VM1 Innovation in medium voltage technologyVacuum circuit-breaker with magnetic actuator

Main Characteristics• Maintenance-free• Extremely high number of operating cycles• Electronic controller with sensor technology • Vacuum interrupters embedded in epoxy resin• High quality standard• Compatible with conventional circuit-breakers• For universal applications worldwide

AB

B P

T /

3

VM1

VM1Rated voltage kV 12 17.5 24

Rated current A ...2500 ...2500 ...2500

Rated short-circuit kA ...31.5 ...31.5 ...25breaking current

AB

B P

T /

4

VM1

“new“ VD4 “new look“ VM1

�Common look and feel� the same common look and feel according to PT Guidelines for Product

Design

AB

B P

T /

5

VM1

“new look“ VM1“new“ VD4

� “new“ VD4 and “new look“ VM1 have common frame suitable forinterchangeable plug-in actuators

AB

B P

T /

6

VM1

Emergency manual breaking mechanism

Electronic controller

Magnetic actuator

Electrical energy store

Sensors for switching position detection

AB

B P

T /

7

VM1

AB

B P

T /

8

VM1

Main characteristics� Electronic maintenance-free

� Controller with sensor technology

� Magnetic actuator with extremely high number of operating cycles� up to 100,000 operating cycles for breaking capacity up to 25 kA and rated current up

to 1250 A

� up to 50,000 operating cycles with rated current > 1600 A and/or breaking capacity > 31.5 kA

� Embedding technology to protect vacuum interrupters

� High quality standard

� External dimensions compatible with VD4

� Developed for universal applications worldwide

AB

B P

T /

9

VM1

Single-line diagram of electronic controller

AB

B P

T /

10

VM1

-SO4 Undervoltage opening (only withED2.0 Full Option)

-SL1 Contact locking the CB closing-SO3 Auxiliary and safety open (2^

open command from remote)-SO2 Open command from remote

-SC2 Close command from remote

DO7 CB Remote Open

DO6 Unit Not Ready

DO5 Unit Ready

DO2 CB closed

DO1 CB open

24 .. 48V AC / 24 .. 60 V DC100 .. 240V AC / 110 .. 250 V DC

Auxiliary voltage supply

AB

B P

T /

11

VM1

Electronic controller

Capacitor Sensors

AB

B P

T /

12

VM1

Magnetic actuator

AB

B P

T /

13

VM1Representation of magnetic flux density distribution

Magnetic latching in end-of-runposition

Armature position: 0 mmAmpere-turns: 0 A

Magnetic latching and action of the magnetic field of a coil

Armature position: 0 mmAmpere-turns: 12500 A

Moving armature in opposingposition and magnetic end-of-runlatching

Armature position: 20 mmAmpere-turns: 5000 A

AB

B P

T /

14

VM1

Reduction of the magnetic flux density of Koerdym 280 as a function of the lifetime t at an ambient temperature of 120°C

y

AB

B P

T /

15

VM1Basic version

� Closing pushbutton (SC1)

� Opening pushbutton (SO1)

� Mechanical operation counter

� Mechanical signalling device for circuit-breaker open/closed

� Emergency manual opening device

� Lever for manual emergency opening

� Lamp signalling “READY” for the operation (PRDY)

� Capacitors for storing energy for the operation

� Mobile connector for direct connection to the sockets of the electronic module, to cable the auxiliary circuits

� ED2.0 standard version control module

AB

B P

T /

16

VM1ED2.0 control module standard version

� Signalling contacts without potential, fitted with relay, with the following functions:� N°1 contact signalling circuit-breaker open (DO1)

� N°1 contact signalling circuit-breaker closed (DC1)

� N°1 contact signalling circuit-breaker ready for the operation (capacitors charged and check of circuit-breaker state) (DR) *

� N°1 contact signalling circuit-breaker not ready for the operation (DN, normally closed)

� N°1 transient contact with momentary closing during the opening operation (DOR)

Remark: with the circuit-breaker not supplied (without auxiliary power supply) these contacts are open, except the contact signalling circuit-breaker not ready for the operation (DN).

* Not available in withdrawable version

AB

B P

T /

17

VM1ED2.0 control module standard version

� 2 feeder power supply:�Type 1: 24 ... 48 V AC / 24 ... 60 V DC �Type 2: 100 ... 240 V AC / 110 ... 250 V DC

� Binary inputs (logical inputs) for remote control:�N°1 input for closing control (-SC2)�N°1 input for opening control (-SO2)�N°1 input for additional opening control (-SO3)�N°1 input for circuit-breaker opening on direct command from the

protection release PR512 (-SO5)�N°1 input for lock on closing control (the same function of the locking

electromagnet in the mechanical actuator of the VD4 circuit-breaker) (-SL1)

� Binary inputs:�24 ... 240 V AC (– 15% ... + 10%)�24 ... 250 V DC (– 30% ... + 10%)(minimum duration of the impulse is 20 ms)

AB

B P

T /

18

VM1ED2.0 control module standard version

� Functions:

� Self-opening following determination of incorrect state of circuit-breaker

� Self-opening following load threshold of the capacitors lower than the minimum value required for the opening and closing operation

� Anti-pumping relay function

� Trip-free function

� Monitoring of capacitor load with feeder turning itself off in the case of exceeding the maximum load level

(these functions can be disabled by means of dip-switches)

AB

B P

T /

19

VM1ED2.0 control module full option version (on request)

� Signalling contacts without potential, fitted with relay, with the following functions:

� N°2 contacts signalling circuit-breaker open (DO1, DO2)

� N°2 contacts signalling circuit-breaker closed (DC1, DC2)� N°1 contact signalling circuit-breaker ready for the operation (capacitors

charged and check of circuit-breaker state) (DR)

� N°1 contact signalling circuit-breaker not ready for the operation (DN, normally closed)

� N°1 transient contact with momentary closing during the opening operation (DOR)

Remark: difference respect to ED2.0 control module basic version

AB

B P

T /

20

VM1ED2.0 control module full option version (on request)� Binary inputs (logical inputs) for remote control:

� N°1 input for closing control (-SC2)

� N°1 input for opening control (-SO2)

� N°1input for additional opening control (-SO3)

� N°1 input for circuit-breaker opening on direct command from the protection release PR512 (-SO5)

� N°1 input for lock on closing control (the same function of the locking electromagnet in the mechanical actuator of the VD4 circuit-breaker) (-SL1)

� N°1 input as undervoltage control for (-S04)

Remark: difference respect to ED2.0 control module basic version

AB

B P

T /

21

VM1ED2.0 control module full option version (on request)� Functions:

� Self-opening following determination of incorrect state of circuit-breaker� Self-opening following load threshold of the capacitors lower than the minimum

value required for the opening and closing operation� Anti-pumping relay function� Trip-free function� Monitoring of capacitor load with feeder turning itself off in the case of exceeding

the maximum load level� Undervoltage function with selection of the reference rated voltage and with

possibility of delaying the opening from 0 to 5 s (-SO4)� Watchdog of the electronic power circuit with feeder turning itself off in the case of

overtemperature and/or overcurrent� Slow capacitor charging function (the power load passes from 100 watt to 40

watt, doubling the charging time)� Monitoring continuity of the opening and closing coils� Watchdog (DN)� Additional safety opening command function

Remark: difference respect to ED2.0 control module basic version

AB

B P

T /

22

VM1Accessories available (on request)� Signalling auxiliary contacts circuit-breaker open/closed

�Fixed circuit-breaker (-BB1; -BB2; -BB3; -BB8):�Set of 5 make contacts plus 5 break contacts�Set of 10 make contacts plus 10 break contacts (alternatively)

�Withdrawable circuit-breaker (-BB1; -BB2)�Set of 5 break contacts plus 5 make contacts

� Transmitted contacts of the withdrawable circuit-breaker installed in the truck (-BT1; -BT2)These contacts are either in addition or as an alternative to the position contacts (for signalling circuit-breaker racked out) located in the unit; they also carry out thefunction of the position contact (-BT3)

� Position contact of the withdrawable circuit-breaker (-BT3)With binary input SL1 prevents remote CB closing during translation of the truck; it is supplied when the transmitted contacts -BT1; -BT2 are not required

� Motorised truck (-MT) (only for VM1 for UniGear panel)

AB

B P

T /

23

VM1Features of the control module ED2.0 (standard version)� The closing coil can only be activated when VM1 is open� The opening coil can only be activated when VM1 is closed� Closing is disabled when an opening command is active at the same time� De-activation of the opening or closing coil takes place when the relative limit position

has been reached� WRONG POSITION (auto trip) function: if the final CLOSED (or OPEN) position is

not reached within 70 ms during a closing (or opening) operation, an opening operation is immediately started to guarantee reaching a defined safe position in any case.

� Anti-pumping function ensures that only one closing-opening cycle is carried out when a closing command followed by an opening command is active; active closing command must be cancelled and reset for the next closing operation.

� Activation of the input for the closing command can be locked by means of an external locking signal.

� Input for the “lock on closing” command must be energised to be able to close the circuit-breaker (without power it inhibits closing).

AB

B P

T /

24

VM1Features of the control module ED2.0 full version� Undervoltage function

� controls VM1 opening if the voltage applied drops below the limit of tolerance (established by the Standards)

� rated voltage value to be monitored is set in the factory in conformity with the order specifications but it can be changed by dip-switches

� to prevent UVR intervention, when the voltage drops below the specified level (e.g. in the case of motor starting), it is possible to set a trip time

� UVR function can be disabled� Monitoring function of the actuator closing and opening coil; if a fault is

detected, the luminous “READY” signal on front of the circuit-breaker turns off and the “READY/NOT READY” signalling contacts are activated.

� Additional safety opening command function; the second input of the control module for the opening function is designed so that an opening command is carried out directly even in the case of a fault in the microprocessor.

AB

B P

T /

25

VM1

Features of the capacitor� The energy stored is suitable for an O-C-O operating cycle without recharging� The energy stored is constantly monitored by measuring the voltage of the capacitor� “READY” indication signals:

� application of the power supply voltage� “ready” status of VM1 for the next operation

� “READY” signal switched on means� (VM1 in the open position) energy sufficient for one C-O operating cycle� (VM1 in the closed position) energy sufficient for one opening operation; energy available

is sufficient for one opening operation within 60 s from interruption of the auxiliary power supply (up to 120 s with 2 capacitors)

AB

B P

T /

26

VM1

Lifetime t of aluminium electrolytic capacitors as a function of the ambient temperature T

y

AB

B P

T /

27

VM1

Switching energy for CO VM1: 150 JVD4: 115 J

Capacitor voltage 80 VClosing cycle

VM1 max. 100 Jwithout capacitor max. 2.3 kW for 54 ms

Making current max. 29 A for 44 msBreaking capacity

with capacitor max. 50 Jwithout capacitor max. 2.1 kW for 27 ms

Breaking current max. 27 A for 30 msOpening time 35 ... 45 msArcing time 10 ...15 msTotal interruption time 45 ... 60 msClosing time 50 ... 60 ms

Characteristic data