nur für internen Gebrauch, © by Siemens AG, IC LMV MV1 IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 1 / 51 - IC LMV MV1 Design catalogue NXAIR NXAIR switchgear, IEC 62271-200, SION circuit breaker, <=17,5 kV, <=40 kA, busbar <=4000 A, feeder <=4000 A, Loss of service continuity category: LSC 2B Partition class: PM Internal arc classification: IAC A FLR <= 40 kA, 1s Author / Originator Department Telephone Version Date Herbert Soens IC LMV MV1 PPM +49 9131 7 33776 01 - 19 17.06.2010 – 21.06.2011 20 19.07.2011 21 01.08.2011 22 04.08.2011 23 12.09.2011 24 24.10.2011 Draft Release X Paper Released by: Name Function Department Date Signature Thomas Lange R&D IC LMV MV1 R&D Tahsin Karadeniz R&D IC LMV MV1 R&D TUR

Transcript of NXAIR Design catalogue.pdf

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 1 / 51 -

    IC LMV MV1

    Design catalogue NXAIR

    NXAIR switchgear, IEC 62271-200, SION circuit breaker,

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 2 / 51 -

    Distribution list: Name Function Department Date Signature

    IC LMV MV1 S

    IC LMV MV1 CoC

    IC LMV MV 1 HUB Gebze

    IC LMV MV1 R&D SWF

    IC LMV MV1 R&D Gebze

    IC LMV MV1 POR

    Continuous Recording of Changes In this overview, enter changes as against the released / distributed documents only !!!

    Revised chapters / pages

    New issue

    Object and reason for change / Reference to change requests

    00 -19 Revisions see version 21.06.2011

    20 Optical arc detection system released, IP50/51 for package 2 released, package 2 with absorbers released, Rucksack package 2 released, motor mechanism for all withdrawable parts, feeder and busbar earthing released (exeption contactor panel), seismic version released, separate panel for ct in running busbar for

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 3 / 51 -

    Content page 1 Switchgear specification 4 1.1 Technical data 4 1.2 Busbars 5 1.3 Design options 5 1.4 Processing 6 1.5 Rated supply voltages 7 2 Panel specification 8 2.1 Components in basic versions 8 2.1.1. Switching device panel panel 8 2.1.1.1 Circuit breaker panel 8 2.1.1.2 Contactor panel 9 2.1.1.3 Metering panel 9 2.1.1.4 Busbar current metering panel 9 2.1.1.5 Bus sectionalizer 10 2.1.1.5.1 Bus sectionalizer type 1 11 2.1.1.5.2 Bus sectionalizer type 2 11 2.1.1.6 Busbar connecting panel 12 2.2 Configuration of panels 13 2.2.1 Panel types 13 2.2.2 Design options 13 2.2.3 Components 14 3 Accessories 20 4 Additional tables 21

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 4 / 51 -

    1 Switchgear specification Technical data Standard IEC 62271-

    200

    GOST 1) IEC 62271-

    200

    GOST 1) IEC 62271-

    200

    Rated voltage Ur 7.2 kV 12 kV 17.5

    Rated lightning impulse withstand voltage Up

    (phase/phase, phase/earth, open contact gap)

    60 kV 60 kV 75 kV 75 kV 95

    Rated lightning impulse withstand voltage Up 2)

    (disconnecting distance)

    70 kV 70 kV 85 kV 85 kV 110

    Rated short time power frequency withstand voltage Ud

    (phase/phase, phase/earth, open contact gap)

    20 kV 32 kV 28 kV 42 kV 38

    Rated short time power frequency withstand voltage Ud 2)

    (disconnecting distance)

    23 kV 36 kV 32 kV 48 kV 45

    3.3 kV 6.0 kV 13.8 kV

    3.6 kV 6.6 kV 15 kV

    4.8 kV 7.2 kV 16

    5.0 kV 10.0 kV

    6.0 kV 11.0 kV

    6.6 kV

    Operating voltage UN

    7.2 kV

    50 Hz 50 Hz 50 Hz Rated frequency fr

    60 Hz 60 Hz 60 Hz

    Rated short-time withstand current Ik

    25kA 31.5 kA 40 kA 25 kA 31.5kA 40 kA 25 kA 31.5kA 40 kA

    Rated peak withstand current Ip for 50 Hz

    63kA 80 kA 100 kA 63 kA 80kA 100 kA 63 kA 80kA 100 kA

    Rated peak withstand current Ip for 60 Hz

    65kA 82 kA 104 kA 65kA 82 kA 104 kA 65kA 82 kA 104 kA

    1 s Rated short-circuit duration tk

    3 s

    30 C

    35 C

    40 C

    45 C

    50 C

    Ambient temperature 3)

    55 C

    IAC A FLR, 1 s (standard version)

    IAC A FLR, 1 s (standard version), additionally pressure switches for all three compartments without testing device

    IAC A FLR, 1 s (standard version), additionally pressure switches for all three compartments with testing device

    Resistance to internal arc faults 4)

    IAC A FLR, 1 s (standard version), additionally optical system for all three compartments (low voltage devices to be calculated in sedis)

    Confinement of internal arc within compartments (pressure tied partitions)

    Standard, for 40 kA only up to 100 ms (with pressure switches or optical arc detection system)

    Pressure relief duct to release gases outside switchgear room

    Optionally with 5)

    IP 3X D

    IP 4X

    IP 50 6)

    Degree of protection

    IP 51 6)

    1.1

    See level (m)

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 5 / 51 -

    Busbars 1250 A, (1 x 100 mm x 10 mm, copper) 3150 A, (3 x 120mm x 10 mm, copper)

    2500 A, (2 x 100 mm x 10 mm, copper) 4000 A, (3 x 120 mm x 10 mm, copper)

    Busbar insulation Optionally with

    1.2

    Busbar transverse partition Optionally with (Standard for 40 kA panels or panels with busbar current >= 3150 A)

    Design options Rated

    voltage (kV)

    IAC classifi-cation

    Arc fault level (kA)

    Arc fault duration (s)

    Height of switchgear room (mm)

    Pressure relief system 2)

    >= 2500 / < 2800 duct to outside

    = 2800 absorbers

    >= 2500 / < 3000 duct to outside

    31.5 1 or 0,1

    >= 3000 absorbers

    >= 2500 / < 3500 duct to outside

    = 3500 absorbers

    >= 2500 / < 3500 duct to outside

    = 3500 absorbers

    31.5 1 or 0,1 >= 2500 / < 3500 duct to outside

    >= 3500 absorbers

    >= 2500 / < 3500 duct to outside

    Pressure relief channel system 1)

    17.5 IAC A FLR

    40 1 or 0,1

    >= 3500 absorbers

    Busbar system Single

    Withdrawable part design Design version

    Truck type design 3)

    Freestanding with cable access from front or rear

    Freestanding with cable access from above and rear for 600/800/1000 mm panels up to 17.5 kV/31.5 kA/2500 A or 800/1000 mm panels up to 17.5 kV/40 kA/

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 6 / 51 -

    630 mm (Standard) Height of low voltage compartment

    980 mm

    Transverse partition in low voltage compartment

    Standard

    Lightning in low voltage compartment Optionally with

    Optionally english

    Optionally german

    Language for labels and operating instructions

    Optionally spanish

    Pressure resistant floor cover in cable compartment

    Standard

    Anticondensation heater in switching device compartment, 100 W

    Optionally with

    Anticondensation heater in cable compartment, 100 W

    Optionally with

    Anticondensation heater in low voltage compartment, 20 W

    Optionally with

    Standard:

    Steel parts zinc-plated, high voltage and low voltage door at front and end walls powder coated RAL 7035

    Or all sheet metal parts powder coated in RAL 7035 (depending on manufacturing location)

    Optionally powder coating of rear wall in standard colour RAL 7035

    Optionally with special colour instead of standard colour for high voltage and low voltage door at front and end walls

    Surface treatment enclosure, partitions

    Optionally powder coating of rear wall in special colour

    Seismic withstand capability Optionally with 1)

    Separate earthing bar between withdrawable part and earthing bar in cable compartment

    With

    Additional earthing wire between high voltage door and enclosure

    Standard

    Additional earthing wire between low voltage door and enclosure

    Standard

    Surface treatment of primary contacts Silver plated (Standard)

    Surface treatment of busbar and earthing bar Optionally silver plated

    Standard Surface treatment of components in primary part

    Optionally silicon free

    Standard

    Optionally halogen free

    Secondary wiring and channels

    Optionally silicon free

    Processing Panels complete Scope of order

    Panels complete with low voltage compartment as advance delivery

    Transport units Single panels

    Packing for truck on road or rail

    Packing for airfreight

    Packing for sea freight, transport and storage period up to 6 months

    Packing

    Packing for sea freight, transport and storage period up to 12 months

    Visual inspection

    Complete routine test per panel in acc. to IEC 62271-200

    Complete routine test per typical in acc. to IEC 62271-200

    Visual inspection and mechanical function test per typical

    1.4

    Acceptance test

    Without

    1) special marking-spreading tool for drive-in anchors to fix panel to bottom and drilling jig needed, see chapter accessories

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 7 / 51 -

    Rated supply voltages DC 24 V DC 120 V AC 100 V 1)

    DC 30 V DC 125 V AC 110 V 1)

    DC 32 V DC 127 V AC 120 V 1)

    DC 48 V DC 220 V AC 125 V 1)

    DC 60 V DC 240 V AC 230 V 1)

    Auxiliary voltage

    DC 110 V AC 240 V 1)

    DC 24 V DC 120 V AC 100 V 1)

    DC 30 V DC 125 V AC 110 V 1)

    DC 32 V DC 127 V AC 120 V 1)

    DC 48 V DC 220 V AC 125 V 1)

    DC 60 V DC 240 V AC 230 V 1)

    Circuit breaker motor voltage

    DC 110 V AC 240 V 1)

    DC 110 V AC 100 V 1)

    DC 125 V AC 110 V 1)

    DC 220 V AC 115 V 1)

    AC 120 V 1)

    AC 230 V 1)

    Operating voltage for closing solenoid and closing latch of contactor 3TL6

    AC 240 V 1)

    DC 110 V AC 100 V 1)

    DC 125 V AC 110 V 1)

    DC 220 V AC 115 V 1)

    AC 120 V 1)

    AC 230 V 1)

    Operating voltage for releasing mechanical closing latching 3TL6

    AC 240 V 1)

    DC 24 V DC 120 V AC 100 V 1)

    DC 30 V DC 125 V AC 110 V 1)

    DC 32 V DC 127 V AC 120 V 1)

    DC 48 V DC 220 V AC 125 V 1)

    DC 60 V DC 240 V AC 230 V 1

    First shunt trip voltage of SION

    DC 110 V AC 240 V 1)

    DC 24 V DC 120 V AC 100 V 1)

    DC 30 V DC 125 V AC 110 V 1)

    DC 32 V DC 127 V AC 120 V 1)

    DC 48 V DC 220 V AC 125 V 1)

    DC 60 V DC 240 V AC 230 V 1)

    Second shunt trip voltage of SION

    DC 110 V AC 240 V 1)

    DC 24 V DC 48 V DC 60 V

    DC 110 V

    Motor mechanism withdrawable part, feeder and busbar earthing

    AC 110 V AC 230 V

    DC 24 V DC 125 V

    DC 48 V DC 220 V

    DC 60 V DC 240 V

    Interlocking supply (electromagnetic interlock of withdrawable part / truck and earthing switch

    DC 110 V

    AC 220 240 V

    1.5

    Heater supply voltage

    AC 110 V

    1) for 50 and 60 Hz

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 8 / 51 -

    2 Panel specification 2.1 Components 2.1.1 Switching device panel

    2.1.1.1 Circuit breaker panel Panel width (mm) Compartment Design resp. devices

    bare copper optionally insulated copper optionally with top box for voltage transformers optionally with busbar earthing switch hand operated optionally with top box for make proof earthing switch motor operated bushing type insulators between breaker and busbar

    busbar

    optionally capacitive voltage indication withdrawable circuit breaker, hand operated switching

    device optionally withdrawable circuit breaker, motor operated cables bushing type insulators and optionally block type current transformers bushing type insulators and optionally extended block type current transformers 2) up to 17.5 kV / 31.5 kA / 2500 A possible

    optionally fixed mounted voltage transformers optionally make proof earthing switch hand operated optionally make proof earthing switch motor operated optionally surge arrestors or limiters optionally capacitive voltage indication

    600 1)

    connection

    optionally devices for zero sequence transformers

    Panel width (mm) compartment bare copper optionally insulated copper optionally with top box for make proof earthing switch hand operated optionally with top box for make proof earthing switch motor operated optionally with top box for voltage transformers bushing type insulator between breaker and busbar optionally with top box for bar or cable connection

    busbar

    optionally capacitive voltage indication optionally withdrawable circuit breaker, hand operated optionally withdrawable circuit breaker, motor operated optionally withdrawable disconnetor link, hand operated

    switching device

    closed panel, without slots cables or optionally bar connection bushing type insulators and optionally block type current transformers bushing type insulators and optionally extended block type current transformers up to 17.5 kV / 31.5 kA / 2500 A possible 2) or up to 17.5 kV/40 kA/

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 9 / 51 -

    2.1.1.1 Circuit breaker panel

    Panel width (mm) compartment Design resp. devices bare copper optionally insulated copper bushing type insulator between breaker and busbar

    busbar

    optionally capacitive voltage indication optionally withdrawable circuit breaker, hand operated optionally withdrawable circuit breaker, motor operated optionally withdrawable disconnetor link, hand operated natural ventilated panel forced ventilated, current relais controlled

    switching device

    forced ventilated, current relais controlled and redundant version cables or optionally bar connection bushing type insulators and optionally block type current transformers bushing type insulators and optionally extended block type current transformers up to 17.5 kV / 31.5 kA / 2500 A possible 1) or up to 17.5 kV/40 kA/

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 10 / 51 -

    2.1.1.5 Bus sectionalizer can be designed as:

    Type I consisting of: Typ II consisting of:

    circuit breaker bus riser panel with disconnector

    circuit breaker bus riser panel, optionally with metering

    rated current 1) (A)

    width of panel (mm)

    rated current 1) (A)

    width of panel (mm)

    rated current 1) (A)

    width of panel (mm)

    rated current 1) (A)

    width of panel (mm)

    1250 800 1250 800 1250 800 1250 800

    2000 1) 800 2000 1) 800 2000 1) 800 2000 1) 800

    2500 1000 2500 1000 2500 1000 2500 800

    3150 1000 3150 1000 3150 1000 3150 1000

    4000 1000 4000 1000 4000 1000 4000 1000

    2.1.1.5.1 Bus sectionalizer type I, 1250 A / 2000 A 1) (mirror-image installation possible)

    Circuit breaker panel, 1250 A / 2000 A 1) Panel width (mm) Compartment Design resp. devices

    bare copper optionally insulated copper optionally with top box for make proof earthing switch hand operated optionally with top box for make proof earthing switch motor operated optionally with top box for voltage transformers bushing type insulators between breaker and busbar optionally with top box for bar or cable connection

    busbar

    optionally capacitive voltage indication optionally withdrawable circuit breaker, hand operated switching

    device optionally withdrawable circuit breaker, motor operated bar connection to bus riser panel bushing type insulators and optionally block type current transformers optionally fixed mounted voltage transformers

    800

    connection

    optionally capacitive voltage indication option

    Bus riser panel with disconnecting module, 1250 A / 2000 A 1)

    Panel width (mm) Compartment Design resp. devices bare copper optionally insulated copper optionally with top box for make proof earthing switch hand operated optionally with top box for make proof earthing switch motor operated optionally with top box for voltage transformers bushing type insulators between breaker and busbar optionally with top box for bar or cable connection

    busbar

    optionally capacitive voltage indication optionally switching device

    withdrawable disconnetor link, hand operated

    bar connection to bus circuit breaker panel bushing type insulators and optionally block type current transformers optionally fixed mounted voltage transformers

    800

    connection

    optionally capacitive voltage indication

    detailed configuration in NX-Tools+

    1) rated current, see also tables in chapter 4.10, 2000 A version only in 40 kA possible

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 11 / 51 -

    2.1.1.5.1 Bus sectionalizer type I, 2500 A, 3150 A, 4000 A, (mirror-image installation possible)

    Circuit breaker panel, 2500 A, 3150 A, 4000 A Panel width (mm) Compartment Design resp. devices

    bare copper optionally insulated copper bushing type insulators between breaker and busbar

    busbar

    optionally capacitive voltage indication optionally withdrawable circuit breaker, hand operated optionally withdrawable circuit breaker, motor operated natural ventilated forced ventilated, current relais controlled

    switching device

    forced ventilated, current relais controlled and redundant version bar connection to bus riser panel bushing type insulators and optionally block type current transformers optionally fixed mounted voltage transformers

    1000

    connection

    optionally capacitive voltage indication option

    Bus riser panel with disconnecting module, 2500 A, 3150 A, 4000 A

    Panel width (mm) Compartment Design resp. devices bare copper optionally insulated copper bushing type insulators between breaker and busbar

    busbar

    optionally capacitive voltage indication optionally withdrawable disconnetor link, hand operated natural ventilated 1) forced ventilated 1), current relais controlled

    switching device

    forced ventilated 1), current relais controlled and redundant version bar connection to bus circuit breaker panel bushing type insulators and optionally block type current transformers optionally fixed mounted voltage transformers

    1000

    connection

    optionally capacitive voltage indication

    detailed configuration in NX-Tools+

    2.1.1.5.2 Bus sectionalizer type II, 1250 A / 2000 A 2) (mirror-image installation possible)

    Circuit breaker panel, 1250 A / 2000 A 2) Panel width (mm) Compartment Design resp. devices

    bare copper optionally insulated copper optionally with top box for make proof earthing switch hand operated optionally with top box for make proof earthing switch motor operated optionally with top box for voltage transformers bushing type insulators between breaker and busbar optionally with top box for bar or cable connection

    busbar

    optionally capacitive voltage indication optionally withdrawable circuit breaker, hand operated switching

    device optionally withdrawable circuit breaker, motor operated bar connection to bus riser panel bushing type insulators and optionally block type current transformers optionally fixed mounted voltage transformers

    800

    connection

    optionally capacitive voltage indication

    Bus riser panel 1250 A / 2000 A 2), optionally with metering module Panel width (mm) Compartment Design resp. devices

    bare copper optionally insulated copper optionally with top box for bar or cable connection

    Busbar

    optionally capacitive voltage indication switching device

    optionally withdrawable part with voltage transformers and primary fuses, hand operated

    bar connection to circuit breaker panel bushing type insulators and optionally block type current transformers

    800

    Connection

    optionally fixed mounted voltage transformers

    detailed configuration in NX-Tools+

    1) 2500 A closed panel, 3150 A natural ventilated panel, 4000 A forced ventilated panel 2) 2000 A only for 40 kA possible

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 12 / 51 -

    2.1.1.5.2 Bus sectionalizer type II, 2500 A, 3150 A , 4000 A, (mirror-image installation possible)

    Circuit breaker panel, 2500 A, 3150 A, 4000 A Panel width (mm) Compartment Design resp. devices

    bare copper optionally insulated copper bushing type insulators between breaker and busbar

    busbar

    optionally capacitive voltage indication optionally withdrawable circuit breaker, hand operated optionally withdrawable circuit breaker, motor operated optionally ventilation slots forced ventilated, current relais controlled

    switching device

    forced ventilated, current relais controlled and redundant version bar connection to bus riser panel bushing type insulators and optionally block type current transformers optionally fixed mounted voltage transformers

    1000

    connection

    optionally capacitive voltage indication

    Bus riser panel 2500 A, 3150 A, 4000 A, optionally with metering module Panel width (mm) Compartment Design resp. devices

    bare copper optionally insulated copper optionally with top box for bar or cable connection

    busbar

    optionally capacitive voltage indication optionally withdrawable part with voltage transformers with primary fuses, hand operated

    switching device

    optionally ventilation slots for >= 3150 A bar connection to circuit breaker panel bushing type insulators and optionally block type current transformers

    800/1000

    connection

    optionally fixed mounted voltage transformers

    detailed configuration in NX-Tools+

    2.1.1.6 Busbar connecting panel (only in 800 mm panel width) Panel width (mm) Compartment Design resp. devices 800/1000 busbar bare copper

    optionally insulated copper optionally with top box for make proof earthing switch hand operated optionally with top box for make proof earthing switch motor operated optionally with top box for voltage transformers

    optionally with top box for bar or cable connection switching device

    optionally withdrawable part with voltage transformers and fuses, hand operated

    connection cable connection to bus riser panel optionally block type current transformers optionally fixed mounted voltage transformers

    optionally capacitive voltage indication

    detailed configuration in NX-Tools+

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 13 / 51 -

    2.2 Configuration of panels 2.2.1 Panel types

    busbar current 1) (A)

    feeder current 1) (A)

    basic ver-sion

    rated voltage (kV)

    panel type short circuit breaking current (kA)

    rated busbar current (A)

    rated current (A)

    rated breaker current (A)

    rated panel current (A)

    panel design

    width (mm)

    depth (mm)

    630 800 630 1000 1250 1000

    600

    1250

    1250 1250 1250

    closed

    800 630 800 630 1000 1250 1000

    600

    1250 1250 1250

    closed

    800

    2500

    2500 2500 2500 natural ventilated 1000

    1350 2)

    1250 1250 1250 closed 800 2500 2500 2500 natural ventilated 1000

    1500 3)

    3150

    3150 3150 3150 natural ventilated 1000 1540 4) 1250 1250 1250 closed 800 2500 2500 2500 natural ventilated 1000

    1500 3)

    3150 3150 3150 natural ventilated 1000

    25

    4000

    4000 3150 4000 forced ventilated 5) 1000 1540 4)

    630 800 630 1000 1250 1000

    600

    1250

    1250 1250 1250

    closed

    800 630 800 630 1000 1250 1000

    600

    1250 1250 1250

    closed

    800

    2500

    2500 2500 2500 natural ventilated 1000

    1350 2)

    1250 1250 1250 closed 800 2500 2500 2500 natural ventilated 1000

    1500 3)

    3150

    3150 3150 3150 natural ventilated 1000 1540 4) 1250 1250 1250 closed 800 2500 2500 2500 natural ventilated 1000

    1500 3)

    3150 3150 3150 natural ventilated 1000

    31.5

    4000

    4000 3150 4000 forced ventilated 5) 1000 1540 4)

    1250 1250 1250 1250 800 1250 1250 1250 800 2000 2500 2000

    closed

    800

    2500

    2500 2500 2500 natural ventilated 1000 1250 1250 1250 800 2000 2500 2000

    closed 800

    2500 2500 2500 natural ventilated 1000

    1500 3)

    3150

    3150 3150 3150 natural ventilated 1000 1540 4) 1250 1250 1250 800 2000 2500 2000

    closed 800

    2500 2500 2500 natural ventilated 1000

    1500 3)

    3150 3150 3150 natural ventilated 1000

    Switching device panel with circuit breaker or disconnecting link

    40

    4000

    4000 3150 4000 forced ventilated 5) 1000 1540 4)

    1250

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 14 / 51 -

    2.2.1 Panel types busbar current 1) (A)

    feeder current 1) (A)

    basic ver-sion

    rated voltage (kV)

    panel type short circuit breaking current (kA)

    Rated busbar current

    (A)

    Rated current (A)

    Rated breaker current (A)

    Rated panel current (A)

    panel design width

    (mm)

    depth

    (mm)

    1250 1250 1250 1250 closed 2x800 2500 2500 2500 2500 natural ventilated 2x1000

    1350

    3150 3150 3150 3150 natural ventilated 2x1000

    25

    4000 4000 3150 4000 forced ventilated 2) 2x1000 1540

    1250 1250 1250 1250 closed 2x800 2500 2500 2500 2500 natural ventilated 2x1000

    1350

    3150 3150 3150 3150 natural ventilated 2x1000

    31.5

    4000 4000 3150 4000 forced ventilated 2) 2x1000 1540

    1250 1250 1250 1250 closed 2x800 2500 2000 2500 2000 closed 2x800 2500 2500 2500 2500 natural ventilated 2x1000

    1500

    3150 3150 3150 3150 natural ventilated 2x1000

    Bus sectionalizer type I consisting of: switching device panel and bus riser panel with disconnector module

    40

    4000 4000 3150 4000 forced ventilated 2) 2x1000 1540

    1250 1250 1250 1250 closed 2x800 2500 2500 2500 2500 natural ventilated 1x1000+

    1x800

    1350

    3150 3150 3150 3150 natural ventilated 2x1000

    25

    4000 4000 3150 4000 forced ventilated 2) 2x1000

    1540

    1250 1250 1250 1250 closed 2x800

    2500 2500 2500 2500 natural ventilated 1x1000+1x800

    1350

    3150 3150 3150 3150 natural ventilated 2x1000

    31.5

    4000 4000 3150 4000 forced ventilated 2) 2x1000

    1540

    1250 1250 1250 1250 closed 2x800 2500 2000 2500 2000 closed 2x800

    2500 2500 2500 2500 natural ventilated 1x1000+1x800

    1500

    3150 3150 3150 3150 natural ventilated 2x1000

    Bus sectionalizer type II consisting of: switching device panel and bus riser panel optionally with metering module

    40

    4000 4000 3150 4000 forced ventilated 2) 2x1000

    1540

    1250 1250 - 1250 800 2500 2500 - 2500 800

    1350

    3150 3150 - 3150 1000

    25

    4000 4000 - 4000 1000 1540

    1250 1250 - 1250 800 2500 2500 - 2500 800

    1350

    3150 3150 - 3150 1000

    31.5

    4000 4000 - 4000 1000 1540

    1250 1250 - 1250 800 2500 2000 - 2000 800 2500 2500 - 2500 800

    1500

    3150 3150 - 3150 1000

    Busbar connecting panel

    40

    4000 4000 - 4000

    closed

    1000 1540

    1) permissible current values depending from ambient temperature values, degree of protection etc are included in chapter 4.10

    2) forced ventilation current relais controlled, optionally redundant version possible

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 15 / 51 -

    2.2.2 Design options Intermediate panel

    Left end panel

    Panel arrangement

    Right end panel

    left

    Door hinges for high voltage and low voltage door 1) right

    2.2.3 Components

    Capacitive voltage indicator at cable side at busbar side LRM (low resistant modified) VOIS Capdis S1+

    2.2.3.1 Capacitive voltage indicator

    Capdis S2+

    2.2.3.2 Panel connection cable compartment From bottom, front From bottom, rear

    Cable connection

    From above and rear 2) 1 single core cable max. 500 mm per phase 2 single core cable max. 500 mm per phase 3 single core cable max. 500 mm per phase 4 single core cable max. 500 mm per phase 6 single core cable max. 500 mm per phase for panel depth 1540 mm

    Number, type and size of cables

    up to 2 three core cable max. 240 mm 3) Deep bottom pan With

    With

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 16 / 51 -

    2.2.3.6 Block-type current transformers 4MA72 standard versi on for current values 2500 A, in connection compartment, drawing number 4MA72: 1250 A /

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 17 / 51 -

    2.2.3.8 Block-type current transformers CT 12 I only for panels up 17.5 kV, busbar current > = 3150 A, drawing number: 110-0314.9, panel depth 1500 resp. 1540 mm, in connection compartment or in busbar current metering panel installation one set at cable side, below breaker

    1 x 1 core in L2 2 x 1 core in L1/L3 + 1 x 2 cores in L2 2 x 1 core in L1/L3 2 x 2 core in L1/L3 + 1 x 1 cores in L2 3 x 1 core in L1/L2/L3 3 x 2 core in L1/L2/L3

    Number of cores

    2 x 2 core in L1/L3 16 kA / 1s 16 kA / 3s 20 kA / 1s 20 kA / 3s 25 kA / 1s 25 kA / 3s 31.5 kA / 1s 31.5 kA / 3s

    Rated short time current / Rated short circuit duration

    40 kA / 1s 40 kA / 3s Rated primary current (not reconectable on the secondary side)

    3150 A 4000 A

    2.5 VA 10 VA 20 VA Rated power 5 VA 15 VA 30 VA 0.2 FS10 5P 10 5P 30 0.2 SFS10 10P 10 0.5 FS5 5P 15

    Class

    1 FS5 5P 20 1 A 5 A / 1 A 1 A / 5 A / 5 A 5 A 1 A / 1 A / 1 A 5 A / 5 A / 1 A 1 A / 1 A 5 A / 5 A / 5 A 5 A / 1 A / 5 A 5 A / 5 A 1 A / 1 A / 5 A 5 A / 1 A / 1 A

    Rated secondary current

    1 A / 5 A 1 A / 5 A / 1 A with approval Current transformers silicon free Secondary wiring halogen free Short-duration power-frequency withstand voltage 32 kV 1 min. for 7.2 kV, Standard

    GOST Short-duration power-frequency withstand voltage 42 kV 1 min. for 12 kV, Standard GOST Language of name plate German / English

    Additional features

    Primary rated current 1.2 x In

    2.2.3.9 Block-type current transformers CT 12 K, extended ver sion only for panels up to 17.5 kV, busbar current >= 3150 A depth 1650 mm, in connection compartment installation one set at cable side, below breaker

    1 x 1 core in L2 2 x 1 core in L1/L3 3 x 1 core in L1/L2/L3 2 x 2 core in L1/L3 2 x 1 core in L1/L3 + 1 x 2 cores in L2 2 x 2 core in L1/L3 + 1 x 1 cores in L2

    Number of cores

    3 x 2 core in L1/L2/L3 16 kA / 1s 16 kA / 3s 20 kA / 1s 20 kA / 3s 25 kA / 1s 25 kA / 3s 31.5 kA / 1s 31.5 kA / 3s

    Rated short time current / Rated short circuit duration

    40 kA / 1s 40 kA / 3s Rated primary current (not reconectable on the secondary side)

    3150 A 4000 A

    2.5 VA 10 VA 20 VA Rated power 5 VA 15 VA 30 VA 0.2 FS10 5P 10 5P 30 0.2 SFS10 10P 10 0.5 FS5 5P 15

    Class

    1 FS5 5P 20 1 A 5 A / 1 A 1 A / 5 A / 5 A 5 A 1 A / 1 A / 1 A 5 A / 5 A / 1 A 1 A / 1 A 5 A / 5 A / 5 A 5 A / 1 A / 5 A 5 A / 5 A 1 A / 1 A / 5 A 5 A / 1 A / 1 A

    Rated secondary current

    1 A / 5 A 1 A / 5 A / 1 A with approval Current transformers silicon free Secondary wiring halogen free Short-duration power-frequency withstand voltage 32 kV 1 min. for 7.2 kV, Standard

    GOST Short-duration power-frequency withstand voltage 42 kV 1 min. for 12 kV, Standard GOST Language of name plate German / English

    Additional features

    Primary rated current 1.2 x In

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 18 / 51 -

    2.2.3.10 Block-type current transformers 4MB61 (size 2) f or contactor panel Installation at cable side

    3 x 1 core in L1/L2/L3 3 x 2 core in L1/L2/L3

    Rated short time current / Rated short circuit duration 1)

    up to 25 kA / 3s

    25 A 75 A 250 A 30 A 100 A 300 A 40 A 125 A 400 A 50 A 150 A

    Rated primary current

    60 A 200 A 5 VA 15 VA Rated power 10 VA 30 VA 5 VA 10P 10 30 VA 10P 10 15 VA 1 M5 10 VA 10P 10 5 VA 1 M5

    Class

    15 VA 10P 10 10 VA 1 M5 1 A 1 A / 1 A 1 A / 5 A 5 A 5 A / 5 A 5 A / 1 A with approval Current transformers silicon free Secondary wiring halogen free Short-duration power-frequency withstand voltage 32 kV 1 min. for 7.2 kV, Standard

    GOST Short-duration power-frequency withstand voltage 42 kV 1 min. for 12 kV, Standard GOST Language of name plate German / English

    Rated secondary current

    Primary rated current 1.2 x In

    2.2.3.9 Voltage transformers 4MR12 up to 17.5 kV, drawing number for 4MR12 without fuses: 110-0137.9

    3 x 1 pole 3 x 1 pole with earth fault winding

    3 x 1 pole with earth fault winding and damping resistor fix mounted without primary fuses, generally with encapsulated primary connection Installation on withdrawable part for busbar metering in metering panel 2),

    generally with fuses 7.2 kV, 6.3 A generally with fuses 12 kV, 6.3 A generally with fuses 17.5 kV, 6.3 A

    in separate compartment, withdrawable with fuses at feeder side 3), generally with fuses 7.2 kV, 6.3 A, generally with fuses 12 kV, 6.3 A generally with fuses 17.5 kV, 6.3 A

    without 100 / 3 V 110 / 3 V

    Earth fault winding

    120 / 3 V 3.3 / 3 kV 6.6 / 3 kV 13.8 / 3 kV 3.6 / 3 kV 7.2 / 3 kV 15 / 3 kV 4.8 / 3 kV 10.0 / 3 kV 17.5 / 3 kV 5.0 / 3 kV 11.0 / 3 kV

    Primary voltage single pole

    6.0 / 3 kV Rated secondary voltage 100 / 3 V 110 / 3 V 120 / 3 V Rated secondary voltage earth fault winding

    100 / 3 V 110 / 3 V 120 / 3 V

    Rating / Class 20 VA / 0.2 50 VA / 0.5 100 VA / 1 Voltage transformer silicon free Secondary wiring halogen free Short-duration power-frequency withstand voltage 32 kV 1 min. for 7.2 kV, Standards

    GOST Short-duration power-frequency withstand voltage 42 kV 1 min. for 12 kV, Standards

    GOST Language of name plate German / English With official certification With approval

    Additional features

    With integral casted primary connection

    1) due to current limiting function of fuses not relevant 2) additional ordering code F23 3) only possible in 800 mm panel or in 1000 mm panel 2500 A or 4000 A, additional ordering code F23, truck type design for switching device not possible

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 19 / 51 -

    2.2.3.10 Surge devices 3EF / 3EK

    Limiters 3EF Type of surge device Arrestors 3EK 3.6 kV 4.8 kV 7.2 kV

    Max. operating voltage for limiters

    12.0 kV 3.6 kV 5.5 kV 7.2 kV 8.25 V 12 15.5

    Max. operating voltage for arrestors

    17.5 Compensated or isolated Solidly earthed

    Neutral point

    Resistive earthed

    2.2.3.11 Zero sequence transformers 7XR96, UGSS708 1 2 80 mm

    Number

    120 mm 50 / 1A 60 / 1A

    Rated secondary current

    100 / 1 A

    Core data 1.25 VA, 1 FS10

    2.2.3.12 Specification of withdrawable part 1) for circuit breaker for disconnecting link for contactor with 1 fuse per phase, without fused control transformer for contactor with 2 fuses per phase, without fused control transformer for contactor with 1 fuse per phase, with fused control transformer 2) for contactor with 2 fuses per phase, with fused control transformer 2) Metering with voltage transformers, without fuses

    Type of withdrawable part

    Metering with voltage transformers, with fuses Manual operated Mechanism Motor operated 3)

    Auxiliary switch 4NO + 4 NC With mechanical interlocking of high voltage door With electromagnetic interlock With padlock

    Mechanical locking devices

    With key interlocking system, key free in test position

    1) withdrawable part on cassette is standard, truck type design as option possible (exception feeder current 3150 A and withdrawable voltage transformers in connection compartment are excluded) 2) only possible in 7.2 kV version 3) not possible for withdrawable part as disconnector function, metering and for contactor panel

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 20 / 51 -

    2.2.3.13 Circuit breaker SION (3AE) 12 kV Ordering number of breaker Panel data Breaker data 1 2 3 4 5 6 7 - 8 9.-14. 15 16 - Z kV kA Busbar

    (A) Feeder (A)

    Width (mm)

    Depth (mm)

    kV kA A

    630 600 12 25 800 3 A E 1 5 5 4 - 1 1000 600 12 25 1250 3 A E 1 5 5 4 - 2

    1250

    1250 800

    1350 / 1500

    12 25 1) 1250 3 A E 1 5 6 5 - 2 630 600 12 25 800 3 A E 1 5 5 4 - 1 1000 600 12 25 1250 3 A E 1 5 5 4 - 2 1250 800 12 25 1) 1250 3 A E 1 5 6 5 - 2

    2500

    2500 1000

    1350 / 1500

    12 31.5 2500 3 A E 1 5 6 5 - 6 1250 800 12 25 1) 1250 3 A E 1 5 6 5 - 2 2500 1000

    1500

    12 31.5 2500 3 A E 1 5 6 5 - 6

    3150

    3150 1000 1540 12 40 3150 3 A E 1 5 6 6 - 7 1250 800 12 25 1) 1250 3 A E 1 5 6 5 - 2 2500 1000

    1500

    12 31.5 2500 3 A E 1 5 6 5 - 6 3150 1000 12 40 3150 3 A E 1 5 6 6 - 7

    25

    4000

    4000 1000

    1540

    12 40 3150 3 A E 1 5 6 6 - 7 630 600 12 31.5 800 3 A E 1 5 5 5 - 1 1000 600 12 31.5 1250 3 A E 1 5 5 5 - 2

    1250

    1250 800

    1350 / 1500

    12 31.5 1250 3 A E 1 5 6 5 - 2 630 600 12 31.5 800 3 A E 1 5 5 5 - 1 1000 600 12 31.5 1250 3 A E 1 5 5 5 - 2 1250 800 12 31.5 1250 3 A E 1 5 6 5 - 2

    2500

    2500 1000

    1350 / 1500

    12 31.5 2500 3 A E 1 5 6 5 - 6 1250 800 12 31.5 1250 3 A E 1 5 6 5 - 2 2500 1000

    1500

    12 31.5 2500 3 A E 1 5 6 5 - 6

    3150

    3150 1000 1540 12 40 3150 3 A E 1 5 6 6 - 7 1250 800 12 31.5 1250 3 A E 1 5 6 5 - 2 2500 1000

    1500

    12 31.5 2500 3 A E 1 5 6 5 - 6 3150 1000 12 40 3150 3 A E 1 5 6 6 - 7

    31.5

    4000

    4000 1000

    1540

    12 40 3150 3 A E 1 5 6 6 - 7 1250 1250 800 12 40 1250 3 A E 1 5 6 6 - 2 1250 800 12 40 1250 3 A E 1 5 6 6 - 2 2000 800 12 40 2500 3 A E 1 5 6 6 - 6

    2500

    2500 1000

    1500

    12 40 2500 3 A E 1 5 6 6 - 6 1250 800 12 40 1250 3 A E 1 5 6 6 - 2 2000 800 12 40 2500 3 A E 1 5 6 6 - 6 2500 1000

    1500

    12 40 2500 3 A E 1 5 6 6 - 6

    3150

    3150 1000 1540 12 40 3150 3 A E 1 5 6 6 - 7 1250 800 12 40 1250 3 A E 1 5 6 6 - 2 2000 800 12 40 2500 3 A E 1 5 6 6 - 6 2500 1000

    1500

    12 40 2500 3 A E 1 5 6 6 - 6 3150 1000 12 40 3150 3 A E 1 5 6 6 - 7

    12

    40

    4000

    4000 1000

    1540

    12 40 3150 3 A E 1 5 6 6 - 7 Standard additional codes for all breakers Special low voltage connection W 6 3 Standard additional code for all breakers Metallic housing of mechnism D 5 2 Standard version for all

    breakers 15. position new version: mechanical interlocking, auxiliary switch 12 NO + 12 NC, with circuit breaker tripping signal, 64-pole plug

    N

    Gost-Certification E 1 3 Secondary wiring halogen free and flame retardent A 1 0

    Additional ordering code, optionally

    Silicon free design A 3 1 1 shunt release 2 shunt releases 1 shunt release+1 ct operated release 0,1 Ws / 20 Ohm

    Release combinations

    1 shunt release+1 undervoltage release

    1) due to temperature rise 31.5 kA breaker is used

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 21 / 51 -

    2.2.3.13 Circuit breaker SION (3AE) 17.5 kV Ordering number of breaker Panel data Breaker data 1 2 3 4 5 6 7 - 8 9.-14. 15 16 - Z kV kA Busbar

    (A) Feeder (A)

    Width (mm)

    Depth (mm)

    kV kA A

    630 600 17,5 25 800 3 A E 1 6 2 4 - 1 1000 600 17,5 25 1250 3 A E 1 6 2 4 - 2

    1250

    1250 800

    1350 / 1500

    17,5 25 1) 1250 3 A E 1 6 6 5 - 2 630 600 17,5 25 800 3 A E 1 6 2 4 - 1 1000 600 17,5 25 1250 3 A E 1 6 2 4 - 2 1250 800 17,5 25 1) 1250 3 A E 1 6 6 5 - 2

    2500

    2500 1000

    1350 / 1500

    17,5 31.5 2500 3 A E 1 6 6 5 - 6 1250 800 17,5 25 1) 1250 3 A E 1 6 6 5 - 2 2500 1000

    1500

    17,5 31.5 2500 3 A E 1 6 6 5 - 6

    3150

    3150 1000 1540 17,5 40 3150 3 A E 1 6 6 6 - 7 1250 800 17,5 25 1) 1250 3 A E 1 6 6 5 - 2 2500 1000

    1500

    17,5 31.5 2500 3 A E 1 6 6 5 - 6 3150 1000 17,5 40 3150 3 A E 1 6 6 6 - 7

    25

    4000

    4000 1000

    1540

    17,5 40 3150 3 A E 1 6 6 6 - 7 630 600 17,5 31.5 800 3 A E 1 6 2 5 - 1 1000 600 17,5 31.5 1250 3 A E 1 6 2 5 - 2

    1250

    1250 800

    1350 / 1500

    17,5 31.5 1250 3 A E 1 6 6 5 - 2 630 600 17,5 31.5 800 3 A E 1 6 2 5 - 1 1000 600 17,5 31.5 1250 3 A E 1 6 2 5 - 2 1250 800 17,5 31.5 1250 3 A E 1 6 6 5 - 2

    2500

    2500 1000

    1350 / 1500

    17.5 31.5 2500 3 A E 1 6 6 5 - 6 1250 800 17,5 31.5 1250 3 A E 1 6 6 5 - 2 2500 1000

    1500

    17.5 31.5 2500 3 A E 1 6 6 5 - 6

    3150

    3150 1000 1540 17.5 40 3150 3 A E 1 6 6 6 - 7 1250 800 17,5 31.5 1250 3 A E 1 6 6 5 - 2 2500 1000

    1500

    17.5 31.5 2500 3 A E 1 6 6 5 - 6 3150 1000 17.5 40 3150 3 A E 1 6 6 6 - 7

    31.5

    4000

    4000 1000

    1540

    17.5 40 3150 3 A E 1 6 6 6 - 7 1250 1250 800 17.5 40 1250 3 A E 1 6 6 6 - 2 1250 800 17.5 40 1250 3 A E 1 6 6 6 - 2 2000 800 17.5 40 2500 3 A E 1 6 6 6 - 6

    2500

    2500 1000 17.5 40 2500 3 A E 1 6 6 6 - 6 1250 800 17.5 40 1250 3 A E 1 6 6 6 - 2 2000 800 17.5 40 2500 3 A E 1 6 6 6 - 6 2500 1000

    1500

    17.5 40 2500 3 A E 1 6 6 6 - 6

    3150

    3150 1000 1540 17.5 40 3150 3 A E 1 6 6 6 - 7 1250 800 17.5 40 1250 3 A E 1 6 6 6 - 2 2000 800 17.5 40 2500 3 A E 1 6 6 6 - 6 2500 1000

    1500

    17.5 40 2500 3 A E 1 6 6 6 - 6 3150 1000 17.5 40 3150 3 A E 1 6 6 6 - 7

    17.5

    40

    4000

    4000 1000

    1540

    17.5 40 3150 3 A E 1 6 6 6 - 7 Standard additional codes for all breakers Special low voltage connection W 6 3 Standard additional code for all breakers Metallic housing of mechnism D 5 2 MLFB and ordering code for 25/31.5 kA breakers in package 2 frame to

    be clarified ? ? ?

    Standard version for all breakers

    15. position new version: mechanical interlocking, auxiliary switch 12 NO + 12 NC, with circuit breaker tripping signal, 64-pole plug

    N

    Gost-Certification E 1 3 Secondary wiring halogen free and flame retardent A 1 0

    Additional ordering code, optionally

    Silicon free design A 3 1 1 shunt release 2 shunt releases 1 shunt release+1 ct operated release 0,1 Ws / 20 Ohm

    Release combinations

    1 shunt release+1 undervoltage release

    1) due to temperature rise 31.5 kA breaker is used

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 22 / 51 -

    2.2.3.14 Contactor 3TL 1) Order nomber Rated

    voltage Standard BIL PFWV

    kV kV kV kV kV phase/phase Open contact

    gap phase/phase open contact

    gap 3 T L 6 2 3 7.2 IEC 60 40 20 20 3 T L 6 3 5 7.2 GOST 60 40 32 32 3 T L 6 6 5 12 IEC 75 60 28 28 1 Auxiliary switch 4NO+3NC 2 Auxiliary switch 6NO+5NC Without closing latch With closing latch AC operating voltage of drive solenoid and closing latch Fused control transformer secondary voltage 110 V AC 2) Fused control transformer secondary voltage 230 V AC 2) 1 HVRC fuse per phase, 442 mm length

    2 HVRC fuses per phase, 442 mm length

    2.2.3.15 Control transformer in contactor panel 2) Primary voltage (kV) 3.3 3.5 4 4.2 4.8 5 5.5 6 6.3 6.6 6.9 7.2 Secondary voltage (V) 110 V AC 220 V AC Frequency (Hz)

    50 60

    2.2.3.16 Fuses motor application of contactor panel Ur In HV HRC fuse Dimension e HV HRC fuse-link (kV) (A) (mm) Order no.: Type 6,3 192 3000213.6,3 HHD 10 192 3000213.10 HHD 16 192 3000213.16 HHD 20 192 3000213.20 HHD 25 192 3000213.25 HHD 31.5 192 3000213.31.5 HHD 40 192 3000213.40 HHD 50 442 3010853.50 HHM 63 442 3010853.63 HHM 80 442 3010853.80 HHM 100 442 3010853.100 HHM 125 442 3010953.125 HHM 160 442 3010953.160 HHM 200 442 3011054.200 HHM 250 442 3011054.250 HHM

    7.2

    315 442 3011054.315 HHM 6,3 A 292 30 004 13.6.3 HHD 10 A 292 30 004 13.10 HHD 16 A 292 30 004 13.16 HHD 20 A 292 30 004 13.20 HHD 25 A 292 30 004 13.25 HHD 31,5 A 292 30 004 13.31.5 HHD 40 A 292 30 004 13.40 HHD 50 A 442 30 101 53.50 HHM 63 A 442 30 101 53.63 HHM 80 A 442 30 102 53.80 HHM 100 A 442 30 102 53.100 HHM 125 A 442 30 102 53.125 HHM

    12

    160 442 30 103 53.160 HHM

    Required extension tubes for fuses with e < 442 m m Order no.: SIBA HV HRC fuse-link with dimension e 3400602 192 mm

    3400601 292 mm

    1) can be used for motor feeder and transformer feeder (not for transformer incomer), insulation level of GOST standard for 7.2 kV rated voltage as an option possible, 2) only possible in 7.2 kV version

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 23 / 51 -

    2.2.3.17 Fuses for withdrawable voltage transformers resp. control transform er of contactor panel application Rated current Metering panel for busbar metering 6.3 A fuses 6.3 A include inside voltage transformer housing Withdrawable voltage transformers at feeder

    side 6.3 A fuses 6.3 A include inside voltage transformer housing

    Control transformer in contactor panel 1) 3.15 A Type Bussmann, 3.15 A

    3. Accessories MLFB No.: 1 2 3 4 5 6 7 - 8 9 10 11 12 - 13 14 15 16 Standard accessory set consisting of: 1 hand crank for charging spring of circuit breaker, 1 Push rod for actuating the ON/OFF push buttons, 1 Hand lever for moving withdrawable part, 1 Hand lever for earthing switch, 1 socket spanner for high voltage and low voltage door, 1 operating manual

    8 B X 2 0 4 2 - 2 T

    1 hand crank for charging spring of circuit breaker 8 B X 2 0 4 2 - 2 U 1 Push rod for actuating the ON/OFF push buttons 8 B X 2 0 7 2 1 Hand lever for moving withdrawable part 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A B 7 1 Hand lever for earthing switch 8 B X 2 0 4 3 - 1 H 1 Adapter for earthing without withdrawable part 8 B X 2 0 4 3 - 1 G 1 Hand lever for withdrawable voltage transformers 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A B 8 1 socket spanner for high voltage door 8 B X 1 6 0 0 1 socket spanner for low voltage door 8 B X 1 6 0 1 1 marking spreading tool for drive-in anchor to fix panel to bottom for seismic version

    8 B X 3 3 0 0 - 0 L A 0 0 - 0 A C 1

    1 drilling jig for seismic version 8 B X 3 3 0 0 - 0 L A 0 0 - 0 A C 2 Endwalls 1Set=2peaces 8 B X 2 0 4 4 - 2 F Service truck, simplified version, 435 mm panel 8 B X 2 0 4 2 - 2 X A Service truck 2), simplified version, 600 mm panel, platform 8 B X 2 0 4 3 - 1 A Service truck 2), simplified version, 800 / 1000 mm panel, platform 8 B X 2 0 4 3 - 1 B Service truck device for withdrawable voltage transformers at cable side 8 B X 3 4 0 0 - 0 A A 0 0 - 0 A A 8 Hand lever for shutter mechanism (set) 8 B X 2 0 4 2 - 2 F A Voltage indication device for LRM-System 8 D X 1 6 2 0 Phase comparison measuring instrument for capacitive voltage indication system Type EPV-HR (Pfisterer incl. 2 HR-LRM Adapter and transport bag

    8 D X 1 6 0 7

    KP Glow lamp voltage tester with operation rod 12 kV 8 B X 1 6 1 5 KP Glow lamp voltage tester with operation rod 17,5 / 24 kV 8 B X 1 6 1 7 Testing equipment for pressure switch 8 A X 1 0 5 0 Portable earthing device up to 25 kA / 1 s,

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 24 / 51 -

    4. Additional tables

    4.1 Technical standards IEC 62271-1 Common clauses for high-voltage switchgear and controlgear standards

    Gemeinsame Bestimmungen fr Hochspannungsschaltgerte

    VDE 0671 1

    IEC 60071 - 1 Insulation co-ordination for equipment in three-phase systems above 1 kV

    Isolationskoordination fr Betriebsmittel in Drehstromnetzen ber 1 kV

    VDE 0111 - 1

    IEC 62271-200 A.C. metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV

    Metallgekapselte Wechselstrom-Schaltanlagen fr Nennspannungen ber 1 kV bis 52 kV

    VDE 0670 6

    IEC 62271-100 High-voltage alternating current circuit-breakers

    Hochspannungs-Wechselstrom-Leistungsschalter

    VDE 0671-100

    IEC 62271-102 Alternating current disconnectors (isolators) and earthing switches

    Wechselstromtrennschalter und Erdungsschalter

    VDE 0671-102

    IEC 60470 Contactors

    Schtze

    VDE 0670-501

    IEC 62265-1 High voltage alternating current switches

    Hochspannungs-Wechselstrom-Lastschalter

    VDE 0671-301

    IEC 62271-105 High-voltage alternating current switch-fuse combinations

    Hochspannungs-Lastschalter-Sicherungskombinationen

    VDE 0671-105

    IEC 60529 Degree of protection provided by enclosures (IP-code)

    Schutzarten durch Gehuse (IP-Code)

    VDE 0470 - 1

    IEC 61243-5 Working under voltage - Voltage detectors

    Part 5: Voltage detection systems

    Arbeiten unter Spannung - Spannungsprfer -

    Teil 5: Spannungsprfsysteme

    VDE 0682 - 415

    IEC 60282 1 Current limiting fuses

    Strombegrenzende Sicherungen

    VDE 0670 4

    IEC 60044 -1 Current transformers

    Stromwandler

    VDE 0414 1

    IEC 60044 -2 Voltage transformers

    Spannungswandler

    VDE 0414 2

    IEC 60721-3-3 Classification of environmental conditions

    Klassifizierung von Umweltbedingungen

    DIN EN 60721-3-3

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 25 / 51 -

    4.2 Technical data

    4.2.1 insulation values Rated voltage kV 7,2 12 17.5

    Rated frequency Hz 50/60 50/60 50/60

    Rated short-duration power frequency withstand voltage Phase/phase, phase/earth, open contact gap 1)

    kV 20 IEC 32 GOST 2)

    28 IEC 42 GOST 2)

    38 IEC

    Rated short-duration power frequency withstand voltage Disconnecting distance 3)

    kV 23 IEC 36 GOST 2)

    32 IEC 48 GOST 2)

    45 IEC

    Rated lightning impulse withstand voltage Phase/phase, phase/earth, open contact gap 1)

    kV 60 IEC, GOST 2) 75 IEC, GOST 2) 95 IEC

    Rated lightning impulse withstand voltage

    Disconnecting distance 3)

    kV 70 IEC, GOST 2) 85 IEC, GOST 2) 110 IEC

    4.2.2 short circuit values, dimensions busbar current 4) (A)

    feeder current 4) (A)

    rated voltage (kV)

    panel type short circuit breaking current (kA)

    rated busbar current (A)

    rated current (A)

    rated breaker current (A)

    rated panel current (A)

    panel design

    width (mm)

    depth (mm)

    Height 5)

    630 800 630 1000 1250 1000

    600 1250

    1250 1250 1250

    closed

    800 630 800 630 1000 1250 1000

    600

    1250 1250 1250

    closed

    800

    2500

    2500 2500 2500 natural ventilated 1000

    1350 6)

    1250 1250 1250 800 2500 2500 2500 natural ventilated 1000

    1500 7) 3150

    3150 3150 3150 natural ventilated 1000 1540 8) 1250 1250 1250 800 2500 2500 2500 natural ventilated 1000

    1500 7)

    3150 3150 3150 natural ventilated 1000

    25

    4000

    4000 3150 4000 forced ventilated 1000 1540 8)

    630 800 630 1000 1250 1000

    600 1250

    1250 1250 1250

    closed

    800 630 800 630 1000 1250 1000

    600

    1250 1250 1250

    closed

    800

    2500

    2500 2500 2500 natural ventilated 1000

    1350 6)

    1250 1250 1250 800 2500 2500 2500 natural ventilated 1000

    1500 7) 3150

    3150 3150 3150 natural ventilated 1000 1540 8) 1250 1250 1250 800 2500 2500 2500 natural ventilated 1000

    1500 7)

    3150 3150 3150 natural ventilated 1000

    31.5

    4000

    4000 3150 4000 forced ventilated 1000 1540 8)

    1250 1250 1250 1250 800 1250 1250 1250 800 2000 2500 2000

    closed

    800 2500

    2500 2500 2500 natural ventilated 1000 1250 1250 1250 800 2000 2500 2000

    closed 800

    2500 2500 2500 natural ventilated 1000

    1500 7)

    3150

    3150 3150 3150 natural ventilated 1000 1540 8) 1250 1250 1250 800 2000 2500 2000

    closed 800

    2500 2500 2500 natural ventilated 1000

    1500 7)

    3150 3150 3150 natural ventilated 1000

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 26 / 51 -

    4.2.3 short circuit values, dimensions busbar current 1) (A)

    feeder current 1) (A)

    rated voltage (kV)

    panel type short circuit breaking current (kA)

    rated busbar current (A)

    rated current (A)

    rated breaker current (A)

    rated panel current (A)

    panel design

    width (mm)

    depth (mm)

    height 2)

    (mm)

    1250

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 27 / 51 -

    4.2.4 dimensions of switchgear room with pressure release channel to lead gases outside 1)

    = 150 at one side of switchgear row, >= 100 for contactor panel, when pressure release duct is used at least at one opposite side of switchgear row >= 500 mm

    for operating in front of switchgear mm >= 1250

    aisles

    for panel replacement mm >= 1750

    Loss of service continuity class 4.3 For feeders with withdrawable parts LSC 2B (metal clad design)

    Partition class 4.4 For feeders with withdrawable parts PM (metal clad design)

    4.5 Internal arc fault classification Standard design IAC = internal arc classification

    A = 300 mm distance of indicators, F/L/R accessibility from F = front, L = lateral and R = rear, 40 kA = short circuit current of switchgear, 1 s = duration of tested arc fault current

    (versions of pressure relief system see table in chapter 1.3, special duct devices see also in chapter 3, accessories)

    Additionally with pressure switch system without testing device, duration 0.1 s

    Additionally with pressure switch system with testing device, duration 0.1 s

    Optional design

    Additionally with optical system, duration 0.1 s

    Additionally to Standard IEC 62271-200 Confinement of internal arc within a compartment (pressure tight partitions up to 17.5 kV/31.5 kA/2500A)

    4.6 Degree of protection enclosure Standard IP 3X D

    optional IP 4X

    optional IP 50, (only for non ventilated panels, and in combination with additional pressure relief channel to lead the gases outside the switchgear room)

    optional IP 51, (only for non ventilated panels, and in combination with additional pressure relief channel to lead the gases outside the switchgear room)

    partitions Standard IP 2X

    4.7 Creepage distances, clearances in air contactor panel circuit breaker panel and others typicals

    435 mm panel 600 mm panel, = 2500 A, = 55 mm on request on request >= 110 mm >= 90 mm

    phase to earth >= 55 mm on request on request >=80 mm >= 80 mm

    creepage distance on request on request on request >= 220 mm >= 220 mm

    A main benefit of type tested switchgear in accordance to IEC 62271-200 is saving space in order to minimize volume of switchgear room. NXAIR switchgear are type tested and fulfill the following requirements with required values as shown in table 4.1, such as:

    rated short-duration power frequency withstand voltage, Phase/phase, phase/earth, open contact gap,

    rated short-duration power frequency withstand voltage, Disconnecting distance

    rated lightning impulse withstand voltage, Phase/phase, phase/earth, open contact gap

    rated lightning impulse withstand voltage, Disconnecting distance

    Due to this special dimensions between phases and to earth are no criteria for quality of isolation capacity. Important criteria are only fulfilling the required test values.

    1) generally needed for 40 kA internal arc current value

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 28 / 51 -

    4.8 Type tests in accordance to IEC 62271-1 resp. IEC 62271 -200 Following type tests will be carried out mandatory:

    chapter Type test

    6.2 Test to verify the insulation level of main circuits and low voltage circuits test values: Rated lightning impulse withstand voltage depending form rated voltage of switchgear, see also 4.2.1 rated short duration power frequency withstand voltage depending from rated voltage, see also 4.2.1

    6.4, 6.5 Tests to prove temperature rise of any part of equipment and measurement of the resistance of circuits test values: rated current of busbar and feeder, maximum temperature rise values for main parts depending from material of contacts and materials based on 40C ambient temperature: silver coated contacts: temperature rise 65C K bolted connections bare copper: temperature rise 50C K bolted connections silver-coated copper: temperature rise 75C K materials used as insulation: temperature rise 50C K accessible parts of enclosure: temperature rise 40C K

    6.6 Tests to prove capability of the main circuits and earthing circuits test values: short time withstand current for 1 or 3 s, see also 4.2.1, multiplied with 2.5 = peak withstand current for 50 Hz applications short time withstand current for 1 or 3 s, see also 4.2.1, multiplied with 2.6 = peak withstand current for 60 Hz applications

    6.101 Tests to prove the making and breaking capacity of the included devices test values: short circuit breaking current, see also 4.2.1, multiplied with 2.5 = short circuit making current for 50 Hz applications short circuit breaking current, see also 4.2.1, multiplied with 2.6 = peak circuit making current for 60 Hz applications

    6.102 Tests to prove satisfactory operation of the included switching devices and removable parts test values: 1000 mechanical cycle for withdrawable part and earthing switch

    6.7 Test to verify the protection of persons against access to hazardous parts and the protection of the equipment against solid foreign objects test values: IP2X, IP3X D, IP 4X; IP50, IP51 depending from version

    Following type tests will be carried out generally ( in standard required mandatory, where applicable):

    6.106 Test to verify internal arc classification test values: IAC A FLR Isc 1s or 0.1 s, see also 4.5

    6.9 Test to verify electromagnetic compatibility (EMC)

    4.9 Routine tests in accordance to IEC 62271-1 resp. IEC 622 71-200 Following routine tests will be carried out:

    7.1 Dielectric test with power frequency voltage of main circuits test values: rated short duration power frequency withstand voltage depending from rated voltage, see also 4.2.1

    7.2 Dielectric test of auxiliary circuits test values: 1 kV, 1 s

    7.5 Design and visual checks

    7.102 Mechanical operation tests

    7.104 Test of auxiliary devices, verification of the correct wiring

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 29 / 51 -

    4.10 NXAIR,

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 30 / 51 -

    4.10 NXAIR,

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 31 / 51 -

    4.10 NXAIR, 17.5 kV, 50 Hz, 25 / 31.5 kA,

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 32 / 51 -

    4.10 NXAIR, 17.5 kV, 60 Hz, 25 / 31.5 kA,

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 33 / 51 -

    4.11 NXAIR,

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 34 / 51 -

    4.11 NXAIR,

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 35 / 51 -

    4.11 NXAIR, 17.5 kV, 50 Hz, 40 kA,

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 36 / 51 -

    4.11 NXAIR, 17.5 kV, 60 Hz, 40 kA,

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 37 / 51 -

    4.12 Permissible combination of components in connection compartment of s witching device panel resp. busbar connecting panel, detailed configuration NX-Tools+

    Connection in cable compartment

    Rated vol-tage

    Short circuit with-stand current

    Rated feeder current

    width Cable access from:

    venti- lation

    current trans-formers

    earthing switch

    voltage trans-formers

    fixed mounted

    voltage transformers

    withdrawable

    Surge limiter 1)

    Surge arrestor

    From bottom, front or rear

    From top, rear 2)

    (kV) (kA) (A) (mm) Number of cables 3) per phase / bar

    Number of cables 3) per phase / bar

    Contactor panel 3 1 - - - -

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 38 / 51 -

    4.13 Permissible combination of components in busbar compartment of swi tching device panel, detailed configuration NX-Tools+ Rated voltage

    Short circuit with-stand current

    Rated feeder current

    Width ventilation Bushing type insulators

    Voltage transformers in top box

    Earthing switch in top box

    Bar or cable connection to busbar

    (kV) (kA) (A) (mm)

    Contactor panel 12 31.5 400 435 - 3 - - -

    All other panel types 3 - - -

    3 3 - - 3 - 1 -

    630 600 without

    3 - 1 3 - - - 3 3 - 3 - 1

    1000 600 without

    3 - 1 3 - - - 3 3 - - 3 - 1 -

    1250 800 without

    3 - - 1 3 - - - 3 3 - - 3 - 1 -

    2000 1) 800 without

    3 - - - 3 - - 2500 1000 natural - - - - 3 - - 3150 1000 natural - - - - 3 - -

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 39 / 51 -

    Technical data of circuit breaker Rated voltage kV 12

    17.5

    Rated frequency Hz 50 / 60 50 / 60

    Rated short-duration power frequency withstand voltage

    Phase/phase, phase/earth, open contact gap

    kV 28, IEC 42, GOST

    38, IEC

    Rated lightning impulse withstand voltage

    Phase/phase, phase/earth, open contact gap

    kV 75, IEC, GOST 95, IEC

    Rated short-time withstand current of main circuits

    kA 25 31.5 40 25 31.5 40

    Rated duration of short circuit s 1, 3 1, 3

    Rated peak withstand current kA 63 / 65 80 / 82 100 / 104 63 / 65 80 / 82 100 / 104

    Rated short circuit breaking current kA 25 31.5 40 25 31.5 40

    Rated short circuit making current kA 63 / 65 80 / 82 100 / 104 63 / 65 80 / 82 100 / 104

    Rated normal current A 800 1250

    800 1250 2500

    1250 2500 3150

    800 1250

    800 1250 2500

    1250 2500 3150

    Asymmetrical breaking current kA 28 35.4 44.9 28 35.4 44.9

    DC component at rated short circuit breaking current

    % 36 36 36 36 36 36

    Rate-of-rise (RRRV) kV /

    s 0.34 0.34 0.34 0.42 0.42 0.42

    Voltage (TRV) peak value kV 20.6 20.6 20.6 30 30 30

    Switching duty 0 0.3 s CO 15 s. CO up to 31.5 kA

    0 3 min. CO 3 min. CO for 40 kA

    Closing time ms < 75

    Opening time 1 st shunt release ms < 65 ms

    Opening time 2 nd, 3 rd shunt release ms < 50 ms

    Arcing time ms < 15 ms

    Breaking time 1 st shunt release ms < 80 ms

    Breaking time 2 nd, 3 rd shunt release ms < 65 ms

    Dead time ms 300 ms

    Close-/ Open time 1 st shunt release ms < 75 ms

    Close-/ Open time 2 nd, 3 rd shunt release ms < 60 ms

    Pulse time for breaker tripping signal for 1 st shunt release ms > 15

    Pulse time for breaker tripping signal for 2 nd and 3 rd shunt release ms > 10

    Spring-charging time for electrical operation s 10

    Synchronous operation error between the poles ms 2

    Release Order no of release

    Power consumption Tripping ranges Tripping pulse

    at DC operation

    appr. W

    at AC

    50/60 Hz operation

    appr. VA

    Tripping voltage DC Tripping voltage / current

    (50/60 Hz AC)

    Closing solenoid 3AY1510 140 140 85 to 110 % U 85 to 110 % U -

    1 st shunt release

    (without energy store)

    3AY1510 140 140 70 to 110 % U 85 to 110 % U -

    2 nd shunt release

    (with energy store)

    3AX1101 70 50 70 to 110 % U 85 to 110 % U -

    Undervoltage release 3AY1103 20 20 35 to 0 % U 35 to 0 % U -

    Ct operated release

    (tripping pulse>= 0.1 Ws

    3AX1104 - - - - -

    Power consumption of motor DC 350 W

    Power consumption of motor AC 400 VA

    Switch classification 1) electrically mechanically Capacitive switching capability

    E2 M2 C2

    4.14

    contacts of auxiliary switch of breaker

    12 NC+12NO Free contacts for external use

    1) detailed information see also 4.15 next page

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 40 / 51 -

    4.15 Technical data of contactor Rated voltage kV 7.2 12

    Ordering nomber

    3TL62 3TL63 3TL66

    Rated frequency Hz 50/60

    phase/phase, phase/earth

    kV 20 32 28 Rated short-duration power frequency withstand voltage

    open contact gap

    kV 20 20 28

    Phase/phase, phase/earth

    kV 60 60 75 Rated lightning impulse withstand voltage

    open contact gap

    kV 40 40 60

    Rated short-time withstand current kA / s 8 / 1 8 / 1 8 / 1

    Rated continuous normal current according to 60470 A 450 400 400

    Rated making capacity A 4500 4000 4000

    Rated breaking capacity A 3600 3200 3200

    Limit switching capacity A 5000 4500 4500

    Rated breaking current for capacitor switching A 250 250 250

    Rated making current for capacitor switching kA 10 10 10

    Mechanical endurance of contactor cycles 1,000,000 1,000,000 1,000,000

    Electrical endurance of vacuum interrupter of contactor while breaking the continuous current

    cycles 1,000,000 500,000 500,000

    Switching rate without mechanical closing latching cycles / h

    1200 600 600

    Power consumption of drive solenoid, making capacity W 650 650 650

    Power consumption of drive solenoid, holding power referred to 230 V AC

    W 90 90 90

    Voltage range of drive solenoid, operating voltage V 0,8 1.1 Ua 0,8 1.1 Ua 0,8 1.1 Ua

    Minimum closing command for drive solenoid ms 100 100 100

    Closing time (interval of time between closing command and the instant when the contacts touch for the first time)

    ms 100 ms at 0.85 Ua 80 ms at 1.00 Ua 60 ms at 1.1 Ua

    100 ms at 0.85 Ua 80 ms at 1.00 Ua 60 ms at 1.1 Ua

    100 ms at 0.85 Ua 80 ms at 1.00 Ua 60 ms at 1.1 Ua

    Opening time (interval of time between opening command and the instant when the contacts start to separate)

    30 ms at 0.85 Ua 50 ms at 1.00 Ua 50 ms at 1.1 Ua

    30 ms at 0.85 Ua 50 ms at 1.00 Ua 50 ms at 1.1 Ua

    30 ms at 0.85 Ua 50 ms at 1.00 Ua 50 ms at 1.1 Ua

    Mechanical closing latch, operating cycles cycles 100,000 100,000 100,000

    Mechanical closing latch, switching rate Cyles / h 60 60 60

    Mechanical closing latch, power consumption of the latch release solenoid

    W 900 900 900

    Mechanical closing latch, voltage range of the latch release solenoid

    V 0.85 1.1 Ua 0.85 1.1 Ua 0.85 1.1 Ua

    Mechanical closing latch, opening pulse s 0.2 max. 1 0.2 max. 1 0.2 max. 1

    Mechanical closing latch, opening time ms < 45 < 45 < 45

    Contacts of auxiliary switch of contactor - 4NO/3NC or 6NO/5NC

    4NO/3NC or 6NO/5NC

    4NO/3NC or 6NO/5NC

    Free contacts for external use -

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 41 / 51 -

    4.16 Technical data of fuses for motor application of contactor panel Current carrying capacity of fuses in contactor pan el

    Un Ith f Type

    Number per phase

    In HV HRC fuse

    Current carrying capacity in A at ambient temperature in C

    kV kA Hz (A) 25C 30C 35C 40C 45C 50C 55C

    3011054.250 2 250 344 333 322 310 298 285 272

    3011054.200 2 200 284 275 266 256 246 235 225

    3010953.160 2 160 250 242 233 225 216 207 197

    3011054.315 1 315 264 256 247 238 229 219 209

    3011054.250 1 250 224 217 210 202 194 186 177

    3011054.200 1 200 184 178 172 166 159 153 146

    3010953.160 1 160 161 156 150 145 139 133 127

    3010953.125 1 125 124 120 116 112 108 103 98

    3010853.100 1 100 100 97 93 90 86 83 79

    3010853.80 1 80 80 79 76 74 71 68 65

    3010853.63 1 63 63 63 63 63 63 63 63

    3010853.50 1 50 50 50 50 50 50 50 50

    50

    For rated fuse currents < 50 A, no current reduction must be considered due to the ambient temperature

    3011054.250 2 250 339 328 317 305 293 281 268

    3011054.200 2 200 280 271 262 252 242 232 221

    3010953.160 2 160 246 238 230 222 213 204 194

    3011054.315 1 315 260 252 243 234 225 216 206

    3011054.250 1 250 221 214 206 199 191 183 175

    3011054.200 1 200 181 176 170 164 157 150 143

    3010953.160 1 160 158 153 148 143 137 131 125

    3010953.125 1 125 122 119 114 110 106 101 97

    3010853.100 1 100 98 95 92 89 85 82 78

    3010853.80 1 80 79 78 75 73 70 67 64

    3010853.63 1 63 63 63 63 63 63 63 63

    3010853.50 1 50 50 50 50 50 50 50 50

    7.2

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 42 / 51 -

    Type designitions for all possible rated fuse curre nts for motor application, fuse length e, order n omber

    Ur In HV HRC fuse Dimension e HV HRC fuse-link

    (kV) (A) (mm) Order no.: Type

    6,3 192 3000213.6,3 HHD

    10 192 3000213.10 HHD

    16 192 3000213.16 HHD

    20 192 3000213.20 HHD

    25 192 3000213.25 HHD

    31.5 192 3000213.31.5 HHD

    40 192 3000213.40 HHD

    50 442 3010853.50 HHM

    63 442 3010853.63 HHM

    80 442 3010853.80 HHM

    100 442 3010853.100 HHM

    125 442 3010953.125 HHM

    160 442 3010953.160 HHM

    200 442 3011054.200 HHM

    250 442 3011054.250 HHM

    7.2

    315 442 3011054.315 HHM

    6,3 292 30 004 13.6.3 HHD

    10 292 30 004 13.10 HHD

    16 292 30 004 13.16 HHD

    20 292 30 004 13.20 HHD

    25 292 30 004 13.25 HHD

    31.5 292 30 004 13.31.5 HHD

    40 292 30 004 13.40 HHD

    50 442 30 101 53.50 HHM

    63 442 30 101 53.63 HHM

    80 442 30 102 53.80 HHM

    100 442 30 102 53.100 HHM

    125 442 30 102 53.125 HHM

    12

    160 442 30 103 53.160 HHM

    Required extension tubes for fuses with e < 442 m m

    Order no.: SIBA HV HRC fuse-link with dimension e

    3400602 192 mm

    3400601 292 mm

    Table for selection fuses depending from starting c onditions of motor

    Starting time of motor

    Number of starts per hour

    Maximum permissible motor starting current in A at rated current and number of HV HRC fuse-links per phase in A

    1x50 1x63 1x100 1x125 1x160 1x200 1x250 2x160 2x200 2x250

    2 131 165 310 418 566 765 1283 1132 1530 2566

    4 118 148 278 375 509 687 1153 1018 1374 2306

    8 107 134 252 340 461 622 1044 922 1244 2088

    16 95 120 225 304 413 557 935 826 1114 1870

    5 s

    32 87 109 205 276 374 505 848 748 1010 1696

    2 112 139 254 344 459 641 1007 918 1282 2014

    4 101 125 228 309 412 575 905 824 1150 1810

    8 91 113 207 280 374 521 819 748 1048 1638

    16 82 102 185 251 335 467 734 670 934 1468

    15 s

    32 74 92 168 228 303 423 666 606 846 1332

    2 99 126 229 303 406 552 865 812 1104 1730

    4 89 113 206 272 365 496 777 730 992 1554

    8 81 102 186 247 330 449 704 660 898 1408

    16 72 92 167 221 296 403 630 592 806 1260

    30 s

    32 65 83 151 200 268 365 572 536 730 1144

    2 91 114 204 273 357 501 777 714 1102 1554

    4 82 103 183 246 321 450 698 642 900 1369

    8 74 93 166 222 291 407 632 582 814 1264

    16 66 83 149 199 260 365 566 520 730 1132

    60 s

    32 60 76 135 181 236 331 514 472 662 1028

    Detailed information regarding fuses also in intran et: https://intranet.wss02.ptd.siemens.de/content/00001 122/AIS_Common/HH-SiSchuetz_Kennlinien.pdf

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 43 / 51 -

    Design example for selection of fuses and current t ransformer depending from motor data Motor data, example Motor data, example Ub = 6 kV Ik = 25 kA P = 900 kW cos = 0.85 = 0.85 Ia = 6 x In max. 2 starts per hour max. starting time 5s

    In = P / Ubx3x cos x = 900 kW / 6 kVx3x0.85x0.85 = 120 A Ia = 6 x In = 720 A The rated operating current of the HV HRC fuse should be read from the above shown table using the data given: 250 A

    Definitions Selection of current transformers

    Ia = starting current of motor Idyn = max. peak current of current transformer ID = cut-off current of fuse Ik = short circuit current (r.m.s. value) In = rated current of motor Ith = short time withstand current P = rated motor power cos = Power factor of motor = motor efficiency

    The cut-off current of a fuse with 250 A rated current is for Ik = 25 kA short circuit value: 25 kA (depending from characteristic of fuse for these values, see also above mentioned link to intranet) Thermal stressing of current transformer by the short time current rating Ith is negligible as a result of current limiting by the HV HRC fuses. The current transformer must be capable of withstanding mechanical stress due only to the cut-off current ID. In this connection the cut-off current ID is equivalent to the peak current of current transformer Idyn. Idyn >= ID Ith = Idyn / 2.5 = 25 kA / 2.5 = 10 kA The current transformer must be designed for an Ith of >= 10 kA

    selection guide according contactor or circuit brea ker for motor switching applications Selection of switching device for motors is influenced by following key factors:

    rated voltage of network and motor frequency of network rated power of motor rated current of motor required switching cycles based on application of motor in production process power factor cos of motor motor efficiency factor starting current of motor number of starts per hour starting time of motor max. number and rated current of fuses which can be installed in panel when contactor is used, ambient temperature of switchgear room for contactors lower rated lightning impulse withstand voltages across the open contact gap as circuit breakers are required based on

    different standards (at 7.2 kV: 40 kV instead of 60 kV, at 12 kV: 60 kV instead of 75 kV)

    Additionally to above mentioned key factors protection and primary cable philosophy have to be considered. Protection philosophy is influenced by significance and importance of motor in process while using differential protection relays in combination with circuit breakers or over current protection in combination with fuses and contactors. Due to current limiting function of fuses in combination with contactors cross section of primary cables can be optimized.

    Based on above mentioned key factors following advice for selecting contactor with fuses can be given:

    Max. fuses which can be installed in contactor panels:

    NXAIR switchgear: 7.2 kV: single fuse per phase 1 x 315 A, parallel fuses per phase 2 x 250 A

    12 kV: single fuse per phase 1 x 160 A, parallel fuses per phase 2 x 160 A

    NXAIR P switchgear: 7.2 kV: single fuse per phase 1 x 315 A, parallel fuses per phase 2 x 250 A

    Depending from max. permissible current values of complete contactor panel including fuses with above mentioned ratings in NXAIR and NXAIR P switchgear,

    based on 35 C ambient temperature of switchgear ro om,

    rated voltage of motor for 7.2 kV application: 6.6 kV

    rated voltage of motor for 12 kV application: 11 kV

    power factor cos = 0,9

    motor efficiency = 0,9

    following average power values of motors can be switched with fused contactor units:

    7.2 kV: 3000 kW

    12 kV: 3000 kW

    For higher power values of motors circuit breakers should be checked.

    Detailed calculation based on precise figures and specific conditions on site can vary above mentioned result.

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 44 / 51 -

    4.17 Technical data of withdrawable part for circuit breaker, di sconnector link, measuring device

    hand operated Standard Mechanism 1)

    motor operated optionally for withdrawable part with circuit breaker

    Mechanical to circuit breaker position

    Standard

    padlockable option

    interlockings

    key interlocking device option

    mechanically Switch classification 2)

    M0

    contacts of auxiliary switch of withdrawable part

    4 NC+4 NO free contacts for external use

    auxiliary voltage DC 35 W Power consumption motor mechanism

    auxiliary voltage AC 35 VA

    Time for moving withdrawable part from test to service position or vice versa appr. 25 s

    4.18 Technical data of earthing switches Rated voltages kV 12 17,5

    Rated frequency Hz 50 / 60 50 / 60

    Rated short-duration power frequency withstand voltage

    Phase/phase, phase/earth

    kV 28 IEC

    42 GOST

    38, IEC

    Rated lightning impulse withstand voltage

    Phase/phase, phase/earth

    kV 75 IEC, GOST 95, IEC

    Rated short-time withstand current 3) kA

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 45 / 51 -

    4.21 Power consumptions of electrical devices device Power consumption

    Motor for spring charging, DC 350 W,

    Motor for spring charging, AC 400 VA

    Circuit breaker

    Running time of motor 10 s

    Drive solenoid, making capacity 650 W

    Drive solenoid, holding power 90 W

    contactor

    Mechanical closing latch, power consumption of the latch release solenoid

    900 W

    Motor mechanism DC 35 W

    Motor mechanism AC 35 VA

    Withdrawable part

    Running time of motor Appr. 25 s

    Motor mechanism DC 35 W

    Motor mechanism AC 35 VA

    Earthing switch busbar or feeder

    Running time of motor appr. 25 s

    Electrical interlocking magnets Only active in releasing function 10 W, suitable for continous energisation

    Circuit breaker compartment 100 W

    Cable compartment 100 W

    heaters

    Low voltage compartment 20 W

    4.22 Configuration information pressure release channel system Application of pressure release channel system to lead gases due to internal arc outside switchgear room

    Rated voltage IAC-classification Arc fault current Arc fault duration Height of switchgear room

    Pressure relief system

    >= 2500 / < 2800 mm duct to outside 2800 mm absorbers

    >= 2500 / < 3000 duct to outside 31.5 kA 1 s or 0.1 s

    >= 3000 mm absorbers

    >= 2500 / < 3500 mm duct to outside

    = 3500 absorbers

    >= 2500 / < 3500 mm duct to outside 3500 mm absorbers

    >= 2500 / < 3500 duct to outside 31.5 kA 1 s or 0.1 s

    >= 3500 mm absorbers

    >= 2500 mm / < 3500 duct to outside

    17.5 kV IAC A FLR

    40 kA 1 s or 0.1 s

    >= 3500 mm absorbers

    All parts of channel system are included in accessories of NXAIR, chapter 3, and can be configurated with NX-Tools+ and will be delivered together with switchgear.

    Channel parts consists of zinc coated steel, thickness 2 mm, screws M8, following parts can be plugged and screwed together, cross section 530 mm x 245 mm:

    Adapter device at standard pressure relief channel to left, will be configurated with NX-Tools+ Adapter device at standard pressure relief channel to right, will be configurated with NX-Tools+ Adapter device at standard pressure relief channel to rear, will be configurated with NX-Tools+ Channel, length 1000 mm, ordering number 8BX3400-0AA00-0AA0 Angle channel 45 up / down, ordering number 8BX3400- 0AA00-0AA1 Angle channel 45 right / left, ordering number 8BX34 00-0AA00-0AA2 Channel, length 500 mm, ordering number 8BX3400-0AA00-0AA3 Channel length extendable from 595 mm to 760 mm in 20 mm steps, ordering number 8BX3400-0AA00-0AA4 Channel, length 370 mm for wall outgoing, powder coated RAL 7035, ordering number 8BX3400-0AA00-0AA5 Fixing ledges, ordering number per set 8BX3400-0AA00-0AA6 Fixing angles, ordering number per set 8BX3400-0AA00-0AA7 Additional fixing parts have to be organized on site.

    Generally all type tests in accordance to IEC 62271-200 will be made on representative functional units. As mentioned in this IEC it is not practicable to make for all arrangements of switchgear special type tests. Because of the variety of types, ratings and possible combinations of components it is possible in accordance to standard that the performance of any particular arrangement may be substantiated by test data or simulation calculations of comparable arrangements. Due to this and the fact that each switchgear room never will have exactly same dimensions, installed equipment etc., the functionality of this channel system has been evaluated by type tests in combination with simulation calculations.

    Following rules for planning have to be considered, see also below shown pictures: Channel should be realized to lateral side or rear side Lateral direction of channel system: end panel (all available typicals) which should be used for adaption of channel does not have busbar voltage transformer resp. busbar earthing switch, ventilated panel is possible Rear side direction of channel system: panel which should be used for adaption of channel does not have busbar voltage transformer resp. busbar earthing switch or ventilation resp. rear side cable box for primary cables coming from above, adaption to one single contactor panel is not possible, but in the middle of two contactor panels. At least one panel of each busbar section (when bus sectionalizer is included) must have one connected channel system to lateral or rearside Length of switchgear and number of busbar device have no impact on configuration of channel system

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 46 / 51 -

    Height of switchgear room have to be >= 2500 mm

    Principle version of pressure release channels, detailed drawing see intranet

    Pressure release channel to left or right side, cross section of channel itself 537 mm x 248.5 mm, location see above drawing

    Pressure release channel to rear side, cross section of channel itself 537 mm x 248.5 mm

    Rear side of switchgear with channel to rear, e.g. three panels

    Side view of switchgear, channel to rear

    600800

    1000

    537

    20002

    248.

    5

    20002

    248.

    5

    600800

    1000

    537

    20002

    248.

    5

    20002

    248.

    5

    switchgear front view,channel lateral

    switchgear top view,channel lateral

    switchgear front view,channel rearside

    switchgear top view,channel rear side

    switchgear front view,channel lateral

    switchgear top view,channel lateral

    switchgear front view,channel rearside

    switchgear top view,channel rear side

    distance at rear side between switchgear and wall > = 150 mm for cable connection from front resp. >= 500 mm for cable connection from rear distance lateral > 150 mm resp. >=100 mm for contactor panel at one side of switchgear rrow resp. 500 mm at opposite side of switchgear row

    Front view of switchgear, channel to lateral side view of switchgear, channel to lateral

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.2011 - 47 / 51 -

    Channel device Ordering nomber Channel type

    8BX3400-0AA00-0AA0

    Channel length 1000 mm

    8BX3400-0AA00-0AB0

    Channel length 260 mm, IP4X

    8BX3400-0AA00-0AA1

    Angle 45 rotatable upwards or downwards

    8BX3400-0AA00-0AA2

    Angle 45 rotatable right or left

    8BX3400-0AA00-0AA3

    Channel length 500 mm

    8BX3400-0AA00-0AA4

    Channel extendable 595 mm to 760 mm in 20 mm steps

    8BX3400-0AA00-0AA5

    Wall outlet box, length 370 mm

    8BX3400-0AA00-0AA6

    Fixing ledges,

    consisting of two parts

    8BX3400-0AA00-0AA7

    Fixing angles,

    Consisting of two parts

  • nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

    IC LMV MV1 PPM, Herbert Soens issued: 24.10.201