VM1: innovationin power technologyArgentina Buenos Aires
November 30, 2006
Die Summe von Vorteilen
� Keine Wartung
� Wenige Einzelteile
� Einfache mechanische Abläufe
� Sehr hohe Zuverlässigkeit
� Hoher Qualitätsstandard
� Sehr hohe Lebensdauer
VM1 Innovation in medium voltage technologyVacuum circuit-breaker with magnetic actuator
Main Characteristics• Maintenance-free• Extremely high number of operating cycles• Electronic controller with sensor technology • Vacuum interrupters embedded in epoxy resin• High quality standard• Compatible with conventional circuit-breakers• For universal applications worldwide
AB
B P
T /
3
VM1
VM1Rated voltage kV 12 17.5 24
Rated current A ...2500 ...2500 ...2500
Rated short-circuit kA ...31.5 ...31.5 ...25breaking current
AB
B P
T /
4
VM1
“new“ VD4 “new look“ VM1
�Common look and feel� the same common look and feel according to PT Guidelines for Product
Design
AB
B P
T /
5
VM1
“new look“ VM1“new“ VD4
� “new“ VD4 and “new look“ VM1 have common frame suitable forinterchangeable plug-in actuators
AB
B P
T /
6
VM1
Emergency manual breaking mechanism
Electronic controller
Magnetic actuator
Electrical energy store
Sensors for switching position detection
AB
B P
T /
8
VM1
Main characteristics� Electronic maintenance-free
� Controller with sensor technology
� Magnetic actuator with extremely high number of operating cycles� up to 100,000 operating cycles for breaking capacity up to 25 kA and rated current up
to 1250 A
� up to 50,000 operating cycles with rated current > 1600 A and/or breaking capacity > 31.5 kA
� Embedding technology to protect vacuum interrupters
� High quality standard
� External dimensions compatible with VD4
� Developed for universal applications worldwide
AB
B P
T /
10
VM1
-SO4 Undervoltage opening (only withED2.0 Full Option)
-SL1 Contact locking the CB closing-SO3 Auxiliary and safety open (2^
open command from remote)-SO2 Open command from remote
-SC2 Close command from remote
DO7 CB Remote Open
DO6 Unit Not Ready
DO5 Unit Ready
DO2 CB closed
DO1 CB open
24 .. 48V AC / 24 .. 60 V DC100 .. 240V AC / 110 .. 250 V DC
Auxiliary voltage supply
AB
B P
T /
13
VM1Representation of magnetic flux density distribution
Magnetic latching in end-of-runposition
Armature position: 0 mmAmpere-turns: 0 A
Magnetic latching and action of the magnetic field of a coil
Armature position: 0 mmAmpere-turns: 12500 A
Moving armature in opposingposition and magnetic end-of-runlatching
Armature position: 20 mmAmpere-turns: 5000 A
AB
B P
T /
14
VM1
Reduction of the magnetic flux density of Koerdym 280 as a function of the lifetime t at an ambient temperature of 120°C
y
AB
B P
T /
15
VM1Basic version
� Closing pushbutton (SC1)
� Opening pushbutton (SO1)
� Mechanical operation counter
� Mechanical signalling device for circuit-breaker open/closed
� Emergency manual opening device
� Lever for manual emergency opening
� Lamp signalling “READY” for the operation (PRDY)
� Capacitors for storing energy for the operation
� Mobile connector for direct connection to the sockets of the electronic module, to cable the auxiliary circuits
� ED2.0 standard version control module
AB
B P
T /
16
VM1ED2.0 control module standard version
� Signalling contacts without potential, fitted with relay, with the following functions:� N°1 contact signalling circuit-breaker open (DO1)
� N°1 contact signalling circuit-breaker closed (DC1)
� N°1 contact signalling circuit-breaker ready for the operation (capacitors charged and check of circuit-breaker state) (DR) *
� N°1 contact signalling circuit-breaker not ready for the operation (DN, normally closed)
� N°1 transient contact with momentary closing during the opening operation (DOR)
Remark: with the circuit-breaker not supplied (without auxiliary power supply) these contacts are open, except the contact signalling circuit-breaker not ready for the operation (DN).
* Not available in withdrawable version
AB
B P
T /
17
VM1ED2.0 control module standard version
� 2 feeder power supply:�Type 1: 24 ... 48 V AC / 24 ... 60 V DC �Type 2: 100 ... 240 V AC / 110 ... 250 V DC
� Binary inputs (logical inputs) for remote control:�N°1 input for closing control (-SC2)�N°1 input for opening control (-SO2)�N°1 input for additional opening control (-SO3)�N°1 input for circuit-breaker opening on direct command from the
protection release PR512 (-SO5)�N°1 input for lock on closing control (the same function of the locking
electromagnet in the mechanical actuator of the VD4 circuit-breaker) (-SL1)
� Binary inputs:�24 ... 240 V AC (– 15% ... + 10%)�24 ... 250 V DC (– 30% ... + 10%)(minimum duration of the impulse is 20 ms)
AB
B P
T /
18
VM1ED2.0 control module standard version
� Functions:
� Self-opening following determination of incorrect state of circuit-breaker
� Self-opening following load threshold of the capacitors lower than the minimum value required for the opening and closing operation
� Anti-pumping relay function
� Trip-free function
� Monitoring of capacitor load with feeder turning itself off in the case of exceeding the maximum load level
(these functions can be disabled by means of dip-switches)
AB
B P
T /
19
VM1ED2.0 control module full option version (on request)
� Signalling contacts without potential, fitted with relay, with the following functions:
� N°2 contacts signalling circuit-breaker open (DO1, DO2)
� N°2 contacts signalling circuit-breaker closed (DC1, DC2)� N°1 contact signalling circuit-breaker ready for the operation (capacitors
charged and check of circuit-breaker state) (DR)
� N°1 contact signalling circuit-breaker not ready for the operation (DN, normally closed)
� N°1 transient contact with momentary closing during the opening operation (DOR)
Remark: difference respect to ED2.0 control module basic version
AB
B P
T /
20
VM1ED2.0 control module full option version (on request)� Binary inputs (logical inputs) for remote control:
� N°1 input for closing control (-SC2)
� N°1 input for opening control (-SO2)
� N°1input for additional opening control (-SO3)
� N°1 input for circuit-breaker opening on direct command from the protection release PR512 (-SO5)
� N°1 input for lock on closing control (the same function of the locking electromagnet in the mechanical actuator of the VD4 circuit-breaker) (-SL1)
� N°1 input as undervoltage control for (-S04)
Remark: difference respect to ED2.0 control module basic version
AB
B P
T /
21
VM1ED2.0 control module full option version (on request)� Functions:
� Self-opening following determination of incorrect state of circuit-breaker� Self-opening following load threshold of the capacitors lower than the minimum
value required for the opening and closing operation� Anti-pumping relay function� Trip-free function� Monitoring of capacitor load with feeder turning itself off in the case of exceeding
the maximum load level� Undervoltage function with selection of the reference rated voltage and with
possibility of delaying the opening from 0 to 5 s (-SO4)� Watchdog of the electronic power circuit with feeder turning itself off in the case of
overtemperature and/or overcurrent� Slow capacitor charging function (the power load passes from 100 watt to 40
watt, doubling the charging time)� Monitoring continuity of the opening and closing coils� Watchdog (DN)� Additional safety opening command function
Remark: difference respect to ED2.0 control module basic version
AB
B P
T /
22
VM1Accessories available (on request)� Signalling auxiliary contacts circuit-breaker open/closed
�Fixed circuit-breaker (-BB1; -BB2; -BB3; -BB8):�Set of 5 make contacts plus 5 break contacts�Set of 10 make contacts plus 10 break contacts (alternatively)
�Withdrawable circuit-breaker (-BB1; -BB2)�Set of 5 break contacts plus 5 make contacts
� Transmitted contacts of the withdrawable circuit-breaker installed in the truck (-BT1; -BT2)These contacts are either in addition or as an alternative to the position contacts (for signalling circuit-breaker racked out) located in the unit; they also carry out thefunction of the position contact (-BT3)
� Position contact of the withdrawable circuit-breaker (-BT3)With binary input SL1 prevents remote CB closing during translation of the truck; it is supplied when the transmitted contacts -BT1; -BT2 are not required
� Motorised truck (-MT) (only for VM1 for UniGear panel)
AB
B P
T /
23
VM1Features of the control module ED2.0 (standard version)� The closing coil can only be activated when VM1 is open� The opening coil can only be activated when VM1 is closed� Closing is disabled when an opening command is active at the same time� De-activation of the opening or closing coil takes place when the relative limit position
has been reached� WRONG POSITION (auto trip) function: if the final CLOSED (or OPEN) position is
not reached within 70 ms during a closing (or opening) operation, an opening operation is immediately started to guarantee reaching a defined safe position in any case.
� Anti-pumping function ensures that only one closing-opening cycle is carried out when a closing command followed by an opening command is active; active closing command must be cancelled and reset for the next closing operation.
� Activation of the input for the closing command can be locked by means of an external locking signal.
� Input for the “lock on closing” command must be energised to be able to close the circuit-breaker (without power it inhibits closing).
AB
B P
T /
24
VM1Features of the control module ED2.0 full version� Undervoltage function
� controls VM1 opening if the voltage applied drops below the limit of tolerance (established by the Standards)
� rated voltage value to be monitored is set in the factory in conformity with the order specifications but it can be changed by dip-switches
� to prevent UVR intervention, when the voltage drops below the specified level (e.g. in the case of motor starting), it is possible to set a trip time
� UVR function can be disabled� Monitoring function of the actuator closing and opening coil; if a fault is
detected, the luminous “READY” signal on front of the circuit-breaker turns off and the “READY/NOT READY” signalling contacts are activated.
� Additional safety opening command function; the second input of the control module for the opening function is designed so that an opening command is carried out directly even in the case of a fault in the microprocessor.
AB
B P
T /
25
VM1
Features of the capacitor� The energy stored is suitable for an O-C-O operating cycle without recharging� The energy stored is constantly monitored by measuring the voltage of the capacitor� “READY” indication signals:
� application of the power supply voltage� “ready” status of VM1 for the next operation
� “READY” signal switched on means� (VM1 in the open position) energy sufficient for one C-O operating cycle� (VM1 in the closed position) energy sufficient for one opening operation; energy available
is sufficient for one opening operation within 60 s from interruption of the auxiliary power supply (up to 120 s with 2 capacitors)
AB
B P
T /
26
VM1
Lifetime t of aluminium electrolytic capacitors as a function of the ambient temperature T
y
AB
B P
T /
27
VM1
Switching energy for CO VM1: 150 JVD4: 115 J
Capacitor voltage 80 VClosing cycle
VM1 max. 100 Jwithout capacitor max. 2.3 kW for 54 ms
Making current max. 29 A for 44 msBreaking capacity
with capacitor max. 50 Jwithout capacitor max. 2.1 kW for 27 ms
Breaking current max. 27 A for 30 msOpening time 35 ... 45 msArcing time 10 ...15 msTotal interruption time 45 ... 60 msClosing time 50 ... 60 ms
Characteristic data