UPS-Systems

Transcript of UPS-Systems - Eltek

Page 1: UPS-Systems - Eltek

UPS-Systems

Page 2: UPS-Systems - Eltek

Device Designation EVD-MIN 0.7-3 kVA EVD-MIN 4.5-6 kVA EVD-MID 6.5 – 20 kVA

Rated output power 0.7 – 1.0 – 1.5 – 2.0 – 3.0 kVA 4.5 – 6.0 kVA 6.5 - 8 - 10 – 12 – 15 – 20 kVA

Input

Voltage 120 / 140 / 160-280VAC based on load 160-280VAC 3 x 380 / 400 / 415VAC (three phase with N) ±20%

220 / 230 / 240VAC (one phase with N) ±20%

Frequency 45-65 Hz 45-65 Hz 50-60Hz

Power factor 0.99 0.99 ≥0.99

Softstart yes yes ≥30 sec.

Intermediate circuit

Voltage 36VDC up to 1kVA and 72VDC up to 3kVA 240VDC 480VDC

Charging current 2A 2A 6A

Output

Voltage 200 / 208 / 220 / 230 / 240 VAC ± 1% 200 / 208 / 220 / 230 / 240 VAC ± 2% 220 / 230 / 240V with N

Wave Form sinusoidal sinusoidal sinusoidal

Frequency 50 / 60 Hz ± 1% 50 / 60 Hz ± 1% 50 / 60 Hz ± 0.1%

Crest factor 3:1 (without transformer)

2.5:1 (with transformer)

3:1 3:1

Harmonic distortion < 3% < 3% ≤1% with linear load, ≤3% with distorting load

Overloadable up to 120% 30 sec.

up to 150% 10 sec.

up to 150% 160 sec. 110% 10min. / 150% 5 sec.

By-Pass static switch static switch static switch

Displacement factor cos Phi

CosPhi 0.7 ind. CosPhi 0.7 ind. CosPhi 0.8 ind. up to cosPhi 0.9 cap.

Efficiency > 85% 90%, ECO mode 95% 94%

Output power 0.7 – 3 kVA (0.49 – 2.1 kW) 4.5 – 6 kVA (3.15 - 4.2 kW) 10 – 20 kVA (8 – 16 kW)

Autonomy time upon request upon request upon request

General data

Environmental conditions

Ambient temperature 0-40°C 0-40°C 0-40°C

Altitude max. 3000m above sea level max. 3000m above sea level max. 1000m above sea level (rated power)

Colour black black RAL 7024 (dark grey)

Humidity up to max. 90% up to max. 90% up to max. 90%

Protection class IP 20 IP 20 IP 20

Noise level <50 dBA <50 dBA <52 dBA

Standards CE, UL, EN62040-1-1, IEC60950-1,

EN62040-2, EN61000-3-2, EN61000-3-3,

FCC Class A, ISO9001, EN62040-3

CE, UL, EN62040-1-1, UL 1778,

EN62040-2, EN61000-3-3, FCC Class A,

ISO9001, EN62040-3, EN 61000-4-5

CE, EN62040-1-1, Directive 73/23/EEC,

93/68/EEC, EN62040-2 Cl. 2, Directive

2004/108/EEC, 93/68/EEC, 89/336/

EEC, IEC801-5 (2.2kV/1.2-50μs), ISO9001,

EN62040-3

Display and user interface RS232, UPSilon 2000 with cable RS232, UPSilon2000 with cable RS232, Multilink CD, communication

software, connection cable

Options Com Slot for 2. RS-232 or SNMP or relay

card, galvic isolation transformer,

single control output socket

Com Slot for 2. RS-232 or SNMP or relay

card, galvanic isolation transformer,

up to 4 UPS systems in parallel

SNMP adapter, Modbus, Profibus, remote

signalling, Shutdown-Software

Dimensions (W x H x D) 0.7-1kVA: 88 x440x405mm

1.5-3kVA: 88x440x650mm

(as tower UPS without transformer)

176x440x680mm

(as tower UPS without transformer)

840 x 930 x 320mm

UPS-Systems

Right to make technical changes reserved

Page 3: UPS-Systems - Eltek

Device Designation EVD-MAX 10 – 80 kVA EVD-MAX 100-800 kVA AMP 10-250 kVA

Rated output power 10 – 15 – 20 – 30 – 40 – 60 – 80 kVA 100 – 120 – 160 – 200 – 250 – 300 – 400 –

500 – 600 – 800 kVA

10 – 15 – 20 – 25 - 30 – 40 – 50 – 60 - 80 –

100 - 120 – 150 – 160 – 200 - 250 kVA

Input

Voltage 3 x 400 VAC (three phase with N) ±20% 3 x 380 / 400 / 415 VAC (three phase with N)) 3 x 380 / 220 with N, 3 x 400 / 230 with N,

3 x 415 / 240 with N

Frequency 50-60 Hz 45-65 Hz 35-70 Hz

Power factor 0.83 (0.9 with filter) 0.95 - 0.99 0.99

Softstart ≥30 sec. ≥30 sec. ≥30 sec.

Intermediate circuit

Voltage 384 VDC 396 VDC up to 200kVA, 480 VDC starting

from 250kVA

360-600 VDC

Charging current 9-35 A 24-128 A 6-10 A (for each unit)

Output

Voltage 3 x 380 / 400 / 415VAC

(three phase with N) ±1%

3 x 380 / 400 / 415VAC

(three phase with N) ±1%

3 x 380 / 220 with N, 3 x 400 / 230 with N,

3 x 415 / 240 with N

Wave Form sinusoidal sinusoidal sinusoidal

Frequency 50 / 60 Hz ± 1% 50 / 60 Hz ± 1% 50 / 60 Hz

Crest factor 3:1 3:1 3:1

Harmonic distortion 2% with linear load, 5% with distorting load <1 % with linear load 2% with linear load, 4% with distorting load

Overloadable 110% 5 h / 125% 10min. / 150% 1min. /

200% 7 sec.

110% 60min. / 125% 10min. / 150% 1min. /

200% 7 sec.

125% 10min. / 150% 1min.

By-Pass static switch / manual static switch / manual static switch / manual

Displacement factor cos Phi

CosPhi 0.8 ind. CosPhi 0.8 ind. up to 0.9 cap. CosPhi 0.8 ind. up to 0.9 cap.

Efficiency 92% 94% 96%

Output power 10 – 80 kVA (8 – 64 kW) 100 – 800 kVA (80 – 640 kW) 10 – 250 kVA (8 – 200 kW)

Autonomy time upon request upon request upon request

General data

Environmental conditions

Ambient temperature 0–40°C 0–40°C 0–40°C

Altitude max. 1000m above sea level (rated power) max. 1000m above sea level (rated power) max. 1000m above sea level (rated power)

Colour RAL 7035 RAL 7035 Front: RAL 9007, side walls: Graffito grey

Humidity up to max. 95% up to max. 95% up to max. 95%

Protection class IP 20 IP 20 IP 20

Noise level 54 – 62 dBA 63 – 78 dBA 55 - 65 dBA

Standards CE, EN50091-1, EN50091-2, EN61000 4/5,

ISO9001,

EN62040-3

CE, ISO9001, EN62040-1, EN62040-2,

EN62040-3

CE, GOST through TÜV, ISO9001,

EN62040-1-1, EN60950-1, EN62040-2,

EN61000-3-3, EN61000-6-2,

EN61000-6-4, EN62040-3

Display and user interface LC Display, RS232, potential free dry

contacts, automatic battery test

LC Display, RS232, potential free dry

contacts, automatic battery test

LC Display (PMD) for each unit, RS232, 10

potential free dry contacts

Options parallel operation, remote signalling,

battery cabinet, communication

software, battery extension, 12-pulse

converter, central battery (parallel

operation)

parallel operation, remote signalling,

battery cabinet, communication

software, battery extension, 12-pulse

converter, THDi-filter, central battery

(parallel operation)

Additional slot for „COM-Cards“ (SNMP,

Elvawatch)

Dimensions (W x H x D) EVD-MAX 10-40: 555 x 1200 x 720mm

EVD-MAX 60-80: 1070 x 1400 x 740mm

EVD-MAX 100: 1070 x 1900 x 800mm

EVD-MAX 120-200: 1200 x 1900 x 800mm

EVD-MAX 250-300: 1630 x 1900 x 850mm

EVD-MAX 400: 1630 x 1900 x 1000mm

EVD-MAX 500-600: 3200 x 1900 x 1000mm

EVD-MAX 800: 4400 x 1900 x 1000mm

Mini: 550 x 1975 x 780mm

Maxi: 730 x 1975 x 800mm

UPS-Systems

Right to make technical changes reserved