THERMOZONE AC 300/ WAC 300
Frico AB, Box 102, SE-433 22 Partille � Tel: +46 31-336 86 00 � Fax: +46 31-26 28 60 � mailbox@frico.se � www.frico.seDesign and specifications are subject to change without notice.
0.5 m
1.5 m
2.5 m
3.5 m
6.9 m/s
5.0 m/s
4.1 m/s
10.0 m/s
AC 300/WAC300
The Thermozone 300-series consists of the ACvariant in both heated and ambient only format andthe hot water heated WAC model.
These models are designed for permanenet hori-zontal installation over doorways of heights between2.5 and 3.0 metres or positioned vertically beside thedoorway when overdoor space is limited. They can besurface mounted or recessed into a false ceiling. A jetof air from the air curtain prevents cold draughtsthrought open doorways and increases comfort levelsin the proximity of the door whereas the ambient airvariant has been specifically designed for cold storeapplications and entrances to airconditionedbuildings to prevent the loss of refrigerated air.
The use of a Thermozone 300 air curtain enablesthe use of floor space close to the doorway and cansignificantly reduce energy losses giving largesavings. The Thermozone 300 range can also be usedfor industrial heating and drying applications. Forwide doorways, several units can be mounted next toeach other and regulated with a common thermostatand control panel.
The Thermozone 300 series is manufactured inlengths of 1.0 and 1.7 metres which can be combinedto best cover a particular doorway. For doorwayswhich are fitted with ceiling mounted sliding doors,adaptation sets are available that direct the airflowclose to the opening.
� Corrosion proof houing made of hot zinc-plate andpowder enamelled steel panels. Colour: RAL 9016.
� Compact design for installation where space islimited.
� Adjustable mounting brackets for optimisation ofair stream.
� Easy access to connections.
Approved by SEMKO and CE compliant
Air velocity profile
Thermozone® AC 300/WAC 300AIR CURTAINS FOR DOORWAYS BETWEEN 2.5 AND 3.5 METRES
Ambient, no heat
Hot water heat
Electrical heat 8-12 kW
Lengths: 1 and 1.7 metres
63
THERMOZONE AC 300/ WAC 300
Frico AB, Box 102, SE-433 22 Partille � Tel: +46 31-336 86 00 � Fax: +46 31-26 28 60 � mailbox@frico.se � www.frico.seDesign and specifications are subject to change without notice.
Thermozone 300 air-curtains are specifically designed toprotect and heat the exposed entrances of shopping mallsand department stores and will perfectly complementautomatic sliding doors and double door entry systems.
This H&M store occupies a prime location in the heart ofStockholm. The use of Thermozone 300 air curtains toreplace doors in an eight-meter wide entrance has enabledunhindered customer access and improved the potential ofthis presitgious site.
Thermozone 300 can bemounted vertically at theside of an entrancedoorway and shielded fromshopping carts or smallertrucks using an optionalbarrier. With the telescopehood between the topmostunit and the ceiling, and acovering hoop between theunits, you get anaesthetically pleasinginstal lat ion.
At the Golden GateVIP entrance, at theStockholm GlobeArena, the red carpet isalways rolled out.Every measure hasbeen taken to ensurethat guests feel a littleextra welcome,including twoThermozone AC300units to ensure that thewelcome is alwayswarm.
Smaller industrydoors are effectivelyprotected by aThermozone AC/WAC300. A pleasantand draught-freeworking environmentcan be maintainedeven when the doorsare frequentlyopened.
At a loading bay, doors areoften open for prolongedperiods. Cold draughts canthen significantly effect theinternal temperature.Thermozone 300 is anexcellent complement togaiters in counteractingdraughts and saving energy.
64
THERMOZONE AC 300/ WAC 300
Frico AB, Box 102, SE-433 22 Partille � Tel: +46 31-336 86 00 � Fax: +46 31-26 28 60 � mailbox@frico.se � www.frico.seDesign and specifications are subject to change without notice.
Thermozone AC 300 without heat
Type Output stages Air flow Sound level Voltage Amperage Length Weight[kW] [m3/h] [dB(A)] [V] [A] [mm] [kg]
AC301 0/ 900/1800 44/62 230V~ 1 .6 1000 3 9
AC302 0/ 1300/2700 45/63 230V~ 2 .5 1670 5 7
Protection class AC300 without heat: (IP24), splash-proof design.
Thermozone AC 300 with electrical heating
Type Output stages Air flow Dt * 1 Sound level Voltage [V] Voltage[V] Length Weight[kW] [m3/h] [°C] [dB(A)] Amperage[A] Amperage[A] [mm] [kg]
(control) (heat)
AC308 0/ /4/8 900/1800 27/13 44/62 230V~/1 .6A 400V3~/11 .6A 1000 4 4
AC312 0/ /6/12 1300/2700 27/13 45/63 230V~/2 .5A 400V3~/17 .3A 1670 6 4
*1) ∆t = temperature rise of passing air at maximum heat output and lowest/highest air flow.
Protection class AC 300 with electrical heating: (IP24), splash-proof design.
Thermozone WAC 300 with hot water heating
Type Air flow Water volume Sound level Voltage Amperage Length Weight[m3/h] [l] [dB(A)] [V] [A] [mm] [kg]
WAC301 800/1700 2 .5 44/62 230V~ 1 .6 1000 5 1
WAC302 1200/2500 3 .5 45/63 230V~ 2 .5 1670 7 4
WAC301V 800/1700 2 .5 44/62 230V~ 1 .6 1000 5 1
WAC302V 1200/2500 3 .5 45/63 230V~ 2 .5 1670 7 4
For vertical mounting: WAC301V and WAC302V.Protection class WAC300, with hot water heating: (IP24), splash-proof design.For information on heat output, see output charts on page 71.WAC301, WAC302 are approved by SEMKO and CE compliant.WAC301V, WAC302V are CE compliant.
TECHNICAL SPECIFICATIONS
65
THERMOZONE AC 300/ WAC 300
Frico AB, Box 102, SE-433 22 Partille � Tel: +46 31-336 86 00 � Fax: +46 31-26 28 60 � mailbox@frico.se � www.frico.seDesign and specifications are subject to change without notice.
985 / 1670
975 / 1640640
400
360
Thermozone AC 300
580
400490
335
ø 11
ø 20
POSITIONING, MOUNTING AND INSTALLATION
Different unit lengthsensures coverage of all doorwidth.
Installaton in false ceiling.
DIMENSIONS
Mounting above doorwayWith the supplied mounting consoles, ThermozoneAC/WAC300 units may be fitted in several ways: onthe wall, on the ceiling, on a cable ladder, etc. Theconsoles make it possible to angle the unit for optimalefficiency. They can also be mounted in false ceilings,see sketch nr 2. Among the hot water heated models,WAC301 and WAC302 are mounted in horizontalpostion above the opening. For minimum mountingdistance to doorway, see sketch nr 1 for theelectrically heated models. The units must not bemounted directly below a power point. For maximumperformance the units should cover the whole widthof the opening and be fitted as close to the openingas possible. Several units can be mounted next toeach other to form a continuous air curtain.
Mounting below ceiling-mounted sliding doorsWhen mounting above openings with ceiling-mounted sliding doors, a square-shaped air curtain
Two towers of verticallymounted, with sideblowingunits.
unit cannot be positioned close enough to theopening because of the opening radius of the slidingdoor. The adaption set AXT401/402 is dome-shapedand may therefore be positioned up against the doorwith the outgoing air stream very close to theopening.
Mounting at the side of the openingWhen space above the doorway is limited, modelsWAC301V and WAC302V can be mounted vertically,thus creating a side blowing air stream. Mountingplates AVMP300 are mounted between units andbetween the lowest unit and the floor. For minimummounting distance to doorway, see sketch nr 1 for theelectrically heated models. For maximum performancethe units should cover the whole height of theopening and be fitted as close to the opening aspossible. Several units can be mounted on top of eachother to form a continuous air curtain. Maximumbuilding height for vertical units without structuralsupport, is 3.5 metres.
66
THERMOZONE AC 300/ WAC 300
Frico AB, Box 102, SE-433 22 Partille � Tel: +46 31-336 86 00 � Fax: +46 31-26 28 60 � mailbox@frico.se � www.frico.seDesign and specifications are subject to change without notice.
490
min 300
580
Thermozone AC 300
35 30 35430 1070
1120
945
Connection DN20 (¾�)Inside thread
Sketch 2: Mounting in false ceiling
Sketch 3: WAC300, water connection on the top side to theright
Sketch 1: Minimum distance to wall 300 mm
Connection AC 300 The appliance should be preceded by a triple poleswitch with at least 3 mm breaking gap. Theconnection should be made with a cable type S05VV-U, A05VV-R or similar, through knock outs on the topside of the unit (2 x ø38 mm and 3 x ø29 mm). Forconnection to the supply terminal block, a cable ofmaximum 16 mm2 is used. For connection to thecontrol terminal block, a cable of maximum 6 mm2 isused. For units with electrical heating, power andvoltage should be supplied in different connectionareas. See wiring diagram at page 74-76.
Connection WAC 300 The appliance should be preceded by a triple poleswitch with at least 3 mm breaking gap. Theconnection should be made with a cable type S05VV-U, A05VV-R or similar, through ø29 mm knock outs onthe top side of the unit. For connection to the controlterminal block, a cable of maximum 6 mm2 is used.Connections (DN20 (3/4�), inside thread) to the waterheating coil are located on the top of the unit. Seesketch 3 and wiring diagrams at page 76-77. Thesupplied 0.8 metre flexible hoses, permit the unit to betilted.
Sketch 4: Adaptation set AXT401/402
67
THERMOZONE AC 300/ WAC 300
Frico AB, Box 102, SE-433 22 Partille � Tel: +46 31-336 86 00 � Fax: +46 31-26 28 60 � mailbox@frico.se � www.frico.seDesign and specifications are subject to change without notice.
REGULATION ALTERNATIVES
Air curtains without heat :Fan speed regulationWhen the gate opens and closes, the position limitswitch signals on and off. When on, the fan speed isregulated with a suitable fan speed regulator.
Complete regulation kit:� AGB304, position limit switch� ACR304, 4-stage regulator or
ACR3042, 4-stage regulator high/low speed orACR3042T1, 4-stage regulator high/low speedwith time relay or2221AG, variable fan speed regulator
Air curtains with electrical heating :Fan speed and thermostat regulation with positionlimit switchWhen the gate opens and closes, the position limitswitch signals on and off. When on, the fan speed isregulated with a suitable fan speed regulator. The2-stage room thermostat controls the heat supply intwo stages (0, 1/2, 1/1). The output may be manuallycontrolled with an output selector.
Complete regulation kit:� AGB304, position limit switch� ACR304, 4-stage regulator or
ACR3042, 4-stage regulator high/low speed orACR3042T1, 4-stage regulator high/low speedwith time relay orFRE6, digital variable fan speed regulator
� KRT2800, 2-stage thermostat orRTI2, electronic 2-stage thermostat
� EV300, output selector
ACCESSORIES
RTI2, electronic 2-stage thermostat Regulates the heat. Adjustable temperature differencebetween the stages (1�10°C). Setting range 5�35°C.For electrically heated air curtains (AC308, AC312).Protection class: splash-proof design (IP44).
RTE102, electronic thermostat Opens/closes water valves and starts/stops fans.Internal temperature setting 7�35°C. Delivered withcovering frame. Used with electrically heated aircurtains (WAC301, WAC302, WAC301V, WAC302V).Protection class: normal design (IP30).
For further alternatives: see section on Thermostats.
KRT2800, 2-stage thermostat Regulates the heat. Adjustable temperature differencebetween the stages (1� 4°C). Setting range 0�40°C.For electrically heated air curtains (AC308, AC312)Protection class: jet-proof design (IP55).
KRT1900, capillary tube thermostat Opens/closes water valves and starts/stops fans. Athermostat with alternating relay for control of heatand fans. For hot water heated air curtains (WAC301,WAC302, WAC301V, WAC302V). Protection class: jet-proof design (IP55).
KRT1900/2800 RTE102RTI2
Air curtains with hot water heating :Fan speed and thermostat regulation with positionlimit switchWhen the gate opens and closes, the position limitswitch signals on and off. When on, the fan speed isregulated with a suitable fan speed regulator. Theheat supply is controlled by thermostat and by a setof valves. The output may be manually controlledwith an output selector.
Complete regulation kit:� AGB304, position limit switch� ACR304, 4-stage regulator or
ACR3042, 4-stage regulator high/low speed orACR3042T1, 4-stage regulator high/low speedwith time relay or2221AG, variable fan speed regulator orFRE6, digital variable fan speed regulator
� KRT1900, capillary tube thermostat orRTE102, electronic thermostat
� VR20/25, valve set orTVV20/25, valve and SD20, actuator
68
THERMOZONE AC 300/ WAC 300
Frico AB, Box 102, SE-433 22 Partille � Tel: +46 31-336 86 00 � Fax: +46 31-26 28 60 � mailbox@frico.se � www.frico.seDesign and specifications are subject to change without notice.
AGB304, position limit switchStarts the air curtain or activates a fan speed regula-tor when the door opens. When the door closes, itshuts the air curtain off or signals to the regulator.
ACR304, 4-stage regulator With ACR304, the fan speed can be adjusted in 4stages to achieve optimal performance and protectionat different door heights. The fan is turned off whenthe door closes. The regulator controls a maximum of5�7 units. Max input 14 A. Protection class: splash-proof design (IP 44).
ACR3042, 4-stage regulator high/low speed With ACR3042, the fan speed can be adjusted in 4stages to achieve optimal performance and protectionat different door heights. One speed is selected forwhen the gate is open and a lower speed is selectedfor when the gate is closed. The regulator controls amaximum of 5�7 units. Max input 14 A. Protectionclass: splash-proof design (IP 44).
ACR3042T1, 4-stage regulator
high/low speed with time relay With ACR3042T1, the fan speed can be adjusted in 4stages to achieve optimal performance and protectionat different door heights. One speed is selected forwhen the gate is open and a lower speed is selectedfor when the gate is closed. ACR3042T1 is equippedwith a time relay. When the gate is closed, the fan willremain at the selected speed for a desired period. Thisfunction is particularly useful when a gate isfrequently opened and closed. The regulator controlsa maximum of 5�7 units. Max input 14 A. Protectionclass: splash-proof design (IP 44).
2221AG, Variable fan speed regulator Single-phase thyristor for variable fan speed controland for switching off and on. For surface mounting.Fits in rectangular mounting case. The regulatorcontrols a maximum of 2�3 units. Max input 5 A. Itregulates hot water heated units (WAC301, WAC302,WAC301V, WAC302V) and units without heat (AC301,AC302). Protection class: splash-proof design (IP 44).
FRE6, digital variable fan speed regulator The FRE6 has two different regulation programs tocontrol the air curtain. The UT-regulation that iscontrolled by the door contact, room thermostat andthe outdoor temperature - and the IT-regulation thatis controlled by the door automation. Regulates amaximum of 1-3 units. Max input 6 A. A slave unitmust be used with amperage above 6 A . FRE6regulates hot water heated units (WAC301, WAC302,WAC301V, WAC302V) and electrically heated units(AC308, AC312). Protection class: splash-proofdesign (IP 54).
EV300, output selector Electrically heated units (AC308, AC312) can becontrolled with the output selector EV300. Outputstages: 0�1/2�1/1. Protection class: splash-proofdesign (IP 44).
AGB304 ACR304 2221AG FRE6ACR3042 / ACR3042T1 EV300
69
THERMOZONE AC 300/ WAC 300
Frico AB, Box 102, SE-433 22 Partille � Tel: +46 31-336 86 00 � Fax: +46 31-26 28 60 � mailbox@frico.se � www.frico.seDesign and specifications are subject to change without notice.
VR 20/25, valve set For regulation of water flow to hot water heatedair curtains.
The valve set consists of the following:� AV20/25, stop valve� JV20/25, adjustment valve� TRV20/25, on/off 3-way motor valve� BPV10, by-pass valve� SD20, actuator on/off 230V~
The stop valve (AV20/25) consists of a ball valvewhich is either open or closed. It is used to turn thewater flow off and on. The water flow can be fine-tuned manually with the adjustment valve (JV20/25).It can also be completely turned off. Through apressure outlet the flow can be measured. The kvvalue for JV20 is 0,13�5,9 and for JV25 0,17� 8,52.The 3-way motor valve (TRV20/25) consists of anactuator and a housing. When the TRV20/25 isclosed, the flow through the by-pass valve is low toensure presence of hot water in the heating coil. Thisleads to instant heat supply when needed and somedegree of frost protection. Actuator SD20 works on/off.
The valve set is available with two different valvedimensions: VR 20 - DN20 (3/4�) and VR 25 - DN25(1�). The by-pass valve dimension is DN10 (3/8�). Toregulate VR20/25, a suitable thermostat has to beadded.
TVV20/25, 2-way regulation valve TVV20 has a pipe dimension of DN20 (3/4�) andTVV25 of DN25 (1�). Pressure class PN16. Maximumpressure 2 MPa (20 bar).Maximum pressure fall TVV20: 100 kPa (0,1 bar)Maximum pressure fall TVV25: 62 kPa (0,062 bar)The kv-value is adjustable in 3 stages:
SD20, actuator on/off 230V~ SD20 regulates the heating. Works on/off. A 5 secondclosing of the valves prevents sudden pressurechanges in the pipe system. (IP40).
TVV20/25, 2-way regulation valve and SD20, actuatorprovide a basic form of water regulation without thepossibility of adjusting or shutting the water flow off.A suitable thermostat is choosen to regulate TVV20/25 and SD20.
Pos. 1 Pos. 2 Pos. 3
TVV20 kv 1,6 kv 2,5 kv 3,5
TVV25 kv 2,5 kv 4,0 kv 5,5
SD20JV20/25 TVV20/25AV20/25
TRV20/25 BPV10
TVV20/25
SD20
KRT, RTE
BPV10
AV20/25
JV20/25
TVR20/25
KRT
VR
20
/25
SD20
230V ~230V ~
C̊ C̊
Thermozone AC 300 Thermozone AC 300
70
THERMOZONE AC 300/ WAC 300
Frico AB, Box 102, SE-433 22 Partille � Tel: +46 31-336 86 00 � Fax: +46 31-26 28 60 � mailbox@frico.se � www.frico.seDesign and specifications are subject to change without notice.
Type Description HxWxD[mm]
KRT2800 2-stage thermostat 165x60x57
KRT1900 Capillary tube thermostat 165x60x57
RTI2 Electronic 2-stage thermostat 150x80x50
RTE102 Electronic thermostat 71x71x28
ABG304 Position limit switch
ACR304 4-stage regulator 100x80x90
ACR3042 4-stage regulator high/low speed 213x155x110
ACR3042T1 4-stage regulator high/low speed with time relay 213x155x110
2221AG Variable fan speed regulator 170x85x63
FRE6 Digital variable fan speed regulator 180x210x110
EV300 Output selector 100x80x90
VR20 Valve set, connection DN20
VR25 Valve set, connection DN25
TVV20 2-way valve, connection DN20
TVV25 2-way valve, connection DN25
SD20 Actuator on/off
22003 False ceiling grille 1192x192
22004 False ceiling grille 1515x192
AVMP300 Mounting plates
AXT401 Adaptation set for ceiling-mounted sliding doors 1000
AXT402 Adaptation set for ceiling-mounted sliding doors 1670
AXP300 Collision protection
AXB300 Covering hoop
AXH300 Telescope hood
22003 and 22004, false ceiling grillesThere are false ceiling grilles for air intake anddischarge available for mounting the air curtain infalse ceiling systems. Available in 2 sizes.
AVMP300, mounting platesWhen the units are mounted in a standing position atthe side of the door, mounting plates are fittedbetween units and between the lowest unit and thefloor. The mounting plate consists of two parts. Theouter one is secured in the floor or at the top of thelower unit. The inner part is mounted on the underside of the unit that is standing on the floor.
AXP300, collision protectionAXP300 is mounted on the ground next to a standingair curtain unit to prevent it from being hit by trucks,shopping trolleys and similar.
AXB300, covering hoopThe hoop is fitted between standing units to coverthe joint and provide a neat installation.
AXH300, telescope hoodVertically adjustable (between 50 mm and 110 mm). Itis used to cover the space between the ceiling andthe top unit of a vertical installation.
22003/22004 AVMP300 AXP300 AXB300 AXH300AXT401/402
AXT401/402, adaptation setWhen mounting above openings with ceiling-mounted sliding doors, mounting kits are availablethat position the outgoing air stream close to theopening.
71
THERMOZONE AC 300/ WAC 300
Frico AB, Box 102, SE-433 22 Partille � Tel: +46 31-336 86 00 � Fax: +46 31-26 28 60 � mailbox@frico.se � www.frico.seDesign and specifications are subject to change without notice.
OUTPUT CHARTS WATER
Incoming / outgoing water temperature 80/60°CIncoming air temp. = +15°C Incoming air temp. = +20°C
Type Fan Air Output Outgoing Water- Output Outgoing. Water-position flow air temp. flow air temp. flow
[m3/h] [kW] [°C] [l/s] [kW] [°C] [l/s]
WAC301 max 1700 20.5 50.5 0.24 18.5 52.2 0.22
m i n 800 12.2 59.9 0.14 11.1 60.7 0.13
WAC302 max 2500 32.4 53.2 0.38 29.4 54.6 0.35
m i n 1200 19.2 62.6 0.22 17.5 63.0 0.20
WAC301V max 1700 19.1 48.1 0.22 17.2 49.9 0.20
m i n 800 11.5 57.4 0.13 10.4 58.5 0.12
WAC302V max 2500 29.1 49.3 0.34 26.3 51.0 0.31
m i n 1200 17.6 58.4 0.21 16.0 59.3 0.19
Incoming / outgoing water temperature 60/40°CIncoming air temp. = +15°C Incoming air temp. = +20°C
Type Fan Air Output Outgoing Water- Output Outgoing. Water-position flow air temp. flow air temp. flow
[m3/h] [kW] [°C] [l/s] [kW] [°C] [l/s]
WAC301 max 1700 12.4 36.5 0.14 10.4 38.0 0.12
m i n 800 7.5 42.7 0.08 6.3 43.4 0.07
WAC302 max 2500 19.8 38.3 0.23 16.7 39.6 0.19
m i n 1200 12.0 44.4 0.14 10.2 45.0 0.12
WAC301V max 1700 11.5 34.9 0.13 9.6 36.7 0.11
m i n 800 7.1 41.0 0.08 6.0 42.0 0.07
WAC302V max 2500 17.3 35.5 0.20 14.5 37.1 0.17
min 1200 10.3 41.4 0.12 9.1 42.3 0.10
Incoming / outgoing water temperature 60/30°CIncoming air temp. = +15°C Incoming air temp. = +20°C
Type Fan Air Output Outgoing Water- Output Outgoing. Water-position flow air temp. flow air temp. flow
[m3/h] [kW] [°C] [l/s] [kW] [°C] [l/s]
WAC301 max 1700 9.3 31.1 0.07 7.1 32.2 0.05
m i n 800 5.8 36.5 0.04 4.5 36.6 0.03
WAC302 max 2500 15.1 32.8 0.12 11.6 33.7 0.09
m i n 1200 9.5 38.3 0.07 7.4 38.2 0.05
WAC301V max 1700 8.5 29.8 0.06 6.5 31.2 0.05
m i n 800 5.4 35.0 0.04 4.2 35.5 0.03
WAC302V max 2500 12.7 30.0 0.10 9.6 31.3 0.07
m i n 1200 8.2 35.1 0.06 6.3 35.4 0.04
Incoming / outgoing water temperature 55/35°CIncoming air temp. = +15°C Incoming air temp. = +20°C
Type Fan Air Output Outgoing Water- Output Outgoing. Water-position flow air temp. flow air temp. flow
[m3/h] [kW] [°C] [l/s] [kW] [°C] [l/s]
WAC301 max 1700 10.3 32.9 0.12 8.3 34.3 0.09
m i n 800 6.3 38.2 0.07 5.1 38.9 0.06
WAC302 max 2500 16.5 34.5 0.19 13.4 35.8 0.15
m i n 1200 10.1 39.8 0.12 8.3 40.3 0.09
WAC301V max 1700 9.5 31.5 0.11 7.6 33.2 0.09
m i n 800 5.9 36.8 0.07 4.8 37.7 0.05
WAC302V max 2500 14.4 31.9 0.17 11.5 33.5 0.13
m i n 1200 9.0 37.1 0.10 7.3 37.8 0.08
72
THERMOZONE AC 300/ WAC 300
Frico AB, Box 102, SE-433 22 Partille � Tel: +46 31-336 86 00 � Fax: +46 31-26 28 60 � mailbox@frico.se � www.frico.seDesign and specifications are subject to change without notice.
V V
WAC
301
WAC
302
WAC
301V
WAC
302V
0.01 0.1 1.0
1 0
7 0
1
0.1 1.0 1 0
0.1
0.7
0.01
7 0
0.1 1.0 1 0
0.7
0.01 0.1 1.0
1 0
1
0.1
0.01
Water pressure drop over WAC 300 water coil
Water pressure drop over regulations and valves
Pre
ssur
e dr
op [
kPa]
Pre
ssur
e dr
op [
bar]
PRESSURE DROP WATER
Water flow [m3/h]
Water flow [l/s]
Water flow [m3/h]
Pre
ssur
e dr
op [
kPa]
Pre
ssur
e dr
op [
bar]
Water flow [l/s]
The pressure drop is calculated for an average temperature of 70°C (PVV 80/60).
For other water temperatures, the pressure drop is multiplied with the factor K.
Average temp. water °C 4 0 5 0 6 0 7 0 8 0 9 0
K 1.10 1.06 1.03 1.00 0.97 0.93
73
THERMOZONE AC 300/ WAC 300
Frico AB, Box 102, SE-433 22 Partille � Tel: +46 31-336 86 00 � Fax: +46 31-26 28 60 � mailbox@frico.se � www.frico.seDesign and specifications are subject to change without notice.
~N
1 2 3 4
NP 1 2 3 4
NP
L1 N (L2)230 V~
~N
1 2 3 4
NP 1 2 3 4
NP
L1 N (L2)230 V~
AC301�302
AC301�302
AGB304
AC301�302
AC301�302
4321
1 3 5 70
XXX
X
X
XXXX
321 4 5 6 7 8 9NP
NL
L1 N (L2)230 V~
M~ c̊ M~ c̊ M~ c̊
NL L
PTC
2 6 8
1 5 73
AC/WAC300
ACR304AGB304
WIRING DIAGRAMS AC301 AND AC302
Variable fan speed adjustment with thyristor2221AG
Variable fan speed adjustment with thyristor2221AG, start/stop with position limit switchAGB304
Manual 4-stage fan speed regulation with ACR304, start/stop with position limit switch AGB304
AGB304,position limit switch
2221AG,variable fanspeed regulator
2221AG,variable fanspeed regulator
ACR304,4-stage regulator
AGB304,position limit switch
2221AG
2221AG
Max input for the variable fan speed regulator2221AG is 5A. It regulates 3 x AC301 or 2 xAC302.
AC/WAC300
74
THERMOZONE AC 300/ WAC 300
Frico AB, Box 102, SE-433 22 Partille � Tel: +46 31-336 86 00 � Fax: +46 31-26 28 60 � mailbox@frico.se � www.frico.seDesign and specifications are subject to change without notice.
NP 1 2 3 4 5 6 7
4 5 6
10 12 13 14
10 12 13 14
5 1
6 2
L1 L2 L3
400V3~/230V3~
L1 L2 L3
400V3~/230V3~
L1 N (L2)230 V~
L1 N (L2)230 V~
NP1 2 3 4 65 7
c̊
Hi Lo4321
1 3 5 70
XXX
X
X
XXXX
2 6 8
1 5 73
ACR304
EV300
RTI2
AC308/312
AGB304
321 4 5 6 7 8 9NP
NL
L1 N (L2)230 V~
400V 3~/230V 3~
M~ c̊ M~ c̊ M~ c̊
NL L
PTC
4321
1 3 5 70
XXX
X
X
XXXX
230 V3~
123
Hi
Lo
Diff (1-4)K
123
5 1
6 2
6 2O
XX
X
L1 L2 L313 14121110
400 V3~
K2K2
c̊
c̊
2 6 8
1 5 73
ACR304 EV300
KRT2800
AC308/312
AGB304
AC308/312
Manual 4-stage fan speed regulation with ACR304, start/stop with position limit switch AGB304, automatic2-stage heat regulation with thermostat RTI2, output selection 0�½�1 output with EV300
ACR304,4-stage
regulator
AGB304,position limit
switch
EV300,output selector
WIRING DIAGRAMS AC308 AND AC312
Manual 4-stage fan speed regulation with ACR304, start/stop with position limit switch AGB304, automatic2-stage heat regulation with thermostat KRT2800, output selection 0�½�1 output with EV300
EV300,output selector
KRT2800,2-stage thermostat
ACR304,4-stage
regulator
AGB304,position limit
switch
AC308/312
RTI2,electronic2-stagethermostat
AC308/312
75
THERMOZONE AC 300/ WAC 300
Frico AB, Box 102, SE-433 22 Partille � Tel: +46 31-336 86 00 � Fax: +46 31-26 28 60 � mailbox@frico.se � www.frico.seDesign and specifications are subject to change without notice.
NP 1 2 3 4 5 6 7
4 5 6
10 12 13 14
10 12 13 14
5 1
6 2
L1 L2 L3
400V3~/230V3~
L1 L2 L3
400V3~/230V3~
L1 N (L2)230 V~
L1 N (L2)230 V~
NP1 2 3 4 65 7
c̊
Hi Lo3132 33 34 35 36 37 38
1 2 3 4
X
X
X
X
X
X
X
XX
AGB304
ACR3042
EV300
RTI2
AC308 /312
AC308 /312
NP 1 2 3 4 5 6 7
3132 33 34 35 36 37 38
4 5 6
10 12 13 14
10 12 13 14
1 2 3 4
X
X
X
X
X
X
X
XX
123
Hi
Lo
Diff (1-4)K
123
5 1
6 2
L1 L2 L3
400V3~/230V3~
L1 L2 L3
400V3~/230V3~
L1 N (L2)230 V~
6 2O
XX
X
AGB304
ACR3042
EV300
KRT2800
AC308/312
AC308/312
WIRING DIAGRAMS AC308 AND AC312
High/low fan speed with position limit switch AGB304 and ACR3042, automatic 2-stage heat regulationwith thermostat RTI2s, output selection 0�½�1 output with EV300
RTI2,electronic2-stage thermostat
ACR3042,4-stage regulator
AGB304,position limit
switch
EV300,output selector
High/low fan speed with position limit switch AGB304 and ACR3042, automatic 2-stage heat regulationwith thermostat KRT2800, output selection 0�½�1 output with EV300
ACR3042,4-stage
regulator
AGB304,position limit
switch
EV300,outputselector
KRT2800,2-stagethermostat
AC308/312
AC308/312
76
THERMOZONE AC 300/ WAC 300
Frico AB, Box 102, SE-433 22 Partille � Tel: +46 31-336 86 00 � Fax: +46 31-26 28 60 � mailbox@frico.se � www.frico.seDesign and specifications are subject to change without notice.
NP 1 2 3 4 5 6 9
230 V~
NL N U 1 2TK 5 6 101112TK 21222324
NP 1 2 3 4 5 6 9
21
3c̊
TRV/TVV
SD20
NP 1 2 3 4 5 6 7
230 V~
10 12 13 14 L1 L2 L3
400V3~/230V3~
NL N U 1 2TK 5 6 101112TK 21222324
51
62
8 9
6 2O
XX
X
NL 1 2
NP 1 2 3 4 5 6 7 10 12 13 14 L1 L2 L3
400V3~/230V3~
8 9
21
3c̊
WAC301-WAC302V
EV300
FRE6
FRE6
WAC301-WAC302V
AC308/AC312
AC308/AC312
WIRING DIAGRAMS WAC301, WAC301V, WAC302 AND WAC302V
WIRING DIAGRAMS AC308 AND AC312
Outdoor compensated variable fan speed regulation with FRE6
SD20, actuator, on/off, 230V~
TRV/TVV20/25
Outdoor compensated variable fan speed regulation with FRE6, effect limitation with output selectorEV300 in effect stages 0-½-1.
Outdoorsensor
Roomthermostat
Door contact
Outdoorsensor
Roomthermostat
Door contact
AC308-AC312
EV300,output selector
FRE6,dig i ta l
variable fan speedregulator
WAC301(V)/302(V)
FRE6,dig i ta l
variable fan speedregulator
WAC301(V)/302(V)
FRE6 regulates a maximum of 4 x AC308 or 2 xAC312.
FRE6 regulates a maximum of 4 xWAC301(V) eller 2 x WAC302(V)
77
THERMOZONE AC 300/ WAC 300
Frico AB, Box 102, SE-433 22 Partille � Tel: +46 31-336 86 00 � Fax: +46 31-26 28 60 � mailbox@frico.se � www.frico.seDesign and specifications are subject to change without notice.
NP 1 2 3 4 5 6 9
3132 33 34 35 36 37 38
4 5 6 9
1 2 3 4
X
X
X
X
X
X
X
XX
123
12345
L1
230 V~N (L2)
123
12345
4321
1 3 5 70
XXX
X
X
XXXX
321 4 5 6 7 8 9NP
NL
L1 N (L2)230 V~
M~ c̊ M~ c̊ M~ c̊
NL L
PTC
2 6 8
1 5 73
SD20
TRV/TVV
KRT1900
RTE102
ACR304
AGB304
SD20
TRV/TVV
RTE102
KRT1900
WAC301-WAC302V
WAC301-WAC302V
ACR3042
WAC301-WAC302V
AGB304
WIRING DIAGRAMS WAC301, WAC301V, WAC302 AND WAC302V
Manual 4-stage fan speed regulation with ACR304, start/stop with position limit switch AGB304, automaticheat regulation with thermostat RTE/KRT, actuator SD20 and valve TVV20/25
High/low fan speed with position limit switch AGB304 and ACR3042, automatic heat regulation withthermostat RTE/KRT, actuator SD20 and valve TVV20/25
For variable fan speedcontrol, see wiringdiagrams on page 73.
KRT1900,capillary tube
thermostat
RTE102,electronicthermostat
TRV/TVV20/25
SD20, actuator, on/off, 230V~
ACR304,4-stage regulator
ACR3042,4-stage regulator
AGB304,position limitswitch
KRT1900,capillary tube
thermostat
RTE102,electronicthermostat
TRV/TVV20/25,
SD20, actuator, on/off, 230V~
AGB304,position limitswitch
WAC301(V)/302(V)
WAC301(V)/302(V)