %/m / Info alarm, Pre-alarm 0.025 - 20.00 %/m / Fire 1, Fire 2

Air inlet pipe Accepts both metric and American standard pipe sizes, External diameter 25 mm, Internal diameter 21 mm

Pipe length – VLF-250 – – VLF-500

max. 1 x 25 m (max. 12 holes), max. 2 x 15 m per branch (max. 6 holes per branch) max. 1 x 50 m (max. 24 holes), max. 2 x 30 m per branch (max. 12 holes per branch)

Relay output 3x 2 A / 30 V (Pre-alarm, Alarm, Fault) Terminals 0.2…2.5 mm2 (30…12 AWG) Dimensions (WxHxD) 255 x 185 x 90 mm Operating temperature 0…+40 °C Humidity ≤95 % rel. (no condensation) Protection category IP30 Approval VdS G207155, LPCB

1) Delivery time and ordering approximately 14 working days from date of order from:

EMEA Xtralis (UK) Ltd. Focus 31, mArk Road Hemel Hempstead, Hertfordshire HP2 7BW United Kingdom Tel: + 44 1442 242330 Fax: +44 1442 249327

APAC Xtralis Pty Ltd. 4 North Drive, Virginia Park 236-262 East Boundery Road (PO Box 102) Bentleigh East, Victoria, Australia, 3165 Tel: +61 3 9936 7200 Fax: +61 3 9936 7201

Warranty for all Xtralis products is 24 months. Contact Xtralis (UK) for information about warranty, replacement parts, repair and return items.

54

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 55: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

8 Conventional and collective devices 8.1 Conventional/Collective Line SynoLINE300/600

OOH740 Multi sensor smoke detector, ASA Part no. S54320-F7-A3 Documents Product data sheet A6V10284161

Techn. description A6V10305793 Scope of delivery Detector and dust cap

Application For the detection of flaming fires caused by the combustion of liquid and solid mAtters, as well as smol-dering fires. For reliable fire detection in environments with deceptive phenomena. Function Works according to the scattered-light principle with two sensors, optical forward and backward scatter-ing. Opto-electronic sampling chamber blocks disturbing extraneous light but optimally detects both dark and light smoke particles. Two additional heat sensors increase the fire detector’s immunity to deceptive phenomena. The base must be ordered separately. Technical data Communication protocol C-NET or collectiv Operating voltage (modulated) DC 12…33 V Operating current (quiescent) ~170…250 μA Ext. alarm indicator 2 Operating temperature -25…+50 °C Storage temperature -30…+70 °C Humidity ≤95 % rel. Color white, ~RAL 9010 Protection category EN 60529/IEC 60529 – with detector base seal RS720

IP40 IP44 with detector base seal RS720

System compatibility C-NET FS720 Standards CEA4021, EN 54-5, EN 54-7, EN 54-17 Dimensions (detector with base) Ø117 x 49 mm (incl. base) Approvals VdS G211070, LPCB 126bh/05

DB110 Detector base DB110 (Parameter set 1) Part no. S54372-F5-A1

Application For all point detectors of the series Cerberus PRO FD720. Technical data Color white, ~RAL 9010 Dimensions Ø117 x 23 mm

DB721D Detector base Part no. S54319-F15-A1

Application Universal base for the OOH740 point detector of the series Cerberus PRO FD720 in collective mode. Diode removable Technical data Color white, ~RAL 9010 Dimensions Ø117 x 23 mm

55

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 56: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

PSR720-1 Parameter set resistor 33k Part no. S54319-F16-A1

Function Preassembled resistors complete with spade terminals suitable for easy installation into DB110 and DB721D detector bases to set the OOH740 detector into parameter set 1. Technical data Delivery unit 25 pieces

PSR720-2 Parameter set resistor 33k Part no. S54319-F17-A1

Application Preassembled resistors complete with spade terminals suitable for easy installation into DB110 and DB721D detector bases to set the OOH740 detector into parameter set 2. Technical data Delivery unit 25 pieces

BA720 Base attachment Part no. S54319-F20-A1

Application For the supply of surface-mounted tubes (max. 20 mm) and trunking (max. 25 mm x 15 mm). The detec-tor is fixed with a spring-loaded catch. Note: mounting slots 46...90 mm. Technical data Color white, ~RAL 9010 Dimensions Ø120 x 25 mm

FDBZ291 Designation plate Part no. A5Q00002621 Details see chapter 2.2.1

RS720 Detector base seal Part no. S54319-F8-A1 Details see chapter 2.2.1

DBZ1190-AA Micro terminal Part no. BPZ:4677080001 DBZ1190-AB Auxiliary terminal Part no. BPZ:4942340001 Details see chapter 2.2.1

56

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 57: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

8.2 Alarm indicators for SynoLINE300/600 devices

FDAI91 Alarm indicator Part no. S54370-F9-A1 Document Product data sheet A6V10276520

Application The FDAI91 alarm indicator is the visual parallel indication for fire detectors used on the SynoLINE600 detector line. The alarm indicators are an ideal supplement to fire detectors, where the detectors are mounted in positions which are difficult to reach (e.g. in switching cabinets) or difficult to see (e.g. in hotel rooms) and enable the triggered detector to be quickly located. The FDAI91 is suitable for door frames. For recess supply line. Function The LEDs in the alarm indicator are on, as soon as the appropriate detector is in alarm. Technical data Operating voltage DC 5…8 V Operating current max. 35 mA Screwless connection terminals Wire cross-sectional area max. 1.5 mm2 Environmental temperature -25…+80 °C Humidity ≤95 % rel. Protection category EN 60529/IEC 60529 IP40 Color white, ~RAL 9010 Dimensions 62 x 37 x 24 mm

FDAI92 Alarm indicator Part no. S54370-F3-A1 Document Product data sheet A6V10276520

Application The FDAI92 alarm indicator is the visual parallel indication for fire detectors used on the SynoLINE600 detector line. The alarm indicators are an ideal supplement to fire detectors, where the detectors are mounted in positions which are difficult to reach (e.g. in switching cabinets) or difficult to see (e.g. in hotel rooms) and enable the triggered detector to be quickly located. The FDAI92 is suitable for surface wall mounting. For recess supply line. Function The LEDs in the alarm indicator are on, as soon as the appropriate detector is in alarm. Technical data Operating voltage DC 5…8 V Operating current, dauernd max. 35 mA Screwless connection terminals Wire cross-sectional area max. 1.5 mm2 Environmental temperature -25…+80 °C Humidity ≤95 % rel. Protection category EN 60529/IEC 60529 IP40 Color white, ~RAL 9010 Dimensions 85 x 85 x 28 mm

8.2.1 Accessory FDAI92

AI330 Adapter frame Part no. BPZ:3169430001

Application For surface laid conduit or ducts, to increase the loop space or as an adapter for different mAkes of box. Technical data Color white, ~RAL 9010 Dimensions 85 x 85 x 16 mm

57

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 58: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

FDAI93 Alarm indicator incl. insulating cap Part no. S54370-F5-A1 Document Product data sheet A6V10276520

Application Made of transparent plastic, the alarm indicator is suitable for installation in door frames, switching panels, ceiling voids or special housings. The 22.5 mm Ø mounting hole is drilled by the system owner. The holder must be fitted with an insulating cap for safety. Function Indicator lamp to connect in parallel to automatic fire detectors. Technical data Operating voltage DC 6…8 V Operating current max. 35 mA Humidity ≤95 % rel. Color transparent Protection category EN 60529/IEC 60529 – with DCA1191 – with DJZ1193

IP56 IP65

Dimensions Ø22 x 51 mm

– Insulating cap Part no. BPZ:3048160001

Application Use as spare part.

8.2.2 Accessories for FDAI93

DCA1191 Housing with cover Part no. BPZ:4588560001 – Washer Part no. BPZ:2473130001 DCA1191

Washer

Application For surface mounting in humid, wet areas. Up to 4 alarm indicators FDAI93 can be built into the housing. Technical data Housing with cover Protection category EN 60529/IEC 60529 IP56 Dimensions 135 x 135 x 65 mm Color white, ~RAL 9010 Washer Dimensions Ø23 x 1 mm

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 Details see chapter 2.3.1

58

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 59: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

DJZ1193 Alarm indicator housing incl. washer Part no. BPZ:5302950001

Application For surface mounting in dry areas. 1 alarm indicator FDAI93 in can be built into the housing. Technical data Protection category EN 60529/IEC 60529 IP65 Color white, ~RAL 9010 Dimensions 87 x 87 x 64 mm

MVH1 Mounting arm Part no. BPZ:3496190001

Application For mounting of the alarm indicator housing DJZ1193 and detectors in hollow floors. Technical data Pipe clamp ½" Dimensions 20 x 20 x 290…420 mm

59

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 60: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

8.3 Conventional / Collective 110-series detectors

OH110 Multi sensor fire detector (collective) Part no. S54372-F11-A1 Documents Product data sheet A6V10301051

Technical description A6V10316298 Scope of delivery Detector and dust cap

Application For the detection of flaming fires caused by the combustion of liquid and solid mAtters, as well as smol-dering fires and for reliable fire detection in environments with deceptive phenomena. Function Works according to the scattered light principle with one sensor, optical forward scattering. Opto-electronic sampling chamber holds off disturbing extraneous light but optimally detects smoke particles. An additional heat sensor increases the fire detector’s immunity to deceptive phenomena. Selectable detection behavior by two parameter sets: Parameter set 1 (Sensitive); Parameter set 2 (Robust) Immunity against transient false alarm causes Technical data Communication protocol Collective / Conventional Operating voltage DC 16…28 V Operating current (quiescent) Max. ~100 μA Ext. alarm indicator 2 Operating temperature -10…+50 °C Storage temperature -30…+70 °C Humidity ≤96 % rel. Color white, ~RAL 9010 Protection category EN 60529/IEC 60529 – with detector base seal RS720

IP40 IP42

System compatibility C-NET FS720 Standards CEA4021 / EN 54-7 Dimensions (detector with base) Ø117 x 62 mm (incl. base) Approvals VdS 212059, LPCB request

OP110 Smoke detector (collective) Part no. S54372-F4-A1 Documents Product data sheet A6V10301051

Techn. description A6V10316298 Scope of delivery Detector and dust cap

Application For the detection of smoke-generating flaming and smoldering fires. Function Works according to the scattered light principle with one sensor, optical forward scattering. Opto-electronic sampling chamber holds off disturbing extraneous light but optimally detects smoke particles. Selectable detection behavior by 2 parameter sets: Parameter set 1 (Standard); Parameter set 2 (Sensi-tive) Technical data Communication protocol Collective / Conventional Operating voltage DC 16…28 V Operating current (quiescent) Max. ~100 μA Ext. alarm indicator 2 Operating temperature -10…+55 °C Storage temperature -30…+70 °C Humidity ≤96 % rel. Color white, ~RAL 9010 Protection category EN 60529/IEC 60529 – with detector base seal RS720

IP40 IP42

System compatibility C-Net FS720 Standards EN 54-7 Dimensions (detector with base) Ø117 x 56 mm (incl.base) Approvals VdS G212033, LPCB request

60

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 61: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

HI110 Heat detector (collective, differential) Part no. S54372-F9-A1 Documents Product data sheet A6V10301051

Techn. description A6V10316298 Scope of delivery Detector

Application For areas having high level of dust, dirt or moisture that mAy lead to false activating with smoke detec-tors Function Equipped with one heat sensor. For high requirements. Certain response behavior with slow and fast temperature increases, also by depth temperature. Parameter set: A1R. Technical data Communication protocol Collective / Conventional Operating voltage DC 16…28 V Operating current (quiescent) Max. ~100 μA Ext. alarm indicator 2 Operating temperature -10…+50 °C Storage temperature -30…+70 °C Humidity ≤96 % rel. Color white, ~RAL 9010 Protection category EN 60529/IEC 60529 – with detector base seal RS720

IP40 IP42

System compatibility C-NET FS720 Standards EN 54-5 / EN 54-17 Dimensions (detector with base) Ø117 x 62 mm (incl. base) Approvals VdS G212004, LPCB request

HI112 Heat detector (static) Part no. S54372-F10-A1 Documents Product data sheet A6V10301051

Techn. description A6V10316298 Scope of delivery Detector

Application For areas having high levels of dirt or temperature fluctuation that mAy lead to false activating with smoke detectors Function Equipped with one heat sensor. Measures permanent the ambient temperature, with exceeding of the mAximum temperature, the detec-tor sends a danger signal to the fire control panel. Selectable detection behavior by 2 parameter sets: Parameter set 1: A2S; Parameter set 2: B Technical data Communication protocol Collective / Conventional Operating voltage (modulated) DC 16…28 V Operating current (quiescent) Max. ~100 μA Ext. alarm indicator 2 Operating temperature -10…+50 °C (HI112, A2S) -10…+65 °C (HI112, B) Storage temperature -30…+70 °C Humidity ≤96 % rel. Color white, ~RAL 9010 Protection category EN 60529/IEC 60529 – with detector base seal RS720

IP40 IP42

System compatibility C-NET FS720 Standards EN 54-5 Dimensions (detector with base) Ø117 x 62 mm (incl. base) Approvals VdS G212015, LPCB request

61

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 62: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

8.3.1 Accessories for point detectors

LP720 Detector locking device Part no. S54319-F9-A1

Application Threaded pin M3 x 12 to protect detector against theft. Scope of delivery 2 hexagonal wrenches, 100 threaded pins Technical data Threaded pin M3 x 12 Hexagonal wrench 1.5 mm

8.4 Detector bases

DB110 Detector base Part no. S54372-F5-A1

Application Standard conventional detector base for all series 110 point detectors. Selects parameter set 1 within detectors Technical data Color white, ~RAL 9010 Dimensions Ø117 x 23 mm

DB110D Detector base Part no. S54372-F6-A1

Application Conventional detector base complete with a continuity diode for all series 110 point detectors selects parameter 1 within detectors Technical data Color white, ~RAL 9010 Dimensions Ø117 x 23 mm

DB110R Detector base Part no. S54372-F7-A1

Application Conventional detector base complete with a resistor for parameter setting for all series 110 point detec-tors. Selects parameter set 2 within detectors Technical data Color white, ~RAL 9010 Dimensions Ø117 x 23 mm

DB110RD Detector base Part no. S54372-F8-A1

Application Conventional detector base complete with a resistor for parameter setting and continuity diode for all series 110 point detectors. Selects parameter set 2 within detectors Technical data Color white, ~RAL 9010 Dimensions Ø117 x 23 mm

62

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 63: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

8.4.1 Accessories for detector bases

BA720 Base attachment Part no. S54319-F20-A1

Application For the supply of surface-mounted tubes (max. 20 mm) and trunking (max. 25 mm x 15 mm). The detec-tor is fixed with a spring-loaded catch. Note: mounting slots 46…90 mm. Technical data Color white, ~RAL 9010 Dimensions Ø120 x 25 mm

FDBZ291 Designation plate Part no. A5Q00002621 Details see chapter 2.2.1

RS720 Detector base seal Part no. S54319-F8-A1 Details see chapter 2.2.1

DBZ1190-AA Micro terminal Part no. BPZ:4677080001 DBZ1190-AB Auxiliary terminal Part no. BPZ:4942340001 Details see chapter 2.2.1

63

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 64: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

8.5 Manual call point collective

FDM1101-RG Manual call point with glass plate Part no. S54371-F6-A1 FDM1101-RP Manual call point with resettable plastic element Part no. S54371-F6-A2 Documents Product data sheet A6V10206486

Technical description A6V10201150 Application For immediate manual actuation of a fire alarm. For indoor and outdoor application. For surface- and recess-mounted feed lines in easily accessible places. For surface mounting the housing base FDMH295-x must be ordered separately. Function FDM1101-RG Direct alarm actuation by pushing in the glass plate. By replacing the glass plate the push button is reset and the device is ready for operation again. FDM1101-RP Direct alarm actuation by pushing on the plastic element. The switch is reset with the key and the device is ready for operation again. Technical data Communication protocol collective Operating voltage DC 16…28 V Operating current 60…100 mA Terminal block 0.28…1.5 mm² Operating temperature -25…+70 °C Storage temperature -30…+75 °C Humidity ≤95 % rel. (no condensation) Protection category EN 60529/IEC 60529 IP44 Standard EN 54-11 Color red, ~RAL 3000 Dimensions 87 x 87 x 20 mm Approvals – FDM1101-RG – FDM1101-RP

VdS 209148, LPCB 126as/01 VdS 209148, LPCB 126as/02

FDMH295-R Back box Part no. A5Q00013437 FDMH295-S Back box with holes and socket Part no. A5Q00013438 Details see chapter 4.2 FDMH295-R

FDMH295-S

64

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 65: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

8.5.1 Accessories for FDM1101

FDMC295 Protective cover Part no. A5Q00013440 Details see chapter 4.2.1

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 – Back nut Part no. A5Q00004479 Details see chapter 4.2.1

DBZ1190-AB Auxiliary terminal Part no. BPZ:4942340001 Details see chapter 2.2.1

8.5.2 Spare parts for FDM1101

FDMG295 Glass palte 'neutral' Part no. A5Q00013442 FDMP295 Plastic element 'neutral' Part no. A5Q00013445 Details see chapter 4.2.2

FDMK295 Key Part no. A5Q00013448 Details see chapter 4.2.2

65

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 66: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

FDMH291-R Housing red with key Part no. A5Q00002217 FDMH291-Y Housing yellow with key Part no. A5Q00004979 FDMH291-G Housing blue with key Part no. A5Q00004981 FDMH291-B Housing green with key Part no. A5Q00004980 DMA1101 Switching unit collective Part no. A5Q00005578 Document Product data sheet 007980

Application Collective manual call point for the immediate manual actuation of a fire alarm. For the connection on the collective/SynoLINE600 detector line. An integral LED provides visual indication of alarm. The housing FDMH291-x and the electronic unit DMA1101 must be ordered separately. Function Direct alarm actuation by pushing in the glass plate. By replacing the glass plate the push button is set back and the device is ready for operation again. Technical data Communication protocol collective/SynoLINE600 Operating voltage DC 16…26 V Operating current 60…100 mA Anschlussklemmen 0.28…1.5 mm2 Operating temperature -25…+70 °C Storage temperature -30…+75 °C Humidity ≤95 % rel. Color red, ~RAL 3000, blue, ~RAL 5005,

yellow, ~RAL 1023, green, ~RAL 6024 Protection category EN 60529/IEC 60529 IP44 Standard EN 54-11 Dimensions 87 x 87 x 46.6 mm Approvals LPCB 531j/02

66

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 67: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

8.5.3 Accessories for DM1101

FDMC291 Protective cover Part no. A5Q00001644

5 pieces

Application Protects the manual call point from unintentional glass break. Technical data Color transparent

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 – Back nut Part no. A5Q00004479 Details see chapter 4.1.1

8.5.4 Spare parts for DM1101

FDMG291 Replacement glass Part no. A5Q00002122

10 pieces

Replacement glass for manual call point housings FDMH291-x.

FDMK291 Cover with key Part no. A5Q00001643

Spare key with call point front for manual call point housings FDMH291-x.

67

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 68: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

DMA1192-AA Housing red with glass and key Part no. BPZ:5222870001 DMA1192-AB Housing yellow with glass and key Part no. BPZ:5464250001 DMA1192-AC Housing blue with glass and key Part no. BPZ:5464120001 DMA1192-AD Housing green with glass and key Part no. BPZ:5090190001 DMA1103D Switching unit collective Part no. A5Q00004470 DMA1104D Switching unit collective Part no. A5Q00005925 Document Product data sheet 007980

DMA1103D

DMA1104D

Application Collective manual call point for the immediate manual actuation of a fire alarm. For indoor and outdoor application, equally suited for wet, humid and dusty areas. For surface- and recess-mounted feed lines in easily accessible places. For the connection on the collective/SynoLINE600 detector line. An LED always indicates the status of the manual call point. The housing DMA1192-xx and the electronic unit DMA1103D must be ordered separately. Function DM1103 Indirect alarm actuation by smashing in the glass plate and pressing the push button. To replace the glass plate, open the housing door with the key. The push button must be set back before closing the door again. DM1104 Direct alarm actuation by smashing in the glass plate. To replace the glass plate, open the housing door with the key, upon closing the door the button is reset. Technical data Communication protocol collective/SynoLINE600 Operating voltage DC 16…26 V Operating current 60…100 mA Anschlussklemmen 0,28…1,5 mm2 Einsatztemperatur -25…+70 °C Storage temperature -30…+75 °C Humidity ≤95 % rel. Color red, ~RAL 3000, blue, ~RAL 5005,

yellow, ~RAL 1023, green, ~RAL 6024 Protection category EN 60529/IEC 60529 – mit Dichtung DMZ1197-AD

IP54 IP65

Standard EN 54-11 Dimensions 134 x 134 x 43 mm Approvals – DM1103 – DM1104

VdS G295036 VdS G299068, LPCB 531j/02

68

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 69: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

DM1103-L Manual release button complete Part no. A5Q00017630 Document Product data sheet 007980

Application Manual release button DM1103-L for the immediate manual actuation of a gas extinguishing system. For indoor and outdoor application, equally suited for wet, humid and dusty areas. For surface-mounted feed lines to the DM1103-L the housing is equipped with opening at the top and bottom, with sealing studs for M20 cable glands or locking plug (2 locking plugs, 2 holes enclosed). Function For indirect extinguishing release by smashing in the glass plate and pressing the push button. To re-place the glass plate, open the housing door with the key. The push button must be set back before closing the door again. Technical data Communication protocol collective/SynoLINE600 Connection terminals 0.28…1.5 mm2 Operating temperature -25…+70 °C Storage temperature -30…+75 °C Humidity ≤95 % rel. Color yellow, ~RAL 1023 Protection category EN 60529/IEC 60529 – with seal DMZ1197-AD

IP54 IP65

Standard EN12094-3 Dimensions 134 x 134 x 43 mm Approvals VdS G206029

DM1103-S Emergency stop button complete Part no. A5Q00014486 Document Product data sheet 007980

Application Emergency stop button DM1103-S for the stop function of a gas extinguishing system. For indoor and outdoor application, equally suited for wet, humid and dusty areas. For surface-mounted feed lines to the DM1103-S, the housing is equipped with openings at the top and bottom, with sealing studs for M20 cable glands or locking plug (2 locking plugs, 2 holes enclosed). Function Indirect stop function by smashing in the glass plate and pressing the push button. As soon as the but-ton is not pressed any longer (self reset), the stopped extinguishing release will continue. To replace the glass plate, open the housing door with the key. Technical data Communication protocol collective/SynoLINE600 Anschlussklemmen 0.28…1.5 mm2 Operating temperature -25…+70 °C Storage temperature -30…+75 °C Humidity ≤95 % rel. Color blue, ~RAL 5005 Protection category EN 60529/IEC 60529 – with seal DMZ1197-AD

IP54 IP65

Standard EN12094-3 Dimensions 134 x 134 x 43 mm Approvals VdS G206030

8.5.5 Accessories for DM1103/04

DMZ1197-AC Protective cover Part no. BPZ:5223550001

5 pieces

Application Protects the manual call point from unintentional glass break. Technical data Color transparent

69

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 70: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

DMZ1197-AD Protection seal Part no. BPZ:5470680001

5 pieces

Application Protects the manual call point in wet applications. Technical data Color transparent

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 Details see chapter 4.2.1

– Locking plug red, M20 x 1.5 (1 hole) Part no. A5Q00006735 – Locking plug red, M20 x 1.5 (2 holes) Part no. A5Q00010055 Locking plug 1 hole (10 pcs.)

Locking plug 2 holes (10 pcs.)

Application Für die Aufputz-Kabeleinführung. Für die Anwendung in trockenen Räumen. Technical data Color red Dimensions M20 x 1.5

8.5.6 Spare parts for DM1103/04

DMZ1196-AC Spare glass Part no. BPZ:4942050001

10 pieces

Application Use as spare part.

DMZ1195 Key Part no. BPZ:4851910001

10 pieces

Application For housings DMA1192-xx. Use as spare part.

70

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 71: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

8.6 Conventional FDM1101A manual call points

FDM1101A-RG Manual call point with glass plate Part no. S54371-F6-A3 FDM1101A-RP Manual call point with resettable plastic element Part no. S54371-F6-A4 Documents Product data sheet A6V10206486

Technical description A6V10201152 Application For immediate manual actuation of a fire alarm. For indoor and outdoor application. For surface- and recess-mounted feed lines in easily accessible places. For surface mounting the housing base FDMH295-x must be ordered separately. Function FDM1101A-RG Direct alarm actuation by pushing in the glass plate. By replacing the glass plate the push button is reset and the device is ready for operation again. FDM1101A-RP Direct alarm actuation by pushing on the plastic element. The switch is reset with the key and the device is ready for operation again. Technical data Communication protocol conventional Operating voltage max. AC 28 V or DC 28 V Operating current 100 mA…max. 1 A Terminal block 0.28…1.5 mm² Operating temperature -25…+70 °C Storage temperature -30…+75 °C Humidity ≤95 % rel. (no condensation) Protection category EN 60529/IEC 60529 IP44 Standard EN 54-11 Color red, ~RAL 3000 Dimensions 87 x 87 x 20 mm Approvals – FDM1101A-RG – FDM1101A-RP

VdS 209149, LPCB 126as/03 VdS 209149, LPCB 126as/04

FDMH295-R Back box Part no. A5Q00013437 FDMH295-S Back box with holes and socket Part no. A5Q00013438 Details see chapter 4.2 FDMH295-R

FDMH295-S

71

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 72: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

8.6.1 Accessories for FDM1101A

FDMC295 Protective cover Part no. A5Q00013440 Details see chapter 4.2.1

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 – Back nut Part no. A5Q00004479 Details see chapter 4.2.1

DBZ1190-AB Auxiliary terminal Part no. BPZ:4942340001 Details see chapter 2.2.1

8.6.2 Spare parts for FDM1101A

FDMG295 Glass palte 'neutral' Part no. A5Q00013442 FDMP295 Plastic element 'neutral' Part no. A5Q00013445 Details see chapter 4.2.2

FDMK295 Key Part no. A5Q00013448 Details see chapter 4.2.2

72

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 73: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

8.7 Alarm indicators collective devices

AI91C Alarm indicator Part no. S54370-F7-A1 Document Product data sheet A6V10276522

Application The AI91C alarm indicator is the visual parallel indication for fire detectors used on the SynoLINE300 detector line. The alarm indicators are an ideal supplement to fire detectors, where the detectors are mounted in positions which are difficult to reach (e.g. in switching cabinets) or difficult to see (e.g. in hotel rooms) and enable the triggered detector to be quickly located. The AI91C is suitable for door frames. For recess supply line. Function The LEDs in the alarm indicator are on, as soon as the appropriate detector is in alarm. Technical data Operating voltage DC 6…28 V Operating current max. 35 mA Screwless connection terminals Wire cross-sectional area max. 1.5 mm2 Environmental temperature -25…+80 °C Humidity ≤95 % rel. Protection category EN 60529/IEC 60529 IP40 Color white, ~RAL 9010 Dimensions 62 x 37 x 24 mm

AI92C Alarm indicator Part no. S54370-F8-A1 Document Product data sheet A6V10276522

Application The AI92C alarm indicator is the visual parallel indication for fire detectors used on the SynoLINE300 detector line. The alarm indicators are an ideal supplement to fire detectors, where the detectors are mounted in positions which are difficult to reach (e.g. in switching cabinets) or difficult to see (e.g. in hotel rooms) and enable the triggered detector to be quickly located. The AI92C is suitable for surface wall mounting. For recess supply line. For surface supply line use adapter frame AI330. Function The LEDs in the alarm indicator are on, as soon as the appropriate detector is in alarm. Technical data Operating voltage DC 6…28 V Operating current, dauernd max. 35 mA Screwless connection terminals Wire cross-sectional area max. 1.5 mm2 Environmental temperature -25…+80 °C Humidity ≤95 % rel. Protection category EN 60529/IEC 60529 IP40 Color white, ~RAL 9010 Dimensions 85 x 85 x 28 mm

8.7.1 Accessory for AI92C

AI330 Adapter frame Part no. BPZ:3169430001

Application For surface laid conduit or ducts, to increase the loop space or as an adapter for different mAkes of box. Technical data Color white, ~RAL 9010 Dimensions 85 x 85 x 16 mm

73

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 74: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

8.8 Air sampling smoke detection kit FDBZ292

FDBZ292 Air sampling smoke detection kit Part no. A5Q00021362 Documents Product data sheet 009728

Installation 009726 Application Reliable monitoring of fresh air, used air and air re-circulation ducts for smoke in air conditioning and ventilation systems. The smoke detector DO1104A and the base DB1101A must be ordered separately. Function The air sampling smoke detection kit is mounted in the ventilation system where air flow measuring devices are usually installed, i.e. where there is no air vortex, change of direction, duct branching, duct narrowing or duct extensions. The distance to the branching, bracket or bend must have 5 x the duct diameter. In order to guarantee smoke detection, mount on the outside of the air duct sampling, after the last air inlet. Accessories for all shapes of duct. Technical data Smoke detector DO1104A Detector base DB1101A System compatibility collective/SynoLINE600, in C-NET via Transpon-

der FDCIO223 Min. duct diameter 100 mm Permissible air speed 1…20 m/s Air flow indicator ≥1 m/s Ambient temperature -20…+50 °C Dimensions (WxHxD) 146 x 235 x 183 mm Color grey, ~RAL 7001 Protection category IP54 Humidity ≤95 % rel.

8.8.1 Accessories FDBZ292

DO1104A Smoke detector, collective wide spectrum Part no. BPZ:5090640001 Documents Product data sheet 001578

Technical description 1001 Application Automatic fire detector with higher response sensitivity for the early warning of smoke-forming, flaming fires and smoldering fires. The base DB1101A must be ordered separately. Technical data Communication protocol collective/SynoLINE600 Operating voltage DC 16…24 V Quiescent current max. 100 μA Operating temperature -25…+60 °C Sensitivity typ. 1.8 %/m Protection category IP44 Color white, ~RAL 9010 Dimensions (ØxH) 115 x 51 mm (incl. base) Standard EN 54-7 Approval VdS G297038

74

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 75: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

DB1101A Base for collective detector series Part no. BPZ:4863650001 Document Product data sheet 001035

Application Base mAde of impact and scratch-proof plastic and environmentally safe mAterials. Integral rubber gasket to protect against draught, dirt and dripping water from above. Screwless terminals for easy installation. Space for auxiliary terminals as micro terminals (0.5 mm²) and connection terminals (2.5 mm²). Fits all standard flush-mounted boxes from 55 to 80 mm. Technical data Cable capacity 0.2…2.5 mm² Dimensions (ØxH) 115 x 21 mm Color white, ~RAL 9010

FDBZ292-AA Air flow tube 0.6 m Part no. A5Q00021363 FDBZ292-AB Air flow tube 1.5 m Part no. A5Q00021364 FDBZ292-AC Air flow tube 2.8 m Part no. A5Q00021366

Application The air flow tube is introduced through a hole drilled into the duct and shortened according to the diame-ter of the duct.

FDBZ292-AD Sealing kit for air flow tubes Part no. A5Q00021367

Application One sealing kit is necessary for – applications using the mounting bracket – applications using air flow tubes longer than 1 m Two sealing kits are necessary for – applications using the mounting bracket and air flow tubes longer than 1 m

FDBZ292-AF Mounting bracket Part no. A5Q00021369

Application The mounting bracket is used for uneven, round and insulated ducts.

75

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 76: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

8.9 Conventional alarm devices 8.9.1 Alarm devices AGT24.1, RoLP/R/S, ROLP/W/S

RoLP/R/S RoLP/W/S

Alarm device Part no. GBI:1082507 GBI:1082508

Document Product data sheet A6V10423405

Application For inside and outdoor applications. For general signaling in fire use. Removable base for simple surface mounting. Adapter base for cable entry with screwed cable gland. Red or white ABS plastic housing. Function Powerful alarm - recognizable as a danger signal even against a high background noise level. 32 different tones programmable (user selectable). Adjustable sound intensity, improved tone clarity, automatic synchronization. Second input for secondary tone in two stage alarm systems. Technical data Operating voltage DC 18…28 V Alarm current 12 mA Operating temperature -25…+70 °C Tones 32 Sound level 102 dB(A) Cable capacity 0.28…1.5 mm² Protection category EN 60529/IEC 60529 – with DAB-R/ DAB-W

IP54 IP65

Dimensions Ø93 x 63 mm Color Red, white

DAB-R DAB-W

Adapter base Part no. S54370-N27-A1 S54370-N27-A2

Document Product data sheet A6V10423405

Application Deep base for surface wiring for all types of RoLP sounders for a higher protection category. Technical data Protection category EN 60529/IEC 60529 IP65 Color White or red Dimensions Ø93 x 50 mm

76

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 77: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

AGT24.1 Alarm device Part no. BPZ:5371040001 Document Product data sheet 001790

Application For fire detection and extinguishing systems. For small to medium size rooms with a low background noise level. Function 4 different tones with two sound intensities. Remote-controlled change of tone for two-stage alarm. Technical data Operating voltage DC 9…30 V Alarm current 3…15 mA Operating temperature -25…+85 °C Tones 4 Frequency range 510…970 Hz Sound level at 24 V and 1 m 86…97 dB(A) Cable capacity 0.28…1.5 mm² Protection category EN 60529/IEC 60529 IP42 Dimensions Ø110 x 35 mm Color white, ~RAL 9003

8.9.2 Beacons SOL-LX-W-RW / SOL-LX-W-WW & SOL-LW-C-WW

SOL-LX-W-RW SOL-LX-W-WW SOL-LX-W-RW SOL-LX-W-RW

Beacon, wall mounting Part no. S54370-N30-A1 S54370-N30-A2 S54370-N30-A3 S54370-N30-A4

Document Product data sheet A6V10423405

Application For use where current consumption is a key consideration. Ideal for bedrooms, bathrooms and toilets. White or red ABS plastic housing for surface mounting. Function Flashing signal lamp with red or white flashing color. Up to 7.5 m room coverage. Selectable flash rate from 0.5 Hz to 1 Hz to reduce the current consumption. Selectable range reduction to 2.5 m reduces the power consumption up to 50 %. Technical data Operating voltage DC 9…60 V Alarm current 10…25 mA Operating temperature -25…+70 °C Flash rate 1 Hz (switchable to 0.5 Hz) Coverage 7.5 m (switchable to 2.5 m) Coverage Volume 135 m³ (15 m³) Cable capacity 0.28…1.5 mm² Protection category EN 60529/IEC 60529 – with DAB-R/ DAB-W

IP33C IP65

Dimensions Ø93 x 37 mm

77

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 78: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

SOL-LW-C-WW SOL-LW-C-WR

Beacon, ceiling mounting Part no. S54370-N29-A1 S54370-N29-A2

Document Product data sheet A6V10423405

Application For use where current consumption is a key consideration. Ideal for bedrooms, bathrooms and toilets. White or red ABS plastic housing for surface mounting. Function Flashing signal lamp with red or white flashing color. Up to 7.5 m diameter room coverage. Selectable flash rate from 0.5 Hz to 1 Hz to reduce the current consumption. Selectable range reduction to 2.5 m recuces the power consumption up to 50 %. Technical data Operating voltage DC 9…60 V Alarm current 10…25 mA Operating temperature -25…+70 °C Flash rate 1 Hz (switchable to 0.5 Hz) Coverage 7.5 m (switchable to 3 m) Coverage Volume 132 m³ (21 m³) Cable capacity 0.28…1.5 mm² Protection category EN 60529/IEC 60529 – with DAB-R/ DAB-W

IP33C IP65

Dimensions Ø93 x 38 mm

DAB-R DAB-W

Adapter base Part no. S54370-N27-A1 S54370-N27-A2

Application Deep base for surface wiring for all types of SOL beacons for a higher protection category. Technical data Protection category EN 60529/IEC 60529 IP65 Color White or red Dimensions Ø93 x 50 mm

78

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 79: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

8.9.3 Combined sounders and beacons

RoLP-LX-RW RoLP-LX-WW RoLP-LX-WR RoLP-LX-RR

Sounder beacon Part no. S54370-N28-A1 S54370-N28-A2 S54370-N28-A3 S54370-N28-A4

Document Product data sheet A6V10423405

Application For use where current consumption is a key consideration. Ideal for bedrooms, bathrooms and toilets. Function Powerful alarm - recognizable as a danger signal even against a high background noise level. Additional flashing signal lamp with red or white flashing color. Up to 7.5 m room coverage. Selectable flash rate from 0.5 Hz to 1 Hz to reduce the current consumption. Selectable range reduction to 2.5 m reduces the power consumption up to 50 %. Technical data Operating voltage DC 18…28 V Alarm current 22…37 mA Operating temperature -25…+70 °C Sound level 102 dB(A) Flash rate 1 Hz (switchable to 0.5 Hz) Coverage 7.5 m (switchable to 2.5 m) Coverage Volume 135 m³ (15 m³) Cable capacity 0.28…1.5 mm² Protection category EN 60529/IEC 60529 IP65 Dimensions Ø135 x 95 mm

79

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 80: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

8.10 Devices for explosion-hazard area of zones 1 and 2 8.10.1 Interface for connection of the 'Ex' devices to C-NET

FDCIO223 Transponder Part no. S24218-B102-A1 Documents Product data sheet 009168 FDCIO223

Technical description 009122 Application For connection of collective fire detectors (GMT/conventional line, GMT/conventional line with shunt-Zener-diode barrier (SB3) for explosion-hazard areas). Accessories and spare parts for FDCIO223 see chapter 6.4.1 and 6.4.2. Technical data Operating voltage C-NET DC 12…33 V Communication protocol C-NET External power supply: Input voltage DC 18…32 V In-/outputs as collective detector line collective GMT Siemens/Cerberus, Synova con-

ventional/SynoLINE300, collective/SynoLINE600 or similar

Collective line factor (KLK) 32 Operating temperature -25…+60 °C Storage temperature -30…+65 °C Humidity ≤95 % rel. Connection terminals 0.2…1.5 mm2 (Auxiliary terminal 2.5 mm2) Color housing / cover white, ~RAL 9010 / transparent mAtt Protection category EN 60529/IEC 60529 – with auxiliary housing FDCH221

IP30 IP65

System compatibility C-NET FS720 Standards CEA GEI I-084, EN 54-17, EN 54-18 Dimensions 132 x 90 x 24 mm Approvals VdS G206054, LPCB 531m/03

80

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 81: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

8.10.2 Interface for connection of 'Ex' devices to SynoLINE600

DCA1191 Housing with cover Part no. BPZ:4588560001 DCA1192A Electronic unit, SynoLINE600 Bestell-Nr. BPZ:5081200001 DCB1192A Terminal base Bestell-Nr. BPZ:5084500001 Documents Product data sheet 001571 DCA1191

DCA1192A

DCB1192A

Technical description 1519 Application The input/output module DC1192 for galvanic isolation (detection line coupler) between control unit of collective line SynoLINE600 and shunt Zener diode barrier with fire detectors for explosion-hazard areas (via SB3). The housing DCA1191, the terminal base DCB1192A and the electronic unit DCA1192A must be or-dered separately. Technical data Primary line -> collective/SynoLINE600 – Compatibility E3M080, CI1110/15, FC330A, FC10, FC700A,

CZ10, KB24, GF24 Secundary line -> collective/SynoLINE600 – Operating voltage DC 18…22 V – Operating current max. 5 mA – Line resistance, depends on the type of line 50…250 Ω – End-of-line unit EOL22 (Ex) – Line factor (KLK) 25 Connection terminals 0.2…2.5 mm² (AWG24…14) External supply: Operating voltage DC 18…32 V Operating temperature -25…+70 °C Storage temperature -30…+75 °C Humidity ≤95 % rel. Color housing white, ~RAL 9010 Schutzart EN 60529 / IEC 60529 mit DCA1191 IP56 Standards EN 54-17, EN 54-18 Dimensions 135 x 135 x 65 mm Approvals VdS G298021, LPCB 126bm/02

EOL22(Ex) End-of-line Part no. BPZ:5162220001

Application End-of-line unit for collective detection lines as well as generally as end-of-line unit within explosion-hazard areas of zones 1 and 2.

81

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 82: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

8.10.3 Shunt Zener diode barrier SB3

SB3 Shunt Zener diode barrier Part no. BPZ:4837400001 Document Product data sheet 001222

Application This barrier is needed for an intrinsically safe installation in explosion-hazard areas connected to the in-/output module. This barrier restricts the electrical energy between non-intrinsically safe and intrinsically safe circuits. The installation has to be done according to the national safety regulations. The SB3 has to be mounted into the housing DCA1191 together with the Z3I410 installation set. Always install shunt Zener diode barriers outside explosion-hazard areas. Technical data Operating voltage max. DC 28 V Operating current max. 100 mA Type Stahl 9001/00-280-100-101 Standard EN 50014 (IEC 60079-0)/

EN 50020 (IEC 60079-11)

8.10.3.1 Accessories for SB3

DCA1191 Housing with cover Part no. BPZ:4588560001

Application For surface mounting in humid, wet areas. One Shunt Zener diode barrier SB3 can be built into the housing. Technical data Protection category EN 60529/IEC 60529 IP56 Dimensions 135 x 135 x 65 mm Color white, ~RAL 9010

Z3I410 Installation set Part no. BPZ:4837660001

Application One SB3 shunt Zener diode barrier mAy be mounted together with support plate Z3I410 in housing DCA1191 with protection category IP56.

DBZ1190-AA Micro terminal Part no. BPZ:4677080001 Details see chapter 2.2.1

– Metall-Kabelverschraubung M20 x 1,5 Part no. A5Q00004478 Details see chapter 2.3.1

82

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 83: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

8.10.4 Point detectors AlgoRex Serie 'Ex'

DO1101A-Ex Smoke detector, wide spectrum collective 'Ex' Part no. BPZ:5008010001 Documents Product data sheet 001469

Technical description 1485 Application For the early warning of smoke-forming, flaming fires and smoldering fires in explosion-hazard areas of zones 1 and 2. The base DB1101A must be ordered separately. Function Penetrating smoke scatters the light of an infrared beam in the detector. If the light scatter exceeds a certain value, the detector transmits a danger signal to the control unit. Technical data Communication protocol collective/SynoLINE600 Operating voltage DC 17…24 V Quiescent current max. 100 µA Operating temperature -25…+60 °C Storage temperature -30…+75 °C Ex-classification II 2 G Ex ib IIC T4 (-25 °C ≤Ta ≤60 °C) Dimensions 115 x 51 mm (incl. base) Humidity ≤95 % Protection category EN 60529/IEC 60529 IP44 Standard for fire detectors EN 54-7

for explosion-hazard areas EN 50014 (IEC 60079-0)/ EN 50020 (IEC 60079-11)

Approvals PTB 02 ATEX 2135 VdS G296052, LPCB 1161a/01

Color white, ~RAL 9010 System compatibility collective/SynoLINE600, in C-NET via Transpon-

der FDCIO223

DT1101A-Ex Heat detector collective 'Ex' Part no. BPZ:4852140001 Documents Product data sheet 001469

Technical description 1485 Application For the monitoring of explosion-hazard areas of zones 1 and 2 with a mAximum ambient temperature of 50 °C. It is characterized by reliable response behavior, not only in the event of slow temperature rises, but also where the temperature rises are fast. The base DB1101A must be ordered separately. Function The detector measures the ambient temperature with one NTC thermistor and the detector housing temperature with another NTC thermistor. In this way the detector can rapidly and differentially evaluate an increase in temperature independent of the starting temperature. Technical data Communication protocol collective/SynoLINE600 Operating voltage DC 16…24 V Quiescent current max. 100 µA Operating temperature -25…+50 °C Storage temperature -30…+75 °C Ex-classification II 2 G Ex ib IIC T4 (-25 °C ≤Ta ≤50 °C) Dimensions 115 x 54.5 mm (incl. base) Humidity ≤95 % rel. Protection category EN 60529/IEC 60529 IP44 Standard for fire detectors EN 54-5: A1R

for explosion-hazard areas EN 50014 (IEC 60079-0)/ EN 50020 (IEC 60079-11)

Approvals PTB 02 ATEX 2097 VdS G296019, LPCB 1161c/02

Color white, ~RAL 9010 System compatibility collective/SynoLINE600, in C-NET via Transpon-

der FDCIO223

83

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 84: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

DT1102A-Ex Heat detector collective 'Ex' Part no. BPZ:4852270001 Documents Product data sheet 001469

Technical description 1485 Application For the monitoring of explosion-hazard areas of zones 1 and 2 with a mAximum ambient temperature of 70 °C. It is the right heat detector for locations where large temperature fluctuations and high tempera-tures occur. It continuously measures the ambient temperature and reacts if defined mAximum values are exceeded. The base DB1101A must be ordered separately. Function The detector measures the ambient temperature with one NTC thermistor and the detector housing temperature with another NTC thermistor. In this way the detector can rapidly and differentially evaluate an increase in temperature independent of the starting temperature. Technical data Communication protocol collective/SynoLINE600 Operating voltage DC 16…24 V Quiescent current max. 100 µA Operating temperature -25…+70 °C Storage temperature -30…+75 °C Ex-classification II 2 G Ex ib IIC T4 (-25 °C ≤Ta ≤70 °C) Dimensions Ø115 x 54.5 mm (incl. base) Humidity ≤95 % rel. Protection category EN 60529/IEC 60529 IP44 Standard for fire detectors EN 54-5: B

for explosion-hazard areas EN 50014 (IEC60079-0)/ EN 50020 (IEC60079-11)

Approvals PTB 02 ATEX 2097 VdS G296019, LPCB 1161c/04

Color white, ~RAL 9010 System compatibility collective/SynoLINE600, in C-NET via Transpon-

der FDCIO223

DB1101A Detector base Part no. BPZ:4863650001 Document Product data sheet 001035

Base mAde of impact and scratch-proof plastic and environmentally safe mAterials. Integral rubber gasket to protect against draught, dirt and dripping water from above. Screwless terminals for easy installation. Space for auxiliary terminals as micro terminals (0.5 mm²) and connection terminals (2.5 mm²). Fits all standard flush-mounted boxes from 55 to 80 mm. Technical data Cable capacity 0.2…2.5 mm² Dimensions Ø115 x 21 mm Color white, ~RAL 9010

8.10.4.1 Accessories for DB1101A

DBZ1191 Base attachment, surface mounting Part no. BPZ:4540830001

5 pieces

Application For surface wiring feed and provision of more wire loop space. Bases DB1101A are mounted using a spring-loaded catch. Technical data Dimensions Ø116 x 22 mm Color white, ~RAL 9010

84

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 85: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

DBZ1190-AA Micro terminal Part no. BPZ:4677080001 DBZ1190-AB Auxiliary terminal Part no. BPZ:4942340001 Details see chapter 2.2.1

8.10.5 Infrared flame detector DF1101-Ex

DFB1190 Base for infrared flame detector Part no. BPZ:5165360001 DF1101-Ex Infrared flame detector collective 'Ex' Part no. BPZ:5166750001 Documents Product data sheet 001744 DFB1190

DF1101-Ex

Technical description 1673

Application Infrared flame detector for explosion-hazard areas of zones 1 and 2, for inside and outside applications. It is suitable for chemical production plants, oil refineries, propane and butane filling installations, for all explosion-hazard areas in which flaming fires involving carbonaceous mAterials could be expected. The base DFB1190 must be ordered separately. Function One sensor measures the hot carbon dioxide in a specific flame wavelength; the two other sensors simultaneously measure the interference radiation in other wavelengths. With intelligent signal pro-cessing through fuzzy algorithms and wavelet analysis, the DF1101-Ex achieves excellent detection reliability while mAintaining the highest immunity to interference radiation and sunlight. In order to safe-guard against a possible decision emergency, the detector contains an additional emergency activation channel. Technical data Communication protocol collective/SynoLINE600 Operating voltage DC 16…28 V Quiescent current 0.5 mA Operating temperature -35…+70 °C Storage temperature -40…+75 °C Ex-classification II 2 G Ex ib IIC T4 (-35 °C ≤Ta ≤70 °C) Dimensions 135 x 135 x 77 mm Humidity (no heavy condensation of window) ≤95 % rel. Protection category EN 60529/IEC 60529 IP67 Standard EN 54-10 for flame detectors

EN 50014 (IEC 60079-0), EN 50020 (IEC 60079-11) for explosion-hazard areas

Approvals VdS G299085, PTB 02 ATEX 2161, LPCB 126bb/01

Color white, ~RAL 9010 System compatibility collective/SynoLINE600, in C-NET via Transpon-

der FDCIO223

85

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 86: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

8.10.5.1 Accessories for DF1101-Ex

MV1 Mounting bracket Part no. BPZ:3950450001 MWV1 Ball and socket joint Part no. BPZ:3674840001 DFZ1190 Rain hood Part no. BPZ:5302660001 Details see chapter 2.5.1 MV1

MWV1

DFZ1190

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 Details see chapter 2.3.1

EOL22(Ex) End-of-line Part no. BPZ:5162220001 Details see chapter 8.10.4.1

86

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 87: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

8.10.6 Manual call points DM1103(Ex), DM1104(Ex)

DMA1192-AA Housing red with glass and key Part no. BPZ:5222870001 DMA1103D Switching unit collective Part no. A5Q00004470 DMA1104D Switching unit collective Part no. A5Q00005925 Document Product data sheet A6V10236643

DMA1103D

Label for manual call point in explosion-hazard area DMA1104D

Label for manual call point in explosion-hazard area

Application For immediate manual actuation of an alarm. For indoor and outdoor application, equally suited for wet, humid and dusty areas. For surface- and recess-mounted feed lines in easily accessible places. The housing DMA1192-AA and the electronic unit DMA110xD must be ordered separately. The label 'avoid electrostatic charging' is enclosed with switching unit DMA110xD. Function DM1103(Ex) Indirect alarm actuation by smashing in the glass plate and pressing the push button. To replace the glass plate, open the housing door with the key. The push button must be reset before closing the door again. DM1104(Ex) Direct alarm actuation by smashing in the glass plate. To replace the glass plate, open the housing door with the key, upon closing the door the button is reset. Technical data Communication protocol collective/SynoLINE600 Operating voltage DC 16…26 V Operating current 60…100 mA Anschlussklemmen 0.28…1.5 mm2 Einsatztemperatur -25…+70 °C Storage temperature -30…+75 °C Ex-classification 'simple apparatus' acc. EN 50020 § 5.4

Ex ib IIC T4 (Ta ≤70 °C) Humidity ≤95 % rel. Color red, ~RAL 3000 Protection category EN 60529/IEC 60529 – mit Dichtung DMZ1197-AD

IP54 IP65

Standard EN 54-11 Dimensions 134 x 134 x 43 mm Approvals – DM1103 – DM1104

VdS G295036 VdS G299068, LPCB 531j/02

System compatibility collective/SynoLINE600, in C-NET via Transpon-der FDCIO223

8.10.6.1 Accessories for DM1103(Ex), DM1104(Ex)

DMZ1197-AC Protective cover Part no. BPZ:5223550001 Details see chapter 8.5.5

87

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 88: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

DMZ1197-AD Protection seal Part no. BPZ:5470680001 Details see chapter 8.5.5

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 Details see chapter 8.5.5

– Locking plug red, M20 x 1.5 (1 hole) Part no. A5Q00006735 – Locking plug red, M20 x 1.5 (2 holes) Part no. A5Q00010055 Details see chapter 8.5.5

EOL22(Ex) End-of-line Part no. BPZ:5162220001 Details see chapter 8.10.4.1

8.10.6.2 Spare parts for DM1103(Ex), DM1104(Ex)

DMZ1196-AC Spare glass Part no. BPZ:4942050001 Details see chapter 8.5.6

DMZ1195 Key Part no. BPZ:4851910001 Details see chapter 8.5.6

88

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 89: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

8.10.7 Alarm indicators FDAI92-Ex, FDAI93-Ex

FDAI92-Ex Alarm indicator (wall mounting) Part no. S54370-F4-A1 Document Product data sheet A6V10276518

Application Alarm indicators are connected in parallel to automatic fire detectors in order to indicate quickly the source of an alarm signal from detectors, which are not easily accessible or visible. For recess supply line. For surface supply line use adapter frame AI330. Function The LEDs in the alarm indicator are on, as soon as the appropriate detector is in alarm. Only one external alarm indicator mAy be connected to each detector. Technical data Operating voltage DC 4…5 V Operating current, dauernd max. 35 mA Screwless connection terminals Wire cross-sectional area max. 1.5 mm2 Environmental temperature -25…+80 °C Ex-classification 'simple apparatus' acc. EN 50020 § 5.4

Ex ib IIC T4 (Ta ≤70 °C) Humidity ≤95 % rel. Protection category EN 60529/IEC 60529 IP40 Approvals EECS, ESTI Color white, ~RAL 9010 Dimensions 85 x 85 x 28 mm

8.10.7.1 Accessory for FDAI92-Ex

AI330 Adapter frame Part no. BPZ:3169430001

Application For surface laid conduit or ducts, to increase the loop space or as an adapter for different mAkes of box. Technical data Color white, ~RAL 9010 Dimensions 85 x 85 x 16 mm

89

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 90: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

FDAI93-Ex Alarm indicator incl. insulating cap Part no. S54370-F6-A1 Document Product data sheet A6V10276518

Application Made of transparent plastic, the FDAI93-Ex alarm indicator is suitable for installation in door frames, switching panels, ceiling voids or special housings. The 22.5 mm Ø mounting hole is drilled by the sys-tem owner. The holder must be fitted with the insulating cap for safety. For installation in humid rooms the DCA1191, DJZ1193 housings as well as a washer are available (must be ordered separately). Up to 4 alarm indicators can be built into the housing DCA1191. Function Indicator lamp to connect in parallel to automatic fire detectors. Only one external alarm indicator mAy be connected to each detector. Technical data Operating voltage DC 1,5 V Operating current, dauernd max. 20…30 mA Screwless connection terminals Wire cross-sectional area max. 1.5 mm2 Environmental temperature -25…+80 °C Ex-classification 'simple apparatus' acc. EN 50020 § 5.4

Ex ib IIC T4 (Ta ≤70 °C) Humidity ≤95 % rel. Protection category EN 60529/IEC 60529 – with DJZ1193 – with DCA1191

IP65 IP56

Approvals EECS, ESTI, PTB Color transparent plastic Dimensions Ø26 x 51 mm

– Insulating cap Part no. BPZ:3048160001

Application Use as spare part.

8.10.7.2 Accessories for FDAI93-Ex

DCA1191 Housing with cover Part no. BPZ:4588560001 – Washer Part no. BPZ:2473130001 DCA1191

Washer

Application For surface mounting in humid, wet areas. Up to 4 alarm indicators FDAI93-Ex can be built into the housing. Technical data Housing with cover Protection category EN 60529/IEC 60529 IP56 Dimensions 135 x 135 x 65 mm Color white, ~RAL 9010 Washer Dimensions Ø23 x 1 mm

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 Details see chapter 2.3.1

90

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 91: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Conventional and collective devices

DJZ1193 Alarm indicator housing incl. washer Part no. BPZ:5302950001

Application For surface mounting in dry areas. 1 alarm indicator FDAI93-Ex can be built into the housing. Technical data Protection category EN 60529/IEC 60529 IP65 Color white, ~RAL 9010 Dimensions 87 x 87 x 64 mm

MVH1 Mounting arm Part no. BPZ:3496190001

Application For mounting of the alarm indicator housing DJZ1193 and detectors in hollow floors. Technical data Pipe clamp ½" Dimensions 20 x 20 x 290…420 mm

8.10.8 Alarm device DB3 for explosion-hazard areas

DB3 Alarm device for explosion-hazard areas for

zones 1 and 2 Part no. BPZ:5757970001

Document Product data sheet 009001

Application The flameproof audible alarm device is intended for the use in potentially explosive atmospheres. It has been designed with high ingress protection to cope with harsh environmental conditions. Technical data Operating voltage DC 12…48 V Alarmstrom max. 380 mA Volume at 24 V and 1 m 101…115 dB(A) Anzahl Töne 27 Operating temperature -20…+55 °C Ex-classification II 2 G Ex d IIC T5 (-20 °C ≤Ta ≤55 °C) Cable capacity 6 x 2,5 mm² Dimensions 137 x 184 mm Color red, anti-static, UV stable,

glass reinforced polyester Approvals BAS 00ATEX2097X Standard CENELEC, EN 50014, 18 Protection category EN 60529/IEC 60529 IP66/67

91

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 92: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Test equipment and accessories

9 Test equipment and accessories 9.1 Detector exchanger for FD720 point detectors

DX791 Detector exchanger Part no. S54319-F6-A1 Document Product data sheet A6V10203222

Application For all Cerberus PRO FD720 point detectors and dust caps. Function Rational insertion and removal of point detectors. Equipped with a vacuum cup for insertion and removal of dust cap. Compatible with the telescope rods FDUM291/292 and the conventional extension rods VR10/11/12/13 and the MP/MT grab rods and extension rods. Technical data Dimensions Ø30 x 35 x 160 mm

9.1.1 Accessory DX791

FDUD491 Adapter Part no.. S54319-F18-A1

Anwendung Adapter for the detector exchanger for FD720 point detectors

92

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 93: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Test equipment and accessories

9.2 Detector tester RE6, RE6T, RE7T, RE8ST, RE8STCO

RE6 Detector tester for smoke detectors Part no. BPZ:3680300001 Document Product data sheet A6V10203222

Application The detector tester (delivered with bellow DZZ1190) is placed over the detector and given a brief push to release the test gas and so simulate the presence of fire aerosols. The detector responds quickly and actuates an alarm. The test gas is free of halogenated chlorofluorocarbons (CFCs). It is not combustible. The extension rod FDUM291/292 and the test gas can REF8, REF8-S must be ordered separately.

9.2.1 Accessories for RE6

RG320 Bellow for RE6 Part no. BPZ:5166880001

Application The bellow is fitted to the RE6 to fit all Synova 300 point detectors in an ideal way.

REF8 Test gas can for smoke detectors Part no. A5Q00011687 REF8-S Test gas can for smoke detectors Part no. A5Q00011688 REF8 REF8-S

Application REF8 has been developed as an environmentally friendly test gas for the testing of smoke detectors. REF8 can be used in the temperature range of 0…+40 °C in dry or in humid environments. Complies with environmental laws. Protects atmosphere and ozone layer. REF8-S has been developed as environmentally friendly test gas for the testing of smoke detectors. REF8-S can be used in the temperature range of -20…+40 °C in dry or in humid environments. REF8-S remains measurable longer than REF8, and is used for detectors having a longer signal evaluation time. Complies with environmental laws. Protects atmosphere and ozone layer. Use only together with detector tester RE6.

93

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 94: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Test equipment and accessories

RE6T Detector tester for heat detectors Part no. BPZ:3680270001 Document Product data sheet A6V10203222

Application This detector tester contains a hot air generator. For the performance check, the tester is pushed over the detector. The hot air released, heats the detector and so actuates an alarm. The extension rod FDUM291/292 must be ordered separately.

Forbidden in electrical switching stations or areas where there is a danger of explosion!

Technical data Mains voltage AC 220 V / 50…60 Hz, ~300 W Operating temperature 0…+40 °C

RE7T Solo461 Heat detector tester kit Part no. A54370-S3-A1 Document Product data sheet A6V10252901

Anwendung The detector tester contains a hot air generator. For the performance check, the tester is pushed over the detector. The hot air released, heats the detector and so actuates an alarm. The adaptor RE7T-A and the extension rod FDUM291/292 must be ordered separately. Kit consists of: – Tester – 2 Battery batons – Charger

Forbidden in electrical switching stations or areas where there is a danger of explosion!

Technical data Operating temperature 5…+45 °C Storage temperature -10…+50 °C Humidity ≤95 %

RE8ST Testfire 1001-101 ST test kit Part no. S54370-S23-A1 Document Product data sheet A6V10397718

Application The detector tester contains a smoke capsule. For the performance check, the tester is pushed over the detector. The smoke released actuates an alarm. The extension rod FDUM291/292 must be ordered separately. Kit consists of: – 1 Testfire 1001-101 tester – 1 smoke capsule – 2 Batteries – 1 Charger (incl. 12V connection cable) – 2 mAins cables (110 / 120-220 / AC 240 V) – 1 USB cable

Forbidden in electrical switching stations or areas where there is a danger of explosion!

Technical data Operating temperature 5…+45 °C Storage temperature -10…+50 °C Humidity ≤95 %

94

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 95: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Test equipment and accessories

RE8STCO Testfire 2001-101 ST test kit Part no. S54370-S24-A1 Document Product data sheet A6V10397718

Application The detector tester contains a smoke or a CO capsule. For the performance check, the tester is pushed over the detector. The smoke / CO released actuates an alarm. The extension rod FDUM291/292 must be ordered separately. Kit consists of: – 1 Testfire 1001-101 tester – 1 smoke capsule – 1 CO capsule – 2 Batteries – 1 Charger (incl. 12V connection cable) – 2 mAins cables (110 / 120-220 / AC 240 V) – 1 USB cable

Forbidden in electrical switching stations or areas where there is a danger of explosion!

Technical data Operating temperature 5…+45 °C Storage temperature -10…+50 °C Humidity ≤95 %

9.2.2 Accessories for RE7T, RE8ST, RE8STCO

RE7T-A Solo719 Adaptor for FDUM29x Part no. S54370-N4-A1

Application Adaptor from heat detector tester RE7T to the telescope rods FDUM29x.

95

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 96: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Test equipment and accessories

9.2.3 Spare parts for RE7T

RE7T-B Solo760 Battery for RE7T Part no. S54370-N5-A1

Application Use as spare part for RE7T heat detector tester.

RE7T-C Solo725 Charger for RE7T Part no. S54370-N6-A1

Application Use as spare part for charging of battery baton to the RE7T heat detector tester.

RE8-S RE8-S für RE8ST & RE8STCO Part no. S54370-N25-A1

Application Use as spare part for RE8ST & RE8STCO. 6 pieces

RE8-CO RE8-CO für RE8STCO Part no. S54370-N22-A1

Application Use as spare part for RE8STCO. 6 pieces

9.2.4 Accessories for DX791, RE6, RE6T, RE7T, RE8ST, RE8STCO

FDUM291 Telescope rod Part no. A5Q00004996

Application The three-part telescope with tri-oval tubes serve as extensions for the detector exchanger and other applications up to 5 m. Technical data Color yellow, black Dimensions Ø34.5 mm x 1.6 m (drown out length= 4.2 m)

96

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 97: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Test equipment and accessories

FDUM292 Telescope rod Part no. A5Q00004997

Application The three-part telescope with tri-oval tubes serve as extensions for the detector exchanger and other applications up to 8 m. Technical data Color yellow, black Dimensions Ø44.5 mm x 2.1 m (drown out length = 7.3 m)

9.2.4.1 Spare parts for FDUM291

– Adapter with lever, screw and nut incl. attach-

ment and bushing screw Part no. A5Q00009786

– Lever with screw and nut Part no. A5Q00009787 – Small flap with screw and nut Part no. A5Q00009788 – Large flap with screw and nut Part no. A5Q00009789

Application Use as spare part.

9.2.4.2 Spare parts for FDUM292

– Adapter with lever, screw and nut incl. attach-

ment and bushing screw Part no. A5Q00009786

– Lever with screw and nut Part no. A5Q00009787

Application Use as spare part.

97

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 98: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Test equipment and accessories

9.3 Detector base tester DZB1191

DZB1191 Detector base tester Part no. BPZ:4680660001 Document Product data sheet 001049

Application The DB1191 base tester is handy and simple means of testing the detection line and detector base connections. Function The base tester is inserted in the detector base like a detector. Bases can be tested during installation either individually or consecutively after installation is completed. The DBZ1191 can test for open lines, short circuit, earth leakages, polarity and alarm indicator connec-tion.

9.4 Test equipment for linear smoke detectors 9.4.1 Adjustment device set FDLU291

FDLU291 Adjustment device set for linear smoke detector Part no. A5Q00004905 Documents Product data sheet 007017

Technical description 007016 Application The optics can be rationally adjusted to the reflector by single-handed alignment by means of the ad-justment device. Box with adjustment device, alarm test filter, visor, mAgnet, spiral cable, MC-link cable, and battery 9 V, 0.5 Ah. Technical data Dimensions adjustment device 120 x 65 x 22 mm

9.4.2 Detector tester RE10

RE10 Detector tester Part no. BPZ:3685190001 Document Product data sheet A6V10203222

Application For performance check of linear smoke detector. In compliance with the type of detector to be tested, the alarm test filter is inserted in the detector tester. Alarm test filter contained in FDLU291 or TF04 must be ordered separately. Function The detector tester is then held in front of the optical parts of the detector (i.e. into the infrared ray). The detector reacts after a few seconds.

TF04 Alarm test filter (Absorption 77 %) Part no. BPZ:4931090001

Application Alarm test filter for detector tester RE10.

98

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 99: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Test equipment and accessories

9.5 Line tester FDUL221

FDUL221 Line tester Part no. A5Q00004397 Documents Product data sheet A6V10203222

Operation 008250 Application The line tester is a universal device for the final testing of completely installed C-NET fire detection lines, when no control unit has been connected yet. For troubleshooting for electricians, installers or service technicians. Line tester incl. line connection set FDUL221-A and power supply set FDUL221-B. Technical data Line tester Operating voltage – Battery or via – mains adapter

min. DC 10 V, max. DC 30 V 2 x 9 V AC 240 V / DC 24 V, 625 mA

Current consumption during measuring depending on number of devices Detection line voltage – C-NET (FS720)

DC 32 V

Max. connection factor (MK) per line – with mAins adapter – with battery

Min. 550 min. 150

Operating temperature -25…+40 °C Storage temperature – with battery

-30…+75 °C -25…+60 °C

Humidity ≤95 % rel. (no condensation) Dimensions 190 x 135 x 45 mm Mains adapter AC/DC Input voltage AC 100…240 V / 50…60 Hz / 400 mA Output voltage DC 24 V / 625 mA Dimensions 115 x 52 x 33 mm

9.5.1 Accessories for FDUL221

– Lithium brownstone battery 9 V / 1 Ah Part no. A5Q00004142

10 pieces

Application For the supply of the line tester and others. Technical data Dimensions 25 x 48 x 16 mm

99

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 100: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Test equipment and accessories

9.5.2 Spare parts for FDUL221

FDUL221-A Line connection set Part no. A5Q00008436 FDUL221-B Mains adapter set Part no. A5Q00008437 FDUL221-C PC cable (RS232) Part no. A5Q00008438

FDUL221-A A5Q00008436 Line Connection Set Application Use as spare part.

FDUL221-B A5Q00008437 Power Supply Set FDUL221-C A5Q00008438 PC Cabel (RS232)

9.6 Test lamps for flame detectors

LE3 Test lamp Part no. BPZ:3669510001 FA2003-A1 Battery (12 V, 7 Ah, VDS) Part no. A5Q00019353 Document Product data sheet A6V10203222

Application For checking the alarm function of all flame detector for distance up to 10 m. Technical data Test lamp Dimensions 178 x 180 x 369 mm Battery Dimensions 153 x 103 x 67 mm

9.6.1 Spare part for LE3

– Halogen lamp 12 V / 50 W Part no. BPZ:3679630001

Application Use as spare part.

100

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 101: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Test equipment and accessories

StabexHF Test lamp for flame detectors 'Ex' Part no. BPZ:4620910001 Document Product data sheet 000252, A6V10203222

Application The test lamp is used to carry out a performance check of intrinsically safe flame detectors in explosion-hazard areas of zones 1 and 2. Technical data Operating temperature -20…+40 °C Storage temperature -20…+40 °C Battery capacity 2 x Alkali battery 1.5 V, single-cell UM1 Ex-classification II 2 G Ex ib e IIC T4 Protection category EN 60529/IEC 60529 IP65 Approvals PTB 98 ATEX 2062

9.7 Adapter for C-NET devices

FDUZ227 MCL USB adapter Part no. S54323-F106-A1 Document Product data sheet A6V10355605

Installation A6V10347735 Application The MCL USB adapter is an interface converter for USB to MC link. It can be used to connect FDnet devices or C-NET devices to a PC using a serial protocol (MCL). Function The adapter is used for floor repeater display FT2011-A1, for floor repeater terminal FT2010-A1, for radio gateways FDCW221 & FDCW241, for detector exchanger and tester FDUD292/293 and for line tester FDUL221 (in the future other FDnet devices possible). The SWING devices FDOOT271 & FDCW241 can communicate via radio with the FDUZ227 (in the future other SWING devices will be possible). The radio communication requires the tool FXS2061. Technical data Power supply via USB (5V) Interface USB 2.0, MC link, FDnet, radio Operating temperature -10…+55 °C Storage temperature -20…+60 °C Humidity ≤95 % rel. Dimensions (WxHxD) 100 x 30 x 54 mm Protection category IP30

101

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 102: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Index

10 Index

A Adapter base

for RoLP 76, 78 Adapter for detector exchanger 92 Adapter frame

for AI92C 73 for FDAI92 57 for FDAI92 and for FDCAI221 22 for FDAI92-Ex 89

Adapter with lever for FDUM291 97 for FDUM292 97

Adjustment device set for linear smoke detector 98 AGT24.1 77 AI330 22, 57, 73, 89 AI91C 73 AI92C 73 Air flow tube 0.6 m 75 Air flow tube 1.5 m 75 Air flow tube 2.8 m 75 Air sampling smoke detection kit 74 Alarm device

conventional 76, 77 Alarm device for explosion-hazard areas for zones

1 and 2 91 Alarm indicator (door frame)

for C-NET devices 21 for conventional/SynoLINE300 devices 73 for conventional/SynoLINE600 devices 57

Alarm indicator (wall mounting) for C-NET devices 21 for conventional/SynoLINE300 devices 73 for conventional/SynoLINE600 devices 57 for explosion-hazard area 89

Alarm indicator housing incl. washer for AJUT24-Ex 91 for FDAI93 59

Alarm indicator incl. insulating cap 58 for explosion-hazard area 90

Alarm indicator, resistor 75 Ω 22 Alarm sounder

red 35 white 35

Alarm sounder with supplementary optical indication, orange 36

Alarm sounder with supplementary optical indication, red 36

Alarm test filter (Absorption 77 %) 98 Aspirating smoke detector (5S) 53 Aspirating smoke detector (8H) 53

Aspirating smoke detector with display 54 Auxiliary terminal 15, 26, 37, 41, 42, 56, 63, 65, 72,

85

B BA720 15, 56, 63 BA721 38 Back box

for FDM1101A-Rx 71 for FDM1101-Rx 64 for FDM225-xx 26

Back nut for screwed cable gland 24, 26, 48, 65, 67, 72

Ball and socket joint for flame detector 20, 86

Base 50 Base attachment

for FDB22x 37 Base attachment for OOH740 15, 56, 63 base attachment wet with additional integrated

rubber seal 38 Base attachment wet with seal 38 Base attachment, surface mounting

for DB1101A 84 Base for collective detector series

for DO1104A 75 Base for infrared flame detector

for DF1191-Ex 85 Base for infrared flame detector 19

FDF2x1-9 18 Base for linear smoke detector

FDL241-9 16 BAT3.6-10 50, 52 Battery (12 V, 7 Ah, VDS)

for test lamp 100 Beacon, ceiling mounting 78 Bellow for RE6

for Synova 300 detectors 93 Blanking plate 41 BP720 41

C Communication interface 53 Cover with key

for DM1101 67 for FDM221 24

D DAB-R 76, 78 DAB-W 76, 78 DB110 55, 62

102

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 103: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Index

DB1101A 75, 84 DB110D 62 DB110R 62 DB110RD 62 DB3 91 DB721 14 DB721D 14, 55 DB722 14 DBS720 14, 42 DBS721 40 DBS729 41 DBZ1190-AA 15, 37, 41, 42, 56, 63, 82, 85 DBZ1190-AB 15, 26, 37, 41, 42, 56, 63, 65, 72, 85 DBZ1191 84 DBZ1193A 38 DBZ1194 39 DCA1191 58, 81, 82, 90 Designation plate 50 Designation plate

for DB720 15 for DBS720 41, 42 for FDB221/222 37 for FDB293 38

Designation plate for DBS720 56

Designation plate for DBS720 63

Detector base for collective/SynoLINE600 detectors 84

Detector base 14 for FDS221, FDS229 36 for OOH740 collective 14, 55 Parameter set 1 62 parameter set 1 for BS5839, Part 1 62 parameter set 2 62

Detector base parameter set 2 for BS5839, Part 1 62

Detector base DB110 (Parameter set 1) 55 Detector base seal

for DB720 and DBS720 15, 42, 56, 63 Detector base tester

for base DB1101A 98 Detector base with loop contact

for OH/OP/HI720 14 Detector base, flat

for FDS221, FDS229 36 Detector exchanger

for FD720 point detectors 92 Detector heating element

for FDL241-9 17 Detector heating incl. micro terminals 39 Detector locking device 13, 37, 62 Detector tester

for heat detectors 94 for linear smoke detectors 98 for smoke detectors 93

DF1101-Ex 85 DFB1190 85 DFZ1190 20, 86 Dire and CO detector, neural ASA 10 DJZ1193 59, 91 DLF1191-AA 17 DLF1191-AB 17 DLF1191-AC 17 DLH1191A 17 DLR1191 17 DLR1192 17 DLR1193 17 DM1103-L 69 DM1103-S 69 DMA1101 66 DMA1103D 68, 87 DMA1104D 68, 87 DMA1192-AA 68, 87 DMA1192-AB 68 DMA1192-AC 68 DMA1192-AD 68 DMZ1195 30, 34, 52, 70, 88 DMZ1196-AC 30, 34, 52, 70, 88 DMZ1197-AC 29, 33, 52, 69, 87 DMZ1197-AD 29, 33, 70, 88 DO1101A-Ex 83 DO1104A 74 DT1101A-Ex 83 DT1102A-Ex 84 DX791 92 DZB1191 98

E Electronic unit, SynoLINE600 81 EMC Protective cage 39 Emergency stop button complete

for extinguishing system 69 End-of-line

EOL22(Ex) 81, 86, 88 EOL22(Ex) 81, 86, 88 Extraneous light filter 17

F FA2003-A1 100 FDA221 53 FDA241 53 FDAI91 21, 57 FDAI92 21, 57 FDAI92-Ex 89 FDAI93 58 FDAI93-Ex 90 FDB221 36 FDB222 36 FDB271 50 FDB291 37

103

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 104: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Index

FDB293 38 FDB295 38 FDBH291 39 FDBZ291 15, 37, 41, 42, 50, 56, 63 FDBZ292 74 FDBZ292-AA 75 FDBZ292-AB 75 FDBZ292-AC 75 FDBZ292-AD 75 FDBZ292-AF 75 FDBZ293 37 FDBZ294 39 FDBZ295 37 FDCAI221 22 FDCC221S 53 FDCH221 48 FDCI221 45 FDCI222 45 FDCIO221 46 FDCIO222 46 FDCIO223 47, 80 FDCIO224 47 FDCL221 43 FDCL221-M 44 FDCM291 48 FDCW241 49 FDF221-9 18 FDF241-9 19 FDFB291 18, 19 FDL241-9 16 FDLB291 16 FDLU291 98 FDM1101A-RG 71 FDM1101A-RP 71 FDM1101-RG 64 FDM1101-RP 64 FDM223 31 FDM225-RG 25 FDM225-RP 25 FDM226-RG 25 FDM226-RP 25 FDMC291 24, 67 FDMC295 26, 65, 72 FDME221 23 FDME223 32, 33 FDME224 28, 29 FDME273 51 FDMG291 24, 67 FDMG295 27, 65, 72 FDMH273 51 FDMH291-B 23, 66 FDMH291-G 23, 66 FDMH291-R 23, 66 FDMH291-Y 23, 66 FDMH292-R 29, 33

FDMH293-B 28, 32 FDMH293-G 28, 32 FDMH293-O 28 FDMH293-R 28, 32 FDMH293-Y 28, 32 FDMH295-R 26, 64, 71 FDMH295-S 26, 64, 71 FDMK291 24, 67 FDMK295 27, 65, 72 FDMP295 27, 65, 72 FDOOT271/FDB271 50 FDS221-R 35 FDS221-W 35 FDS229-A 36 FDS229-R 36 FDUD491 92 FDUL221 99 FDUL221-A 100 FDUL221-B 100 FDUL221-C 100 FDUM291 96 FDUM292 97 FDUZ227 101 Flashing signal lamp, wall mounting 77

G Glass

for FDM221 24 for FDM223 34 for FDM224 30 for FDM224, FDM224H and FDM273 52

Glass plate 'neutral' for FDM1101A-RG 72 for FDM1101-RG 65 for FDM1225/226 27

H Halogen lamp 12 V / 50 W

for LE3 100 Heat detector (collective, differential) 61 Heat detector (static + RoR) 12 Heat detector (static) 13, 61 Heat detector collective 'Ex' 83, 84 Heavy Duty housing red with glass, hexagon

wrench key, 3 nipples and plate Feuerwehr/Brandmelder 33

HI110 61 HI112 61 HI720 12 HI722 13 Housing blue with glass and key

for DMA110xD 68 for FDME223 32 for FDME224 28

Housing blue with key

104

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 105: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Index

for DMA1101 66 for FDME221 23

Housing for input/output modules 48 Housing green with glass and key

for DMA110xD 68 for FDME223 32 for FDME224 28

Housing green with key for DMA1101 66 for FDME221 23

Housing Heavy Duty red for FDME224 29

Housing orange with glass and key for FDME224 28

Housing red with glass and key for DMA110xD 68, 87 for FDME223 32 for FDME224 28

Housing red with key for DMA1101 66 for FDME221 23

Housing red, with glass and key 51 Housing with cover

for DC1192 81 for FDAI93 58 for FDAI93-Ex 90 for SB3 82

Housing yellow with glass and key for DMA110xD 68 for FDME223 32 for FDME224 28

Housing yellow with key for DMA1101 66 for FDME221 23

I Infrared flame detector (1 Sensor) 18 Infrared flame detector (3Sensors)

with ASAtechnology 19 Infrared flame detector collective 'Ex' 85 Input module

1 input 45 4 inputs 45

Input/output module 1 input, 1 output 46 4 inputs, 4 outputs 46 for extinguishing controls 47

Installation set for SB3 in DCA1191 82

Insulating cap for FDAI93 58 for FDAI93-Ex 90

K Key

for DMA1192-AA 88 for DMA1192-xx 70 for FDM1101A-Rx 72 for FDM1101-Rx 65 for FDM225/226 27 for FDMH293-x 30, 34 for FDMH293-x and FDMH273 52

L Large flap

for FDUM291 97 LaserFOCUS VLF-250 54 LaserFOCUS VLF-500 54 LE3 100 Lever with screw and nut

for FDUM291 97 for FDUM292 97

Line connection set for FDUL221 100

Line separator 43 Line tester

for C-NET detector line 99 Linear smoke detector

with ASAtechnology 16 LI-SOCI2 3,6V-10 Ah 49, 50, 52 Lithium brownstone battery 9 V / 1 Ah 99 Locking plug M20 x 1.5 (1 hole)

for DMA1192-AA 88 for DMA1192-xx 70 for FDMH293-x 30

Locking plug M20 x 1.5 (2 holes) for DMA1192-AA 88 for DMA1192-xx 70 for FDMH293-x 30

Long distance reflector (Prism) 17 LP720 13, 62

M Mains adapter set

for FDUL221 100 Manual call point complete

housing red with glass, key, switching unit and locking plug 31

manual call point with glass plate collective/SynoLINE600 64 conventional/SynoLINE300 71

Manual call point with glass plate 25 Manual call point with glass plate incl. housing base

25 Manual call point with plastic element 25 Manual call point with plastic element incl. housing

base 25 manual call point with resettable plastic element

collective/SynoLINE600 64 conventional/SynoLINE300 71

105

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 106: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Index

manual release button complete for extinguishing system 69

MCL USB adapter Radio 101

Metal screwed cable gland M20 x 1.5 for DCA1191 58, 90 for DFB1190 86 for DMA1192-AA 88 for DMA1192-xx 70 for FDCH221 48 for FDFB291 20 for FDFB293 38 for FDLB291, DLR1191 17 for FDMH291-x 24, 26, 67 for FDMH293-x 30, 34 for FDMH295-R 65, 72

Metall-Kabelverschraubung M20 x 1,5 zu DCA1191 82

Micro terminal 15, 37, 41, 42, 56, 63, 82, 85 Middle distance reflector (400cm2) 17 Mounting arm 59, 91 Mounting bracket 75

for flame detector 20, 86 Mounting feet for input/output modules 48 Mult sensor smoke detector, ASA 9, 55 Multi line separator 44 Multi-sensor fire detector (collective) 60 Multi-sensor smoke detector 11 MV1 20, 86 MVH1 59, 91 MWV1 20, 86

N Neural radio detector 50

O OH110 60 OH720 11 OOH740 9, 55 OOHC740 10 OP110 60 OP720 11

P Parameter set resistor 33k) 56 Parameter set resistor 68k) 56 PC cable (RS232)

for FDUL221 100 Plastic element 'neutral'

for FDM1101A-RP 72 for FDM1101-RP 65 for FDM225/226 27

Protection seal for areas for DM1103/04 70 for DM1103/04(Ex) 88

Protective cage for FDB293 39

Protective cover for DM1101 67 for DM1103/04 69 for DM1103/04(Ex) 87 for FDM1101A-Rx 72 for FDM1101-Rx 65 for FDM221 24 for FDM223 33 for FDM224 29 for FDM225/226 26

Protective cover for FDM224, FDM224H and FDM273 52

PSR720-1 56 PSR720-2 56

R Rain hood

for flame detector 20, 86 RE10 98 RE6 93 RE6T 94 RE7T 94 RE7T-A 95 RE7T-B 96 RE7T-C 96 RE8-CO 96 RE8-CO for RESTCO

as spare part 96 RE8-S 96 RE8-S for RE8ST & RE8STCO

as spare part 96 RE8ST 94 RE8STCO 95 REF8 93 REF8-S 93 Replacement glass

for FDMH291-x 67 RG320 93 RoLP/R/S 76 RoLP-LX-RR 79 RoLP-LX-WR 79 RoLP-LX-WW 79 RoLP-LX-WW 79 RS720 15, 42, 56, 63

S SB3 82 Seal for wet areas

for FDM223 33 for FDM224 29

Sealing element for FDS221-x/FDS229-x 37

Sealing kit for air flow tubes 75

106

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 107: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Index

Short distance filter 5-8m 17 Short distance filter 7-10 m 17 Short distance reflector (100cm2) 17 Shunt Zener diode barrier 82 Small flap

for FDUM291 97 Smoke detector 11 Smoke detector (collective) 60 Smoke detector, collective wide spectrum

for FDBZ292 74 Smoke detector, wide spectrum collective 'Ex' 83 SOL-LW-C-WW 78 SOL-LX-W-RW 77 SOL-LX-W-WW 77 Solo461 Heat detector tester kit 94 Solo719 Adaptor for FDUM29x 95 Solo725 Charger for RE7T

as spare part 96 Solo760 Solo760 Battery for RE7T

as spare part 96 Sounder base 42

for OH/OP/HI720 14 Sounder beacon 79 Sounder interbase 40 Sounder interbase with supplementary optical

indication 41 Spare glass

for DM1103/04 70 for DM1103/04(Ex) 88

StabexHF 101 SWING Radio gateway 49 Switching unit

for FDMH291-x 23 for FDMH292-R 29, 33 for FDMH293-x 28, 32

Switching unit collective direct alarm actuation 66, 68, 87 indirect alarm actuation 68, 87

Switching unit to FDM273 51

T Telescope rod 96, 97 Terminal base

for DCA1192A 81 Test gas can for smoke detectors

for RE6 93 Test lamp 100 Test lamp for flame detectors 'Ex' 101 Testfire 1001-101 ST test kit 94 Testfire 2001-101 ST test kit 95 TF04 98 Transponder 47, 80 TS35, L=288 mm 44

U U-rail TS35, L=122 mm 44 U-rail TS35, L=122 mm 48 U-rail TS35, L=288 mm 48

V V-plug PA M20 x 1.5

for FDMH292-R 30, 34

W Washer

for DCA1191 58, 90

Z Z3I410 82

107

Building Technologies 058_FD720_Equipment_overview_A6V10225323_j_en.doc CPS Fire Safety 04.2014

Page 108: FD720 Cerberus™ PRO, Detector system Equipment overview · Automatic fire detectors in C-NET 2 Automatic fire detectors in C-NET 2.1 Point detectors with detection algorithms OOH740

Siemens Switzerland Ltd Infrastructure &Cities Sector Building Technologies Division International Headquarters CPS Fire Safety Gubelstrasse 22 CH-6301 Zug Tel. +41 41 724 24 24 www.siemens.com/buildingtechnologies

Document no. A6V10225323_j_en_-- Manual FD720 Edition 04.2014 Section 1